1 minute read

Gateway

Next Article
Disclaimer

Disclaimer

Working with Gateway

Purpose

Enabling projects with a coordinating role of a gateway and dashboard.

How to do?

• The Philips MasterConnect system can be setup in standalone way and works without a gateway. Out of the box, MasterConnect products -EasyAir SNS210

MC and Xitanium Wireless Drivers- can be commissioned via the Philips

MasterConnect app but are also open for joining Zigbee networks of gateways from partner companies like ubisys technologies GmbH. • To commission Philips MC wireless products with partner gateways, software and apps of the partners need to be used. • When using a customized profile make sure that in the ubisys app the steering interval is set to 30s and that the parameter “suppress insignificant changes” is put to “no”. • Please refer to gateway suppliers for more information on how to set up a system with their gateway.

Remark:

• If a device is coupled automatically to an (arbitrary) open Zigbee network, it can be recommissioned with the Philips MasterConnect app. This is a desired situation. If a device is coupled automatically to a trusted Gateway, you can recommission it as well. This is an undesired situation and will be repaired in the future via the Gateway. • If ZGP-sensors are used, the refresh time for lighting profiles is limited to ≥2.5 minutes.