Pressure Controller Nozzle & Tubing Positions

Page 1

PROPORTIONAL ONLY CONTROLLER TUBING & NOZZLE POSITIONS, APPLIES TO FISHER 4150K/KR, MALLARD 3350D/3350R & NORRISEAL 4700 & 4900

RELAY TUBING

PROPORTIONAL TUBING

REVERSE ACTING REVERSING BLOCK SCREW

NOTE: LOWER POSITION USED

NOZZLE NOTE: BELOW FLAPPER

BELLOWS

(INCREASE IN SENSING LINE PRESSURE RESULTS IN DECREASED OUTPUT SIGNAL OR DECREASE IN SENSING LINE PRESSURE RESULTS IN INCREASED OUTPUT SIGNAL)

REVERSING BLOCK

FLAPPER

RELAY TUBING

PROPORTIONAL TUBING

DIRECT ACTING REVERSING BLOCK

NOTE: UPPER POSITION USED

NOZZLE NOTE: ABOVE FLAPPER

(INCREASE IN SENSING LINE PRESSURE RESULTS IN INCREASED OUTPUT SIGNAL OR DECREASE IN SENSING LINE PRESSURE RESULTS IN DECREASED OUTPUT SIGNAL)

BELLOWS

REVERSING BLOCK SCREW

FLAPPER Courtesy of

LEGEND: P ~ PROPORTIONAL BELLOWS X ~ NO PRESSURE