DESN10032 Technology & Design Studio 01 Coach House Extension & Refurbishment - 52 Loughbourgh Road, West Bridgeford, Nottingham.
By Craig J Gregory - AT year 01
1
Craig Greogry - N0726862
Technology & Design Studio 01.
CONTENTS: COVER PAGE 01 CONTENTS PAGE 02 COVER LETTER 03-04 BUILDING REGULATIONS APPLICATION 05-07 DRAWING ISSUE SHEET 08
DOOR & WINDOW SCHEDULE 46 ELECTRICAL LAYOUT 47 HEATING SYSTEMS LAYOUT 48 DRAINAGE LAYOUT 49
EXTERNAL RENDERED IMAGE A 50 EXTERNAL RENDERED IMAGE B 51 KITCHEN AREA RENDERED IMAGE 52 DESIGN DATA 09 FOUNDATION CALCULATIONS 10-12 BEDROOM RENDERED IMAGE 53 U-VALUE CALCULATIONS 13-18 EXISTING DRAWING PACKAGE COVER 19 LOCATION PLAN 20 BLOCK PLAN 21 SITE PLAN 22 GROUND FLOOR PLAN 23 FIRST FLOOR PLAN 24 EAST & WEST ELEVATION 25 NORTH & SOUTH ELEVATION 26 PROPOSED DRAWING PACKAGE COVER 27 BLOCK PLAN 28 SITE PLAN 29 FOUNDATION PLAN 30 SOLEPLATE LAYOUT 31 GROUND FLOOR PLAN 32 FIRST FLOOR PLAN 33 FLOOR JOIST LAYOUT 34 ROOF JOIST LAYOUT 35 SECTION A-A 36 SECTION B-B 37 TECHNICAL CUT 38 DETAIL 01 - RIDGE TECHNICAL DETAIL 39 DETAIL 02 - SUSPENDED FLOOR TECHNICAL DETAIL 40 DETAIL 03 - SOLA-TUBE TECHNICAL DETAIL 41 EAST ELEVATION 42 SOUTH ELEVATION 43 WEST ELEVATION 44 NORTH ELEVATION 45 2
Craig Greogry - N0726862
Technology & Design Studio 01.
Spartan Construction & Design
SDC-CHE-52/001 SDC-AT-001
Professionalism from Start to Finish.
Unit 258, “Creative Name” Industrial Estate Nottingham, NG1 4ED 0115 9548 7458 SpartanConstruction&Design-NG@Outlook.com SpartanConstrution&Design.co.uk Planning Department Rushcliffe Borough Council Rushcliffe Arena Rugby Road West Bridgford NOTTINGHAM NG2 7YG 17h May 2018 Dear Sir/Madam,
PROPOSAL DESCRIPTION A two storey habitable extension to be constructed upon an existing Victorian Coach house, located at the rear of the adjacent property (No. 52, Loughborough Road.) The client wishes to conduct these improvements to allow greater longevity and a more suitable habitable dwelling, for the next occupant & future increase in property valuation. These aspects are to be considered and requested by the client:
1 No. Additional bedroom & En-suite Extended communal living area Open plan kitchen & Dining area improvements Proposed new roof layout & design. Improved services & drainage layout to be installed/rectified. Addition of renewable energy services & methods. o Solar photovoltaic cells. o Rain collection system. External landscaping & improved land drainage (Flood prevention.)
The dwelling is located at: The Coach House, 52 Loughborough Road West Bridgford, Nottingham NG2 7JJ Accessible via a hardstanding/shingle driveway running through No. 52’s existing property boundaries are adjacent to the main transit route (Loughborough Road)
3
Craig Greogry - N0726862
Technology & Design Studio 01.
Please find the attached the following documents in relation to the proposed planning application described above including the following: 1. Building Regulations Application 2. Drawing Issue Sheet 3. Coach House Extension DWG package Construction Drawings: a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. r. s. t. u. v. w. x. y. z.
Location Plan Existing Block Plan Existing Site Plan Existing Ground Floor Plan Existing First Floor Plan Existing East & West Elevation Existing South & North Elevation Proposed Block Plan Proposed Site Plan Proposed Foundation Plan Proposed Soleplate Layout Proposed Ground Floor Plan Proposed First Floor Plan Proposed Floor Joist Plan Proposed Roof Joist Plan Section A-A Section B-B Technical Section Detail 01 - Ridge Technical Detail Detail 02 - Suspended Floor Technical Detail Detail 03 - Sola-tube Technical Detail Proposed East Elevation Proposed South Elevation Proposed West Elevation Proposed North Elevation Proposed D & W Schedule
– SDC-AT-C-2018-001-01 – SDC-AT-C-2018-001-02 – SDC-AT-C-2018-001-03 – SDC-AT-C-2018-001-04 – SDC-AT-C-2018-001-05 – SDC-AT-C-2018-001-06 – SDC-AT-C-2018-001-07 – SDC-AT-C-2018-001-08 – SDC-AT-C-2018-001-09 – SDC-AT-C-2018-001-10 – SDC-AT-C-2018-001-11 – SDC-AT-C-2018-001-12 – SDC-AT-C-2018-001-13 – SDC-AT-C-2018-001-14 – SDC-AT-C-2018-001-15 – SDC-AT-C-2018-001-16 – SDC-AT-C-2018-001-17 – SDC-AT-C-2018-001-18 – SDC-AT-C-2018-001-19 – SDC-AT-C-2018-001-20 – SDC-AT-C-2018-001-21 – SDC-AT-C-2018-001-22 – SDC-AT-C-2018-001-23 – SDC-AT-C-2018-001-24 – SDC-AT-C-2018-001-25 – SDC-AT-C-2018-001-26
Mechanical / Electrical Drawings: a. Proposed Drainage Layout b. Proposed Heating Layout c. Proposed Electrical Layout
– SDC-AT-M-2018-001-01 – SDC-AT-M-2018-001-02 – SDC-AT-E-2018-001-01
4. £170 cheque towards the relevant planning fee. If you require any further information, please do not hesitate to contact me. Yours faithfully, Mr Craig J Gregory.
Spartan Construction & Design.
4
Craig Greogry - N0726862
Technology & Design Studio 01.
Building Regulations Application
Building Regulations Application Form The Building Regulations 2010 Please indicate application type:
A) Full Plans Submission (Any new work)
B) Building Notice (Domestic new work only)
C) Regularisation Certificate (Existing unauthorised work)
D) Partnership
1 Applicants details Name:
Mr Adam O’Roake
Address:
52 Loughborough road, West Bridgford, Nottingham Postcode:
Telephone:
N/A
email:
NG2 7JJ N/A
2 Agents details Name: Address:
Mr Craig Gregory. Unit 258 “Creative Name” Industrial Unit, Nottingham. Postcode:
Telephone: 0115 1234 5677
NG1 4ED
email: SpartenDesign&Construction-NG@outlook.com
3 Location of site to which the building work relates Address of site: The Coach House, 52 Loughborough road, West Bridgford, Nottingham Postcode:
NG2 7JJ
4 Proposed / Completed works Description of proposed / completed building work:
Two storey extension of existing Victorian coach house, at rear of No. 52 Property. To consist of a Timber stud frame construction, with an extended living area/study, an additional bedroom with ensuite & renovation to existing floor plan & stair well. Bringing in line with current BR & standards for domestic living; existing services are to be updated in line with current regulation.
5 Declaration This application is deposited in relation to the building work as described above. It is submitted in accordance with Regulations 12(2) and 18 where relevant and is accompanied by the appropriate charge.* I understand that further applicable charges (such as inspection fees) may become payable by the building owner following the first inspection undertaken by the local authority. I / we apply for Full Plans Building Regulation Approval / Building Notice Acceptance / Regularisation Certification / Partnership Application as described on this form and as detailed on any supplementary documents. Signature:
5
X
On behalf of:
Craig Greogry - N0726862
Mr Adam O’Roake (Mr Craig Gregory)
Technology & Design Studio 01.
Date:
6
17 / 05 / 2018
Insert applicants name where the declaration is made by an agent
Craig Greogry - N0726862
Technology & Design Studio 01.
Important Information 1. By completing and submitting this form, you are giving notice of your intention to carry out building work and deposit the attached drawings and other documents as required by the building regulations. 2. In the case of a Building Notice, in accordance with Building Regulation 12 (2) (a) it is your intention to carry out the domestic building work described in Section 3 and 5, of the Building Regulations 2010. 3. In the case of a Full Plans Application, this notice is being given in relation to the building work as described, and is being submitted in accordance with Regulation(2)(b) and is accompanied by the appropriate charge. Please understand that further charges (Inspection Charges) will normally be payable following the first inspection by the local authority. By completing and signing this form, the Council accepts that you have consented to the time period for consideration of the application being extended to two months and that, if appropriate you wish the application to be passed with conditions. 4. In the case of an application for Regularisation, this notice, given in relation to the work described, is submitted in accordance with Regulation 18 and is accompanied by the appropriate charge (and plans where applicable). Please understand that the local authority may require you to take such reasonable steps (e.g. opening up of unauthorised work for inspection, making tests and taking samples) as appropriate, to establish compliance or otherwise. 5. In all cases, the Council may require the submission of further information to show compliance with the Building Regulations.
Fire Consultation Applicant(s) should be aware that under the terms of The Building Act 1984, Section 15, the Local Authority will as required consult with the Fire and Rescue Service and pass on those details that you submit on your application form for the purposes of determining the Building Regulations application. Without this data collection, we could not process the application. Applicant details are only passed on to the statutory consultee(s). If you have any queries regarding this consultation process please telephone 01623 457387. Further details regarding information rights are available on the Information Commissioner’s Office website at www.ico.org.uk
Sewerage Consultation Applicant(s) should be aware that under the terms of The Building Regulations 2010, the Local Authority will as required consult with the Sewerage undertaker and pass on those details that you submit on your application form for the purposes of determining the Building Regulations application. Without this data collection, we could not process the application. Applicant details are only passed on to the statutory consultee(s). If you have any queries regarding this consultation process please telephone 01623 457387. Further details regarding information rights are available on the Information Commissioner’s Office website at www.ico.org.uk
Further Information More details about the Building Control Service here at Nottingham City Council can be found on our website at
http://www.nottinghamcity.gov.uk/planning-andbuilding-control
Nottingham City Council, Loxley House, Station Street, Nottingham, NG2 3NG, T: 0115 876 4447 , E: building.control@nottinghamcity.gov.uk * Please note, Ashfield District Council produces a standard fee sheet with the general charges for commonly undertaken schemes (domestic extensions, garage conversions, etc.), however where necessary we will provide an individual quote on all schemes.
Other Nottinghamshire Local Authority Building Control Teams Ashfield District Council, Council Offices, Urban Road, Kirkby in Ashfield, NG17 8DA, T: 01623 457394, E: bcadmin@ashfield-dc.gov.uk Bassetlaw District Council, Queens Buildings, Worksop, S80 2AH T: 01909 533292, E: building.control@bassetlaw.gov.uk East Midlands Building Consultancy, St.Peters Hill, Grantham, NG31 6PZ T: 03330 038132, E: info@eastmidlandsbc.com Erewash & Broxtowe Building Consultancy, Ilkeston Town Hall, Wharncliffe Road, Ilkeston, DE7 5RP T: 0115 9072244, E: buildingcontrol@erewash.gov.uk Gedling Borough Council, Nottingham Road, Arnold, NG5 6LU T: 0115 9013740, E: buildingcontrol@gedling.gov.uk Mansfield District Council, Chesterfield Road South, Mansfield, NG17 8BH T: 01623 463077, E: pbc@mansfield.gov.uk
SEPTEMBER 2016
7
Craig Greogry - N0726862
Technology & Design Studio 01.
SPARTAN DESIGN & CONSTRUCTION
Unit 258, "Creative Name" industrial Estate, Nottingham, NG1 4ED SDC = Company Initials
DRAWING ISSUE SHEET Coach House Extension & Refurbishment 4B
CLIENT DRAWING NUMBER
DD DATE
PROJECT PROJECT NO:
5
YY
Mr A O'Rouke DRAWING TITLE
17
MM
ISSUED BY SCALE (1:)
SIZE
2018
CJG
LAST REV
SDC-AT-C-2018-C001
Location Plan
1250
A3
A
Xs
SDC-AT-C-2018-C002
Existing Block Plan
500
A3
A
Xs
SDC-AT-C-2018-C003
Existing Site Plan
200
A3
A
Xs
SDC-AT-C-2018-C004
Existing Ground Floor Plans
100
A3
A
Xs
SDC-AT-C-2018-C005
Existing First Floor Plans
100
A3
A
Xs
SDC-AT-C-2018-C006
Existing North & East Elevations
100
A3
A
Xs
SDC-AT-C-2018-C007
Existing South & West Elevations
100
A3
A
Xs
SDC-AT-C-2018-C008
Proposed Block Plan
500
A3
A
Xs
SDC-AT-C-2018-C009
Proposed Site Plan
200
A3
A
Xs
SDC-AT-C-2018-C010
Proposed Foundation Plan
50
A3
A
Xs
SDC-AT-C-2018-C011
Proposed Soleplate Layout Plan
50
A3
B
Xs
SDC-AT-C-2018-C012
Proposed Ground Floor Plan
50
A3
B
Xs
SDC-AT-C-2018-C013
Proposed First Floor Plan
50
A3
A
Xs
SDC-AT-C-2018-C014
Proposed Floor Joist Plan
50
A3
A
Xs
SDC-AT-C-2018-C015
Proposed Roof Joist Plan
50
A3
A
Xs
SDC-AT-C-2018-C016
Proposed Cut A-A
50
A3
A
Xs
SDC-AT-C-2018-C017
Proposed Cut B-B
50
A3
A
Xs
SDC-AT-C-2018-C018
Proposed Construction Strip
20
A3
A
Xs
SDC-AT-C-2018-C019
Detail 01 - Ridge Technical Detail
5
A3
A
Xs
SDC-AT-C-2018-C020
Detail 02 - Suspended Floor Technical Detail
5
A3
A
Xs
SDC-AT-C-2018-C021
Detail 03 - Sola-tube Technical Detail
5
A3
A
Xs
SDC-AT-C-2018-C022
Proposed North Elevations
50
A3
B
Xs
SDC-AT-C-2018-C023
Proposed East Elevations
50
A3
B
Xs
SDC-AT-C-2018-C024
Proposed South Elevations
50
A3
B
Xs
SDC-AT-C-2018-C025
Proposed West Elevations
50
A3
B
Xs
SDC-AT-C-2018-C026
Proposed Door & Window Schedule
2
A3
A
Xs
SDC-AT-E-2018-C001
Proposed Electrical Layout
100
A3
A
Xs
SDC-AT-M-2018-M001
Proposed Drainage Layout
100
A3
A
Xs
SDC-AT-M-2018-M002
Proposed Heating Layout
100
A3
A
Xs
Letter = Drawing Revision
ISSUED TO: PLANNING DEPARTMENT
Xs
CLIENT
Xs
QUANTITY SURVEYOR PROJECT MANAGER
Xs
STRUCTURAL ENGINEER
Xs
M&E ENGINEERS
Xs
TRANSPORT ACOUSTIC CONSULTANT
Xs
N = Number of prints Ne = Negative Xs = Issue Sheet Only Di = Disk Issue eM = eMail F = FTP site
STATUS
PR = Preliminary AC = Approval Comments IN = Information P = Planning FC = Fire Certificate T = Tender C = Construction R = Requested
8
Craig Greogry - N0726862
Technology & Design Studio 01.
Coach House Extension. Proposed Design Data.
Foundation Design 10-12 U-Value Calculations 13-18
9
Craig Greogry - N0726862
Technology & Design Studio 01.
10
Craig Greogry - N0726862
Technology & Design Studio 01.
11
Craig Greogry - N0726862
Technology & Design Studio 01.
12
Craig Greogry - N0726862
Technology & Design Studio 01.
U-Value Calculation Sheet Spartan Construction & Design
Coach house extension - W. Bridgeford
Project: Strucutre:
Professionalism from Start to Finish.
External Wall Coach house extension - W. Bridgeford
DWG REF:
Job Ref: Calc Sheet No. 01 of 06 Checked By: Date: NA 19/05/2018
Surface Resistance - Rse and Rsi From Table 1 BS EN 6946 & Cavity Rcav From Table 2 Material Conductivity - k From B'Regs App Doc L1 2013, Table A19 (or manufacturers literature preferred) R for materials = t/k (t in metres)
-
U = 1/Rtotal
U-Value Calculation Sheet Element
Size (m)
Ref
k
Rsi
Internal Surface
R
Comments
0.130
Table 1. BS 6946
KS (KT-118) Plasterbourd
0.032
R1
0.208
0.154
k From Manufacturer
KS (TW-55) Insulation Panel
0.120
R2
0.015
8.000
k From Manufacturer
OSB
0.010
R3
0.250
0.040
Table A19 2013
Brickwork
0.103
R4
0.770
0.134
Table A19 2013
0.040
Table 1. BS 6946
Rse
External Surface Thickness of Ext' Wall
0.265
Total
8.498
U-Value
0.12
Rse Brickwork (R4) OSB (R3) KS (KT-112) Insulation Panel (R2)
KS (KT-118) Plasterbourd (R1)
Rsi
CONCLUSION: The U-Value calculated has turned out to be 0.12 to the 0.30 W/m2K minimum recommendation required by B'Regs. Therefore this will work.
13
Craig Greogry - N0726862
Technology & Design Studio 01.
U-Value Calculation Sheet Spartan Construction & Design
Coach house extension - W. Bridgeford
Project: Strucutre:
Professionalism from Start to Finish.
External Wall Coach house extension - W. Bridgeford
DWG REF:
Job Ref: Calc Sheet No. 02 of 06 Checked By: Date: NA 19/05/2018
Surface Resistance - Rse and Rsi From Table 1 BS EN 6946 & Cavity Rcav From Table 2 Material Conductivity - k From B'Regs App Doc L1 2013, Table A19 (or manufacturers literature preferred) R for materials = t/k (t in metres)
-
U = 1/Rtotal
U-Value Calculation Sheet Element
Size (m)
Ref
k
Rsi
Internal Surface
R
Comments
0.130
Table 1. BS 6946
KS (KT-118) Plasterbourd
0.032
R1
0.208
0.154
k From Manufacturer
KS (TW-55) Insulation Panel
0.120
R2
0.015
8.000
k From Manufacturer
OSB
0.010
R3
0.250
0.040
Table A19 2013
Air Gap
0.035
R4
0.180
0.194
Table 2. BS 6946
Timber Cladding
0.036
R5
0.130
0.277
Table A19 2013
0.040
Table 1. BS 6946
Rse
External Surface Thickness of Ext' Wall
0.233
Total
8.835
U-Value
0.11
Rse Timber Cladding (R5) Air Gap(R4) OSB (R3) KS (KT-112) Insulation Panel (R2)
KS (KT-118) Plasterbourd (R1) Rsi
CONCLUSION: The U-Value calculated has turned out to be 0.11 to the 0.30 W/m2K minimum recommendation required by B'Regs. Therefore this will work.
14 DESN10032
Craig Greogry - N0726862 2-1
Technology & Design Studio 01. Craig Gregory: N0726862
U-Value Calculation Sheet Spartan Construction & Design
Coach house extension - W. Bridgeford
Project: Strucutre:
Professionalism from Start to Finish.
Ground Floor Coach house extension - W. Bridgeford
DWG REF:
Job Ref: Calc Sheet No. 03 of 06 Checked By: Date: NA 19/05/2018
Surface Resistance - Rse and Rsi From Table 1 BS EN 6946 & Cavity Rcav From Table 2 Material Conductivity - k From B'Regs App Doc L1 2013, Table A19 (or manufacturers literature preferred) R for materials = t/k (t in metres)
-
U = 1/Rtotal
U-Value Calculation Sheet Element
Size (m)
Ref
k
Rsi
Internal Surface
R
Comments
0.170
Table 1. BS 6946
FloorBoards
0.015
R1
0.130
0.115
Table A19 2013
Screed
0.040
R2
0.410
0.098
Table A19 2013
KS Thermafloor TF70
0.100
R3
0.022
4.545
K from Manufacture
Concrete Slab External Surface
0.175
R4 Rse
1.350
0.130
Table A19 2013
0.040
Table 1. BS 6946
Thickness of Ext' Wall
0.330
Total
5.098
U-Value
0.20
Rsi Floorboards (R1) Screed Layer (R2) KS Tthermafloor TF70 Concrete Slab (R4) Rsi
CONCLUSION: The U-Value calculated has turned out to be 0.20 to the 0.25 W/m2K minimum recommendation required by B'Regs. Therefore this will work.
15
Craig Greogry - N0726862
Technology & Design Studio 01.
U-Value Calculation Sheet Spartan Construction & Design
Coach house extension - W. Bridgeford
Project: Strucutre:
Professionalism from Start to Finish.
First Floor Coach house extension - W. Bridgeford
DWG REF:
Job Ref: Calc Sheet No. 04 of 06 Checked By: Date: NA 19/05/2018
Surface Resistance - Rse and Rsi From Table 1 BS EN 6946 & Cavity Rcav From Table 2 Material Conductivity - k From B'Regs App Doc L1 2013, Table A19 (or manufacturers literature preferred) R for materials = t/k (t in metres)
-
U = 1/Rtotal
U-Value Calculation Sheet Element
Size (m)
Ref
k
Rsi
Internal Surface
R
Comments
0.100
Table 1. BS 6946
FloorBoards
0.015
R1
0.130
0.115
Table A19 2013
OSB
0.015
R2
0.250
0.060
Table A19 2013
Air Gap
0.095
R3
0.180
0.528
Table 2. BS 6946
KS Thermafloor TF71
0.120
R4
0.022
5.455
K from Manufacture
Plasterboard
0.026
R5
0.250
0.250
Table A19 2013
0.040
Table 1. BS 6946
Rse
Internal Surface Thickness of Ext' Wall
0.271
Total
6.548
U-Value
0.15
Rse Floorboards (R1) OSB (R2) Air Gap (R3) KS Tthermafloor TF70 (R4)
Plasterboard (R4) Rsi
CONCLUSION:
The U-Value calculated has turned out to be 0.15 to the 0.25 W/m2K minimum recommendation required by B'Regs. Therefore this will work.
DESN10032 16
2-1 Craig Greogry - N0726862
Craig Gregory: N0726862 Technology & Design Studio 01.
U-Value Calculation Sheet Spartan Construction & Design
Coach house extension - W. Bridgeford
Project: Strucutre:
Professionalism from Start to Finish.
Roof Coach house extension - W. Bridgeford
DWG REF:
Job Ref: Calc Sheet No. 05 of 06 Checked By: Date: NA 19/05/2018
Surface Resistance - Rse and Rsi From Table 1 BS EN 6946 & Cavity Rcav From Table 2 Material Conductivity - k From B'Regs App Doc L1 2013, Table A19 (or manufacturers literature preferred) R for materials = t/k (t in metres)
-
U = 1/Rtotal
U-Value Calculation Sheet Element
Size (m)
Ref
k
Rsi
Internal Surface
R
Comments
0.100
Table 1. BS 6946
Plasterboard
0.015
R1
0.250
0.060
Table A19 2013
KS Kooltherm (K100)
0.100
R2
0.018
5.556
K from Manufacture
Air Gap
0.135
R3
0.180
0.750
Table 2. BS 6946
Plasterboard/Vapor Barrier
0.030
R4
0.250
0.120
Table A19 2013
Felt Layer
0.010
R5
0.230
0.043
Table A19 2013
Air Gap
0.025
R6
0.180
0.139
Table 2. BS 6946
Clay Tiles
0.020
R7
1.000
0.020
Table 2. BS 6946
0.040
Table 1. BS 6946
Rse
External Surface Thickness of Ext' Wall
Total
0.335
6.828
U-Value
0.15
Rse Clay Tiles (R7) Air Gap (R6) Felt Layer (R5) Plasterboard/Vapour Barrier (R4)
Air Gap (R3) Insulation (R2) Plasterboard (R1) Rsi
CONCLUSION:
The U-Value calculated has turned out to be 0.15 to the 0.20 W/m2K minimum recommendation required by B'Regs. Therefore this will work.
DESN10032
17
2-1
Craig Greogry - N0726862
Craig Gregory: N0726862
Technology & Design Studio 01.
U-Value Calculation Sheet Spartan Construction & Design
Coach house extension - W. Bridgeford Existing Coach House External Wall Coach house extension - W. Bridgeford
Project: Strucutre:
Professionalism from Start to Finish.
DWG REF:
Job Ref: Calc Sheet No. 06 of 06 Checked By: Date: NA 19/05/2018
Surface Resistance - Rse and Rsi From Table 1 BS EN 6946 & Cavity Rcav From Table 2 Material Conductivity - k From B'Regs App Doc L1 2013, Table A19 (or manufacturers literature preferred) R for materials = t/k (t in metres)
-
U = 1/Rtotal
U-Value Calculation Sheet Element
Size (m)
Ref
k
Rsi
Internal Surface
R
Comments
0.130
Table 1. BS 6946
KS (KT-118) Plasterbourd
0.032
R1
0.208
0.154
k From Manufacturer
KS (KT-112) Insulation Panel
0.075
R2
0.018
4.167
k From Manufacturer
Brickwork
0.300
R3 Rse
0.770
0.390
Table A19 2013
0.040
Table 1. BS 6946
External Surface Thickness of Ext' Wall
0.407
Total
4.880
U-Value
0.20
Rse Brickwork (R3) KS (KT-112) Insulation Panel (R2)
KS (KT-118) Plasterbourd (R1)
Rsi
CONCLUSION: The U-Value calculated has turned out to be 0.20 to the 0.30 W/m2K minimum recommendation required by B'Regs. Therefore this will work.
18 DESN10032
2-1 Craig Greogry - N0726862
Craig Gregory: N0726862 Technology & Design Studio 01.
Coach House Extension. Existing Drawing Package.
LOCATION PLAN 20 BLOCK PLAN 21 SITE PLAN 22 GROUND FLOOR PLAN 23 FIRST FLOOR PLAN 24 EAST & WEST ELEVATION 25 NORTH & SOUTH ELEVATION 26
19
Craig Greogry - N0726862
Technology & Design Studio 01.
8 4 6
t
Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
30a
Century Court
Bdy
23.8m
dy
32
B nst
10a
10b
Co
Fire Precautions
30
2a
Co
Planning
Building Control
3
UA
t&
ons
oC
2
Path
Bor
8
LANE
10
ORD
WILF
14
10
Client Approval
28a
26
rT
ve Ri
X X X
Preliminary
ren
El Sub Sta
30
ESS
ge
9
11
8
6
1
13
38
5
15
7
40
9
3
24.1m
Shelter
24
1
4
The Point
13
Shelter
2
10c
in
7
se
The Coach Hou
73
OVE
MELTON GR
26
23.5m
12
21
2 15
21
a
a
24
rge
Su ry
28
23 23.8m
EB
ROAD
5
TL
HBOR 52
LOUG
23.8m
13
85
Beaver Green
6
23
S
ND
OUGH
OU
TCB
8
LIT
LB
37
1
29
23.8m
1
11
8
23.5m
3
89
18
5
7
Beaver Green
12
2 31
Garage
Tennis Courts
64
28
15
a
Seaton House
15
39
97
11
A
68
Nursing Home
of t ch ri ur Spi y l Ho
Ch
3
AD
10 3
70
A
RI
O CT
)
C (R
RO
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
44 Club
23.8m
49
Coach House Extension & Refurbishment.
46
Frenchhay
29
House
12 LB
2
NW
58
GR
AD RO
GHBOROUGH ROAD
O
D OO
N
Craig Greogry - N0726862
11
1:1250@ A3 TO
a
11
VE 32
84
42
15
EL
2
5 10
20
Location Plan West Bridgeford, Nottingham
M
SCALE 1:1250
23.8m
23/04/18
Mr A O'Roake
VI
LOCATION PLAN
CJG
Mr R. Dundass 38
Club
Cricket Ground
Colour applied.
the
20
nd
La
ta gS
4B
17/05/18
CJG
C001
AR
CH
Technology & Design Studio 01.
n/a A
38
13 X X X
Preliminary
73
Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
23.5m
COA C HOU H SE
ROAD
15
52
LOUG
85
HBOR
8
OUGH
PROPOSED BEAVER GREEN HOUSE NEW BUILD)
Beaver Green
1
89
18
3
5
7
Beaver Green
A
Colour applied
CJG
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Garage
Coach House Extension & Refurbishment.
Seaton House
15
a
23.8m
21
1:500@ A3
4B
64
SCALE 1:500
28
BLOCK PLAN
Existing Block Plan West Bridgeford, Nottingham
Craig Greogry - N0726862
17/05/18
CJG
C002
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval
Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
50
Planning
Building Control
EXISTING 1.0m DEEP EXCAVATION BEHIND COACHHOUSE.
1.
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER.
2.
ALL DIMENSIONS & LEVELS ARE IN METRES UNLESS OTHERWISE STATED.
3.
THE SITE SHOULD BE PREPPED AS STATED IN APP DOC C.
4.
FORMATION LEVEL TO BE PRE-TREATED WITH WEED KILLER 4.1. TOP SOIL TO BE REMOVED & TAKEN TO DESIGNATED AREA ON SITE.
EXISTING ELECTRICAL SUPPLY FROM No. 52 DWELLING (RUNS EXPOSED ALONG MASONRY BOUNDARY WALL)
5.
T02 IN
EXISTING HEDGEROW & TREE.
52
GL 24.900m
C A PV R U D Ø D m INE 0m B 10 OM C
LOUGHBOROUGH ROAD
COACH HOUSE
EXISTING UNDERGROUND DRAINAGE TO PUBLIC SEWER
GL 24.500m
EXISTING TRAMPOLINE (No. 52's) DUG 500mm DEEP BELOW GL & ON BOUNDARY LINE
01
T01 EXISTING UNDERGROUND SERVICES TO DWELLING GL 25.000m
GL 23.800m
HARDSTANDING/ SHINGLE DRIVEWAY LEADING TO No. 52's MAIN STREET ACCESS
THE SITE SHOULD BE KEPT DRY UNTIL STRUCTURES ARE COMPLETED.
LANDSCAPING: 6. ALL EXISTING TREES ARE TO BE KEPT UNLESS STATED VIA NHBC REGULATIONS. 7. ALL EXISTING LANDSCAPING IS GRAVEL/SHINGLE MATERIAL; UP TO & INCLUDING THE COACH HOUSE 11. ALL PROPOSED PATHWAYS ARE TO BE KEPT IN SAME STYLE AS EXISTING PATHWAYS AROUND SITE. 12. ALL EXISTING SERVICES ARE CONNECTED VIA No. 52'S MAIN SUPPLY OR DIRECT TO PUBLIC INFRASTRUCTURE LOCATED ON LOUGHBOURGH ROAD. DRAINAGE: 13. ALL DRAINAGE WORKS TO BE IN ACCORDANCE WITH BS EN 12056 & 752 14. ALL PROPOSED UNDERGROUND DRAINAGE PIPEWORK TO BE VITRIFIED CLAY BY HEPWORTH NOMINAL 150mmØ UNLESS STATED OTHERWISE 15. ALL DRAINAGE PIPEWORK TO BE BEDDED IN GRANULAR MATERIAL AGGREGATE CLASS F BEDDING 10mm 16. ALL DRAINAGE PIPES/INSPECTION CHAMBERS TO BE ENCASED IN GEN 1 ST2 CONSISTENCE CLASS S1 CONCRETE, IF WITHIN MIN 1.00m OF THE DWELLING A
Site Context Developed
CJG
23/05/18
Mr A O'Roake
EXISTING HEDGEROW ALONG No.52's PROPERTY LINE.
Mr R. Dundass
54
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
1
Existing Site Plan West Bridgeford, Nottingham
SITE PLAN 22
Craig Greogry - N0726862
56
1:200@ A3
SCALE 1:200
4B
17/05/18
CJG
C003
Technology & Design Studio 01.
n/a A
X X X
Preliminary
PROPOSED BEAVER GREEN HOUSE
Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING BOUNDARY WALL IN DISREPAIR EXISTING FLAGSTONE PATH/WALKWAY RWP 03 7
6 5 4 3 2 1
1.
EXISTING STRUCTURE PRE-1900 MASONRY CONSTRUCTION. 2. UNKNOWN INTERNAL DIMENSIONS & LAYOUT (NO INTERNAL SITE ANALYSIS) 3. UNKNOWN EXISTING SERVICES, UNLESS SHOWN. 3.1. INCLUDING WASTE REMOVAL SVP & DRAINAGE 3.2. HEATING APPLIANCES 3.3. GAS & ELECTRICAL LAYOUT 3.4. POTABLE WATER SOURCE 3.5. FINISHED FLOOR LEVEL & CONSTRUCTION. 3.6. ROOF TRUSS LAYOUT. 4. ALL EXISTING LANDSCAPING FEATURES ARE TO BE CONSIDERED VIA NHBC REGULATIONS.
LIVING ROOM
2200mm
HARDSTANDING/ SHINGLE DRIVEWAY
GL + 24.900
W01
D01
W02
RWP 02
SCALE 1:100 23
GL + 24.500 HARDSTANDING/ SHINGLE DRIVEWAY LEADING TO No. 52's MAIN STREET ACCESS
EXISTING TRAMPOLINE (No. 52's) DUG 500mm DEEP BELOW GL & ON BOUNDARY LINE
EXISTING UNDERGROUND DRAINAGE TO PUBLIC SEWER
GROUND FLOOR PLAN
T02
EXISTING UNDERGROUND SERVICES TO DWELLING
EXISTING HEDGEROW BOUNDARY
BOUNDARY LINE
EXISTING MASONRY WALL BOUNDARY
01
RWP 01
100mmØ UPVC COMBINED DRAIN
EXISTING UNDERGROUND ELECTRICAL SERVICES
2200mm
C AIN PV R U D Ø D m NE 0m BI 10 OM C
GL + 25.000
KITCHEN
EM BOX
D02
T01
A
Site Context developed
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Existing Ground Floor Plan West Bridgeford, Nottingham 1:100@ A3
4B
Craig Greogry - N0726862
CJG
17/05/18
CJG
C004
Technology & Design Studio 01.
n/a A
PROPOSED BEAVER GREEN HOUSE
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING BOUNDARY WALL IN DISREPAIR EXISTING FLAGSTONE PATH/WALKWAY RWP 03 7 8 9 10
CUPBOARD
EM BOX
EXISTING STRUCTURE PRE-1900 MASONRY CONSTRUCTION. 2. UNKNOWN INTERNAL DIMENSIONS & LAYOUT (NO INTERNAL SITE ANALYSIS) 3. UNKNOWN EXISTING SERVICES, UNLESS SHOWN. 3.1. INCLUDING WASTE REMOVAL SVP & DRAINAGE 3.2. HEATING APPLIANCES 3.3. GAS & ELECTRICAL LAYOUT 3.4. POTABLE WATER SOURCE 3.5. FINISHED FLOOR LEVEL & CONSTRUCTION. 3.6. ROOF TRUSS LAYOUT. 4. ALL EXISTING LANDSCAPING FEATURES ARE TO BE CONSIDERED VIA NHBC REGULATIONS.
BEDROOM 01
D04
T01
D03
2200mm
1.
2200mm
BATHROOM 2200mm
01
SCALE 1:100 24
GL + 24.500 HARDSTANDING/ SHINGLE DRIVEWAY LEADING TO No. 52's MAIN STREET ACCESS
EXISTING TRAMPOLINE (No. 52's) DUG 500mm DEEP BELOW GL & ON BOUNDARY LINE
Craig Greogry - N0726862
EXISTING UNDERGROUND DRAINAGE TO PUBLIC SEWER
FIRST FLOOR PLAN
T02
EXISTING UNDERGROUND SERVICES TO DWELLING
EXISTING HEDGEROW BOUNDARY
BOUNDARY LINE
EXISTING MASONRY WALL BOUNDARY
100mmØ UPVC COMBINED DRAIN
GL + 24.900
N 20 VC AI 1: P R ll U D Fa Ø D m INE 0m B 10 OM C
HARDSTANDING/ SHINGLE DRIVEWAY
GL + 25.000
RWP 02
RWP 01
A
Site Context developed
CJG
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Existing First Floor Plan West Bridgeford, Nottingham 1:100@ A3
4B
17/05/18
CJG
C005
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
1. 2. 3. AS BUILT BEAVER-GREEN HOUSE (ONGOING)
4.
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING RED BRICK VICTORIAN MASONRY EXTERNAL FINISH. ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. ALL GUTTERING HAS BEEN UPDATED TO BLACK UPVC MATERIAL ROOF MATERIAL IS A GREY/BLACK CERAMIC SLATE.
T01 FRL + 29.558 TH
RGL + 28.288 RH
TSB + 29.090
LH
TCL + 26.880 FL
FL
FL
FL
FL
FL
FL
FGL + 25.100 FGL + 24.900
EAST ELEVATION SCALE 1:100
T01 FRL + 29.558 RGL + 28.288 TSB + 29.090 TCL + 26.880 FGL + 25.100 A
Shadows Amended
CJG
23/04/18
FGL + 24.900 Mr A O'Roake
WEST ELEVATION
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
SCALE 1:100
Coach House Extension & Refurbishment.
Existing East & West Elevation West Bridgeford, Nottingham 1:100@ A3
4B
25
Craig Greogry - N0726862
17/05/18
CJG
C006
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
1. 2.
AS BUILT BEAVER-GREEN HOUSE (ONGOING)
3. 4.
T01
FRL + 29.558
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING RED BRICK VICTORIAN MASONRY EXTERNAL FINISH. ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. ALL GUTTERING HAS BEEN UPDATED TO BLACK UPVC MATERIAL ROOF MATERIAL IS A GREY/BLACK CERAMIC SLATE.
RGL + 28.288 TSB + 29.090 TCL + 26.880 FFL + 25.100 FGL + 24.900
EXISTING TRAMPOLINE (No. 52's) DUG 500mm DEEP BELOW GL & ON BOUNDARY LINE
EGL + 24.422
NORTH ELEVATION SCALE 1:100
AS BUILT BEAVER-GREEN HOUSE (ONGOING)
T02 FRL + 29.558
FL
FL
RGL + 28.288 A
TSB + 29.090
Shadows Amended
23/04/18
Mr A O'Roake
TCL + 26.880
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
FFL + 25.100
Coach House Extension
FGL + 24.900
& Refurbishment.
EXISTING TRAMPOLINE (No. 52's) DUG 500mm DEEP BELOW GL & ON BOUNDARY LINE
EGL + 24.422
SOUTH ELEVATION
Existing North & South Elevation West Bridgeford, Nottingham 1:100@ A3
SCALE 1:100 26
CJG
4B
Craig Greogry - N0726862
17/05/18
CJG
C007
Technology & Design Studio 01.
n/a A
Coach House Extension. Proposed Drawing Package Cover.
BLOCK PLAN 28 SITE PLAN 29 FOUNDATION PLAN 30 SOLEPLATE LAYOUT 31 GROUND FLOOR PLAN 32 FIRST FLOOR PLAN 33 FLOOR JOIST LAYOUT 34 ROOF JOIST LAYOUT 35 SECTION A-A 36 SECTION B-B 37 TECHNICAL CUT 38 DETAIL 01 - RIDGE TECHNICAL DETAIL 39 DETAIL 02 - SUSPENDED FLOOR TECHNICAL DETAIL 40 DETAIL 03 - SOLA-TUBE TECHNICAL DETAIL 41 EAST ELEVATION 42 SOUTH ELEVATION 43 WEST ELEVATION 44 NORTH ELEVATION 45 DOOR & WINDOW SCHEDULE 46 ELECTRICAL LAYOUT 47 HEATING SYSTEMS LAYOUT 48 DRAINAGE LAYOUT 49 BEDROOM RENDERED IMAGE 50 EXTERNAL RENDERED IMAGE A 51 EXTERNAL RENDERED IMAGE B 52 LIVING AREA RENDERED IMAGE 53 27
Craig Greogry - N0726862
Technology & Design Studio 01.
38
X X X
Preliminary Client Approval
73
Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
21 8
HBOR
85
LOUG
52
PROPOSED BEAVER GREEN HOUSE (NEW BUILD)
OUGH
COA C HOU H SE
ROAD
5
Beaver Green
1
11
5
3 89
7
Beaver Green
A
Colour Applied
CJG
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Garage Seaton House
15
a
23.8m
BLOCK PLAN
& Refurbishment.
Proposed Block Plan West Bridgeford, Nottingham 1:500@ A3
64
SCALE 1:500 28
Coach House Extension
Craig Greogry - N0726862
4B
17/05/18
CJG
C008
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval
50
Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING 1.0m DEEP EXCAVATION BEHIND COACHHOUSE.
EXISTING ELECTRICAL SUPPLY FROM No. 52 DWELLING (RUNS EXPOSED ALONG MASONRY BOUNDARY WALL)
COACH HOUSE
EXISTING UNDERGROUND DRAINAGE TO PUBLIC SEWER T02
1.
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER.
2.
ALL DIMENSIONS & LEVELS ARE IN METRES UNLESS OTHERWISE STATED.
3.
THE SITE SHOULD BE PREPPED AS STATED IN APP DOC C.
4.
FORMATION LEVEL TO BE PRE-TREATED WITH WEED KILLER 4.1. TOP SOIL TO BE REMOVED & TAKEN TO DESIGNATED AREA ON SITE.
EXISTING HEDGEROW & TREE.
GL 24.900m 01
LOUGHBOROUGH ROAD
52
5.
GL 24.500m EXISTING TRAMPOLINE (No. 52's) REMOVED & REFILLED (CLIENTS DISGRESSION)
T01 PROPOSED UNDERGROUND FW DRAINAGE TO PUBLIC MAINS
GL 25.000m
EXISTING UNDERGROUND SERVICES TO DWELLING
HARDSTANDING/ SHINGLE DRIVEWAY (53.5m LENGTH) LEADING TO No. 52's MAIN STREET ACCESS
GL 23.800m
54
EXISTING HEDGEROW ALONG No.52's PROPERTY LINE.
THE SITE SHOULD BE KEPT DRY UNTIL STRUCTURES ARE COMPLETED.
LANDSCAPING: 6. ALL EXISTING TREES ARE TO BE KEPT UNLESS STATED VIA NHBC REGULATIONS. 7. ALL EXISTING LANDSCAPING IS GRAVEL/SHINGLE MATERIAL; UP TO & INCLUDING THE COACH HOUSE 11. ALL PROPOSED PATHWAYS ARE TO BE KEPT IN SAME STYLE AS EXISTING PATHWAYS AROUND SITE. 12. ALL EXISTING SERVICES ARE CONNECTED VIA No. 52'S MAIN SUPPLY OR DIRECT TO PUBLIC INFRASTRUCTURE LOCATED ON LOUGHBOURGH ROAD. DRAINAGE: 13. ALL DRAINAGE WORKS TO BE IN ACCORDANCE WITH BS EN 12056 & 752 14. ALL PROPOSED UNDERGROUND DRAINAGE PIPEWORK TO BE VITRIFIED CLAY BY HEPWORTH NOMINAL 150mmØ UNLESS STATED OTHERWISE 15. ALL DRAINAGE PIPEWORK TO BE BEDDED IN GRANULAR MATERIAL AGGREGATE CLASS F BEDDING 10mm 16. ALL DRAINAGE PIPES/INSPECTION CHAMBERS TO BE ENCASED IN GEN 1 ST2 CONSISTENCE CLASS S1 CONCRETE, IF WITHIN MIN 1.00m OF THE DWELLING A
Context & Roof layout adjusted
CJG
30/04/18
Mr A O'Roake
Mr R. Dundass
1 56
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
SITE PLAN
& Refurbishment.
Proposed Site Plan West Bridgeford, Nottingham 1:200@ A3
SCALE 1:200 29
Coach House Extension
4B
Craig Greogry - N0726862
17/05/18
CJG
C009
Technology & Design Studio 01.
n/a A
PROPOSED COACH HOUSE EXTENSION
TAG
RE
EXISTING COACH HOUSE STRUCTURE & FND/FLOOR CONSTRUCTION
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING COACH HOUSE (UNKNOWN FND LEVEL)
EXISTING BOUNDARY WALL (UNKNOWN FND LEVEL)
SUITABLE REBARS TO BE INSTALLED DURING FND LAYING, SPECIFIED BY STRUCTURAL ENGINEER & TO HAVE NOMINAL COVER.
FOUNDATION CONNECTION DETAIL SCALE 1:20
EXISTING SVP THICKENED LOCALLY UNDER PROPOSED FOUNDAITON
FOR PROPOSED & EXISTING FOUNDATION CONNECTION. SEE DETAIL, DWG REF C10
TFL 24.280m 2No. COURSES OF STANDARD GRADE 325 x 215 x 300mm THK FND ENGINEERING BLOCK, SUPPLIED VIA CELCON
TFL 24.280m
FOUL WATER RUN IC 02
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER
2.
ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED
3.
ALL LEVELS ARE IN METRES.
4.
ALL CONCRETE CONSTRUCTED TO BS 8500
5.
ALL FOUNDATIONS TO BE NARROW STRIP CLASS & SUITABLE REVETMENT WORKS PRIOR TO EXCAVATION
6.
ALL CONCRETE TO BE MINIMUM OF GEN 1 MIX: S4 CONSISTENCE CLASS.
7.
ALL FOUNDATION CONCRETE LAID AND COMPACTED BY HAND
8.
ALL MORTAR JOINTS TO BE SPECIFIED BY BS 998-2 8.1. CLASS I UNDER DPC LAYER 8.2. CLASS III ABOVE DPC LAYER
9.
All PROPOSED FOUNDATIONS CONNECTION TO THE EXISTING DWELLING; 9.1. TO BE CALCULATED & SPECIFIED BY STRUCTURAL ENGINEER. 9.2. SUFFICIENT SURVEY PRIOR TO EXCAVATION WORK BEGINNING.
225 x 625mm GEN 1 MIX CONCRETE STRIP FOUNDATION.
PROPOSED SVP, THICKENED LOCALLY AROUND FND.
IC 01
1.
A
Proposed drainage & SVP location
CJG
26/03/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
PROPOSED FOUNDATION PLAN
GL 24.900m
SCALE 1:50
30
Proposed Foundaiton Plan West Bridgeford, Nottingham As Shown @ A3
4B
Craig Greogry - N0726862
17/05/18
CJG
C010
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
EXISTING COACH HOUSE
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING COACH HOUSE BEAM-OVER
G
E
H
BEAM-OVER
A
F
1.
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER
2.
ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED
3.
ALL LEVELS ARE IN METRES.
4.
ALL TIMBER TO BE MIN C16 STRENGTH & PRE-TREATED.
D
5. ALL TIMBER SOLEPLATES TO BE 5.1. 50 x 140mm THK C16 PIECES. 5.2. PRETREATED AGAINST WEATHER & INSECT DAMAGE 5.3. 2400mm LONG (UNLESS OTHERWISE SPECIFIED)
A
C
HEAD BINDER LAYOUT
SCALE 1:100
6.
DPC TO BE APPLIED BEFORE FIXING TO SUBSTRUCTURE
7.
ALL TIMBER SOLEPLATES SECURED TO SUBSTRUCTURE WITH SUITABLE FIXINGS
8.
ALL DIMENSIONS ARE TAKEN FROM INTERNAL SIDE OF STRUCTURAL FACE
9.
TIMBER STUD FRAMES ARE TO BE DESIGNED & SPECIFIED BY OUTSIDE MANUFACTURE'S SPECIFCATION
EXISTING COACH HOUSE BEAMOVER BEAM-OVER
A
A
B
B
PROPOSED TIMBER FRAME LAYOUT
Mr A O'Roake
Mr R. Dundass
SCALE 1:50
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
SOLEPLATE LAYOUT SCALE 1:100
31
Craig Greogry - N0726862
Proposed Soleplate Layout West Bridgeford, Nottingham AS SHOWN @ A3
4B
17/05/18
CJG
C011
Technology & Design Studio 01.
n/a -
B X X X
Preliminary
RE
Client Approval
TAG
Planning
7
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
6 5 4 3 2 1
SEE NOTE 05
KITCHEN DINING AREA BEAM OVER
2200mm
EM BOX
2200mm
EXISTING STRUCTURE PRE-1900 MASONRY CONSTRUCTION.
2.
UNKNOWN INTERNAL DIMENSIONS & LAYOUT (NO INTERNAL SITE ANALYSIS)
3.
UNKNOWN EXISTING SERVICES, UNLESS SHOWN. 3.1. INCLUDING WASTE REMOVAL SVP & DRAINAGE 3.2. HEATING APPLIANCES 3.3. GAS & ELECTRICAL LAYOUT 3.4. POTABLE WATER SOURCE 3.5. FINISHED FLOOR LEVEL & CONSTRUCTION. 3.6. ROOF TRUSS LAYOUT.
4.
BEAM OVER
EXISTING STAIRWELL TO BE REDESIGNED & CONSTRUCTED TO CURRENT BUILDING REGULATIONS USING, APP DOC K 5.1. RISE = 170mm 5.2. GOING = 250mm
LOBBY D02
2400mm
6.
ALL PROPOSED EXTERNAL WALLS ARE TO BE CONSTRUCTED WITH 20mm THK KS KOOLTHERM (K118) SEE DWG C020 6.1. PROVIDES CLASS 00 FIRERATING & PROTECTION
01 D01
W03
W02
7.
ALL WINDOWS SUPPLIED BY CRITTALL
8.
ALL DOORS SUPPLIED BY CRITTALL
9.
SOLA-TUBE TO BE INSTALLED VIA MANUFACTURES SPECIFICATIONS & ASTHETICALLY HIDDEN ON FIRST FLOOR.
PROPOSED TIMBER DECKING
DEMOLITION WORK
W04
EXISTING UNDERGROUND SERVICES
ALL EXISTING LANDSCAPING FEATURES ARE TO BE CONSIDERED VIA NHBC REGULATIONS.
5.
W01
GL + 25.000
1.
GL + 25.000
FOUL WATER RUN IC 02
REFURBISHMENT
LIVING ROOM 2400mm
GL + 24.900
A
B
B
DRAINAGE AMENDED
CJG
30/04/18
A
PROPOSED DRAINAGE LAYOUT
CJG
23/04/18
Mr A O'Roake
A
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
IC 01
Coach House Extension & Refurbishment.
Proposed Ground Floor Plan West Bridgeford, Nottingham
GROUND FLOOR PLAN
1:50@ A3
SCALE 1:50 32
4B
Craig Greogry - N0726862
17/05/18
CJG
C012
Technology & Design Studio 01.
n/a B
B X X X
Preliminary
RE
Client Approval
TAG
Planning
SEE NOTE 09
Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
7
CUPBOARD
8 9 10 D03
W05
2200mm
BEDROOM 01
1.
EXISTING STRUCTURE PRE-1900 MASONRY CONSTRUCTION.
2.
UNKNOWN INTERNAL DIMENSIONS & LAYOUT (NO INTERNAL SITE ANALYSIS)
3.
UNKNOWN EXISTING SERVICES, UNLESS SHOWN. 3.1. INCLUDING WASTE REMOVAL SVP & DRAINAGE 3.2. HEATING APPLIANCES 3.3. GAS & ELECTRICAL LAYOUT 3.4. POTABLE WATER SOURCE 3.5. FINISHED FLOOR LEVEL & CONSTRUCTION. 3.6. ROOF TRUSS LAYOUT.
D04
W06
2200mm
BATHROOM
D06
EM BOX
Building Control
2200mm
1 2 3
4.
D05
ALL EXISTING LANDSCAPING FEATURES ARE TO BE CONSIDERED VIA NHBC REGULATIONS.
5.
EXISTING STAIRWELL TO BE REDESIGNED & CONSTRUCTED TO CURRENT BUILDING REGULATIONS USING, APP DOC K 5.1. RISE = 170mm 5.2. GOING = 250mm
6.
ALL PROPOSED EXTERNAL WALLS ARE TO BE CONSTRUCTED WITH 20mm THK KS KOOLTHERM (K118) SEE DWG C020 6.1. PROVIDES CLASS 00 FIRERATING & PROTECTION
W07
01
7.
ALL WINDOWS SUPPLIED BY CRITTAL
8.
ALL DOORS SUPPLIED BY CRITTAL
9.
SOLA-TUBE TO BE INSTALLED VIA MANUFACTURES SPECIFICATIONS & ASTHETICALLY HIDDEN ON FIRST FLOOR.
W08
DEMOLITION WORK
FOUL WATER RUN IC 02
A IC 01
B
2400mm
B
DRAINAGE AMENDED
CJG
30/04/18
A
PROPOSED DRAINAGE LAYOUT
CJG
23/04/18
Mr A O'Roake
A
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
2400mm ENSUITE
Coach House Extension & Refurbishment.
Proposed First Floor Plan West Bridgeford, Nottingham
FIRST FLOOR PLAN
1:50@ A3
SCALE 1:50 33
REFURBISHMENT
BEDROOM 02
D06
W09
EXISTING UNDERGROUND SERVICES
PROPOSED TIMBER DECKING
4B
Craig Greogry - N0726862
17/05/18
CJG
C013
Technology & Design Studio 01.
n/a B
B X X X
Preliminary Client Approval Planning
2No.195 x 97mm THK MADE TO MEASURE C16 EASI-JOIST FLOOR BEAMS @ STATED C/C
TIMBER STUD WALL
4000 x 195 x 97mm THK EASI-JOIST FLOOR BEAMS @ 600mm C/C (UNLESS OTHERWISE STATED) SUPPORTED VIA SUITABLE JOIST HANGER ATTACHED TO C16 TIMBER SOLE PLATE
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
8No.4200x 195 x 97mm THK MADE TO MEASURE C16 EASI-JOIST FLOOR BEAMS @ 600mm C/C (UNLESS OTHERWISE STATED)
8No. 2400 x 35 x125mm THK C16 TIMBER "EASYBACK" PIECES, SECURED TO JOISTS WITH 6No. 50mm C/S FIXINGS
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER.
2.
ALL DIMENSIONS & LEVELS ARE IN METRES UNLESS OTHERWISE STATED.
3.
ALL TIMBER EASI-JOISTS MANUFACTURED BY WOLF SYSTEMS (WS200) 3.1. MADE TO MEASURE COMPONENTS FOR NON-STANDARD DIMENSIONS/SPACING 3.2. BUILT TO MANUFACTURE'S SPECIFICATIONS TO TIMBER FRAME CONSTRUCTION
EXISTING COACH HOUSE & SUSPENDED TIMBER SUSPENDED FLOOR
JOIST HANGER ISOMETRIC DETAIL
1.
NTS
SERVICES: 4. ALL SERVICES TO BE HIDDEN & LAID INTO EASI-JOIST FRAMEWORK WITH SUITABLE PROTECTION FIRE PROTECTION: 5. SUITABLE FIREBLOCKS & FIRE PROTECTION METHODS TO BE INSTALLED AT JUNCTIONS & CONSTRUCTION LAPS. 5.1. REFER TO APP DOC B, VOL 01
228mm THK EXTERNAL TIMBER STUD PARTITION WALL SEE DWG REF C20 FOR CONSTRUCTION LAYOUT
47x47mm THICK TOP CHORD RESTRAINT FIXED TO EASI-JOISTS WITH Z CLIPS TO MANUFACTURERS SPECIFICATIONS 195 x 97mm THK EASI-JOISTS FIXED WITH EASI-JOIST HANGER TO MANUFACTURERS SPECIFICATIONS TO EXT WALL 100mm THICK KNAUF EARTHWOOL ACOUSTIC ROLL FLOOR INSULATION BETWEEN EASI-JOISTS INSTALLED TO MANUFACTURERS SPECIFICATION
END BEARING DETAIL SCALE 1:20 34
DEMOLITION WORK
FOR FIRST FLOOR CONSTRUCTION SEE TECHNICAL DETAIL, DWG REF C020
REFURBISHMENT
8No. 2400 x 35 x125mm THK C16 TIMBER "EASYBACK" PIECES, SECURED TO JOISTS WITH 6No. 50mm C/S FIXINGS 16No. 2650 x 195 x 97mm THK C16 EASI-JOIST FLOOR BEAMS @ 600mm C/C (UNLESS OTHERWISE STATED) SEE JOIST HANGER DETAIL, DWG REF C014 A
Revision Description
140mm THK EXTERNAL INSULATED LOADBEARING TIMBER STUD WALL SEE END BEARING DETAIL, DWG REF C014
CJG
26/03/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
PROPOSED FLOOR JOIST LAYOUT SCALE 1:50
Craig Greogry - N0726862
A
B
A
Proposed FloorJoist Layout West Bridgeford, Nottingham AS SHOWN @ A3
4B
17/05/18
CJG
C014
Technology & Design Studio 01.
n/a A
EXISTING ROOF STRUCTURE TO BE KEPT.
B
X X X
Preliminary Client Approval Planning
SOLA-TUBE INSTALLED INTO EXISTING ROOF STRUCTURE, FIXED TO MANUFACTURES SPECIFICATIONS, SEE NOTES 7 & 8. DWG REF C021 FOR CONSTRUCTION DETAIL EXISTING ROOF LIGHT TO BE KEPT.
PROPOSED NEW RIDGE LINE TO COINCIDE WITH PROPOSED ROOF STRUCTURE
100x50mm THK C16 TIMBER JACK RAFTERS TO FORM AN INVERTED VALLEY, TO EXISTING ROOF STRUCTURE. (SEE NOTE 06)
X X X
Measurement Tender Contract
X X X
X X
Site As Built
2.
ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED
3.
ALL TIMBER TO BE MIN C16 STRENGTH & PRE-TREATED.
4. ALL TIMBER WALLPLATES TO BE 4.1. 50 x 140mm THK C16 PIECES. 4.2. PRETREATED AGAINST WEATHER & INSECT DAMAGE 4.3. 2400mm LONG (UNLESS OTHERWISE SPECIFIED) ALL EASI-JOIST TIMBER RAFTERS, TO BE MANUFACTURED BY "WOLF SYSTEMS" & LAID TO SPECIFICATIONS. SEE WOLF SYSTEM SPECIFICATIONS FOR CONNECTION DETAILS TO EASI-JOIST ROOF TRUSSES
INVERTED HIP ROOF EXTENSION TO EXSTING ROOF STRUCTURE, TO BE CALCULATED FOR LOADINGS BY STRUCTURAL ENGINEER.
SOLA-TUBES 8. PROPOSED SOLATUBE SYSTEMS ARE TO BE CONSTRUCTED & FITTED INTO ROOF SYSYEM, WITH ALL SERVICES & MECHANICAL COMPONENTS HIDDEN FROM VIEW.
T02
T02
T02
T02
2No.T02
7.
175 x75mm THK C16 TIMBER RIDGEBOURD RUNNING CENTRALLY ALONG PROPOSED ROOFLINE (SEE NOTE 5.1)
9.
ADDITIONAL PV16 SOLAR PHOTOVOLTAIC PANELS (SUPPLIED BY CLEARLINE FUSION) TO BE FITTED ONTO PROPOSED EXTENSIONS ROOF STRUCTURE, TO ADD IN ELECTRICAL SUPPLY FOR SOLATUBE LED LIGHTING
GUTTERING 10. DOWNPIPES ARE TO PENETRATE WALL AT FIRST FLOOR LEVEL, TO RUN AS SERVICES THROUGH EASI-JOIST FLOOR BEAM STRUCTURE; TO PROPOSED SURFACE WATER COLLECTION SYSTEM LOCATED EXTERNALLY.
10No. 2400 x 35 x125mm THK C16 TIMBER "EASYBACK" PIECES, SECURED TO JOISTS WITH 6No. 50mm C/S FIXINGS WITH 600mm OVERLAP 20No. 2415 x 195 x 97mm THK C16 EASI-JOIST ROOF RAFTERS @ 600mm C/C (UNLESS OTHERWISE STATED) CONNECTED TO TIMBER WALL PLATE & TIMBER RIDGEBOURD VIA MANUFACTURE'S SPECIFICATION, WITH 280mm OVERHANG (SEE DETAIL, DWG REF C021)
DEMOLITION WORK
140mm THK EXTERNAL INSULATED LOADBEARING TIMBER WALL & SOLE PLATE. (SEE DETAIL, DWG REF C020)
100mm Ø UPVC GUTTERING SYSTEM, SUPPLIED BY MARLEY ETERNET & FITTED TO MANUFACTURES SETTING ALONG EAVES WITH SUITABLE FIXINGS. (SEE NOTE 09)
T01 T01
6No. 2415 x 195 x 97mm THK C16 EASI-JOIST ROOF RAFTERS @ 600mm C/C (UNLESS OTHERWISE STATED) CONNECTED TO TIMBER WALL PLATE & TIMBER RIDGEBOURD VIA MANUFACTURE'S SPECIFICATION (SEE DETAIL, DWG REF C021)
35
Pre-Tender
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER
5.1.
SCALE 1:50
Fire Precautions
1.
5.
PROPOSED ROOF JOIST LAYOUT
Building Control
REFURBISHMENT A
Revision Description
26/03/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
FLAT ROOF SYSTEM
T01
CJG
Coach House Extension & Refurbishment.
T01
A
2No. T01
B
A
Proposed Roofplan West Bridgeford, Nottingham AS SHOWN @ A3
4B
Craig Greogry - N0726862
17/05/18
CJG
C015
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
ROOF CONSTRUCTION & FINISH, SEE DETAIL DWG REF C021
PROPOSED BEDROOM 01
EXISTING DWELLING
WALL & SUSPENDED FLOOR CONSTRUCTION, SEE DETAIL DWG REF C020 DINING ROOM
PROPOSED LIVING AREA/STUDY
GL
A
SECTION A-A SCALE 1:50
Proposed room heights raised to 2400mm
CJG
26/03/18
Mr A O'Roake
GROUND FLOOR & FOUNDATION CONSTRUCTION, SEE DETAIL DWG REF C019
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Proposed Section A-A West Bridgeford, Nottingham 1:50@ A3
4B
36
Craig Greogry - N0726862
17/05/18
CJG
C016
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
X X
Site As Built
ROOF CONSTRUCTION & FINISH, SEE DETAIL DWG REF C021
FRL + 29.558 RGL + 28.952 FL PROPOSED ENSUITE
FL PROPOSED BEDROOM 01
03 02 01
WALL & SUSPENDED FLOOR CONSTRUCTION, SEE DETAIL DWG REF C020 KITCHEN
DINING ROOM 08
TCL + 26.880
07 06 05
FL GL
FL PROPOSED LIVING AREA/STUDY
04 03 02 01
FFL + 25.100 FGL + 24.900
GROUND FLOOR & FOUNDATION CONSTRUCTION,SEE DETAIL DWG REF C019
ROOF CONSTRUCTION & FINISH, SEE DETAIL DWG REF C021
SECTION B-B SCALE 1:50
A
CJG 26/03/18 Proposed room heights raised to 2400mm
Mr A O'Roake
EGL + 24.422
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Proposed Section B-B West Bridgeford, Nottingham 1:50@ A3
4B
17/05/18
CJG
C017
n/a A
FRL + 29.558 RGL + 28.952 FL PROPOSED ENSUITE
FL PROPOSED BEDROOM 01
03 02 01
WALL & SUSPENDED FLOOR CONSTRUCTION, SEE DETAIL DWG REF C020 KITCHEN
DINING ROOM 08
TCL + 26.880
07 06 05
FL
04
FL
03
PROPOSED LIVING AREA/STUDY
GL
02 01
FFL + 25.100 FGL + 24.900
GROUND FLOOR & FOUNDATION CONSTRUCTION,SEE DETAIL DWG REF C019
SECTION B-B
A
CJG 26/03/18 Proposed room heights raised to 2400mm
Mr A O'Roake
EGL + 24.422
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension
SCALE 1:50
& Refurbishment.
Proposed Section B-B West Bridgeford, Nottingham 1:50@ A3
4B
37
Craig Greogry - N0726862
17/05/18
CJG
C017
Technology & Design Studio 01.
n/a A
ROOF CONSTRUCTION & FINISH, SEE DETAIL DWG REF C021
75 x 175mm THK TIMBER RIDGE BEAM, SECURED TO EASI-JOIST RAFTERS. MADE UP C16 TIMBER STUD WALL, TO FORM EXTENDED HEAD ROOM & GABLE END CONSTRUCTION.
37 x 80mm TIMBER BINDERS SECURED TO RIDGE BEAM AS FILLERS, BETWEEN ROOF CONSTRUCTION & BEAM.
120mm THK KINGSPAN KOOLTHERM (K112) INSULATED PANEL, PLACED INBETWEEN 140mm THK C16 INTERNAL TIMBER STUD FRAME.WITH PLASTER SKIM FINISHED, SECURED ONTO TIMBER FRAME WITH C/S SCREWS . 10mm THK ADVENTEC OSB BOARD WITH DUPONT AIRGUARD REFLECTIVE VAPOUR BARRIER MEMBRANE. 15mm THK T&G FLOOR BOARDS, SECURED TO PANEL WITH SUITABLE FIXINGS 15mm THK OSB BOARD LAID OVER & SECURED TO FLOOR EASI-JOIST ROOF BEAMS WITH SUITABLE FIXINGS 4000 x 195 x 97mm THK EASI-JOIST FLOOR BEAMS @ 600mm C/C (UNLESS OTHERWISE STATED) 120mm THK KINGSPAN KOOLTHERM (K70) INSULATED PANEL, PLACED INBWETWEEN TIMBER STUD FRAME.
FOR FIRST FLOOR CONNECTION DETAILS SEE DWG REF C020
12.5mm THK PLASTERBOARD, WITH 3mm PLASTER SKIM FINISH SECURED TO UNDERSIDE OF EASI-JOISTS. PROPOSED ENSUITE
2400 x 120 x 20mm THK TIMBER CLADDING SYSTEM (CLIENT'S REQUEST) FIXED TO 25x25mm TIMBER BATTON RAILS BEFORE ATTACHED TO EXTERNAL OSB BOARD.
KINGSPAN NILVENT BREATHABLE MEMBRANE, FIXED ONTO INSULATED PLASTERBOARD. 140mm THK C16 TIMBER STUD PARTITION WALL SECURED WITH SUITABLE FIXINGS & LAID ONTOP OF 140x100mm TIMBER SOLEPLATE SUITABLE FLASHING/DRIPTRAYS TO BE INSTALLED ALONG BOTTOM OF TIMBER CLADDING & FITTED TO MANUFACTURES SPECIFCATIONS
FOR EXTERNAL WALL BUILDUP SEE DETAIL, DWG REF C019 GL
120mm THK KINGSPAN KOOLTHERM (K112) INSULATED PANEL, PLACED INBWETWEEN TIMBER STUD FRAME. 10mm THK ADVENTEC OSB BOARD WITH DUPONT AIRGUARD REFLECTIVE VAPOUR BARRIER MEMBRANE SECURED ON WITH C/S SCREWS TO TIMBER STUD WALL.
PROPOSED SVP SUITABLEY ENCASED
32.5mm THK KINGSPAN KOOLTHERM (K118) INSULATED PLASTERBOARD WITH PLASTER SKIM FINISHED, SECURED TO TIMBER FRAME WITH .
140 x 2400 x 50mm THK C16 TIMBER SOLEPLATE, LAID ONTO BLOCK WORK WITH MORTAR.
Project: COACH HOUSE EXTENSION &
STANDARD GRADE 300 x 215 x 140mm THK FND BLOCK, SUPPLIED VIA CELCON PROPOSED LIVING AREA
Title:
REFURBISHMENT.
TECHNICAL CUT
2No. COURSES OF STANDARD GRADE 325 x 215 x 300mm THK FND ENGINEERING BLOCK, SUPPLIED VIA CELCON & LAID ONTO WITH FOUNDATION WITH TYPE I MORTAR 225 x 625mm GEN 1 MIX CONCRETE STRIP FOUNDATION
Scale @ A3:
Drawn:
CJG FOR GROUND FLOOR BUILDUP SEE DETAIL, DWG REF C019
1:20
Ch’kd:
Date:
17/05/2018 Time:
N/A Auth:
N/A Traced:
N/A Dwg No:
Rev:
C018
TECHNICAL CUT
N/A A
SCALE 1:20
011 Arkwright Studio, Nottingham Nottinghamshire, England, NG1 4BU Tel: 01234567890
38
Craig Greogry - N0726862
Technology & Design Studio 01
NATURAL BUFF STONE WALL CONSTRUCTION, LAID UP TO WINDOW CILL LEVEL, COLOUR TO CLIENT'S REQUEST
X X X
Preliminary
FOR WALL CONSTRUCTION SEE DWG REF C020
Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
140 x 2400 x 50mm THK C16 TIMBER SOLEPLATE, LAID ONTO BLOCK WORK WITH MORTAR.
SUITABLE WALL CLIP, BEDDED IN MASONRY COURSING & SECURED TO EXTERNAL SIDE OF TIMBER STUD
100x19mm TIMBER BULLNOSE SKIRTING BOARD NAILED TO ROUGH GROUND
WEEP HOLE RYTONS RYTWEEP BEDDED IN MORTAR AT 900mm CENTRES
125x19mm THK OAK HW T&G TIMBER STRIP FLOORING 40mm THK SCREED, EVENLY LAID. 100mm THK KINGSPAN THERMAFLOOR (TF70) INSULATION LAID ONTOP OF DPM LAYER WITH 20mm THK PERIMETER INSULATION 175mm THK CONCRETE, GEN 1 MIX CONSISTENCE CLASS S2 1000 GAUGE POLYTHENE SHEET ONTOP OF 25mm THK SAND BLINDING & LAPPED WITH DPC (MIN 150mm ABOVE GL) 150mm THK WELL COMPACTED HARDCORE, LAID IN 2x75mm THK LAYERS STANDARD GRADE 300 x 215 x 140mm THK FND BLOCK, SUPPLIED VIA CELCON & LAID ONTO WITH FOUNDATION WITH MORTOR 2No. COURSES OF STANDARD GRADE 325 x 215 x 300mm THK FND ENGINEERING BLOCK, SUPPLIED VIA CELCON & LAID ONTO WITH FOUNDATION WITH TYPE I MORTAR
A
Revision Description
SCALE 1:5
Mr A O'Roake 104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Ridge Technical Detail West Bridgeford, Nottingham 1:5@ A3
4B
39
Craig Greogry - N0726862
26/03/18
Mr R. Dundass
225 x 625mm GEN 1 MIX CONCRETE STRIP FOUNDATION, LAID BY HAND TO BS 8500
EXTERNAL WALL & FLOOR DETAIL
CJG
17/05/18
CJG
C019
Technology & Design Studio 01.
n/a A
EASI-JOIST WALL HANGERS SECURED ONTO 140 x 50mm C16 TIMBER SOLEPLATE & FIXED TO FLOOR JOIST VIA GALVANIZED PRESS-STUD FIXINGS (TO MANUFACTURES SPECIFICATIONS)
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
15mm THK T&G FLOOR BOARDS, SECURED TO PANEL WITH C/S SCREWS 15mm THK OSB BOARD LAID OVER & SECURED TO FLOOR EASI-JOIST ROOF BEAMS WITH SUITABLE FIXINGS
4000 x 195 x 97mm THK EASI-JOIST FLOOR BEAMS @ 600mm C/C (UNLESS OTHERWISE STATED) 120mm THK KINGSPAN KOOLTHERM (K70) INSULATED PANEL, PLACED INBWETWEEN TIMBER STUD FRAME. 12.5mm THK PLASTERBOARD, WITH 3mm PLASTER SKIM FINISH SECURED TO UNDERSIDE OF EASI-JOISTS. 2400 x 120 x 20mm THK TIMBER CLADDING SYSTEM (CLIENT'S ASTHETIC RECOMMENDATION) FIXED TO 25x25mm TIMBER BATTON RAILS BEFORE ATTACHED TO EXTERNAL OSB BOARD. 32.5mm THK KINGSPAN KOOLTHERM (K118) INSULATED PLASTERBOARD WITH PLASTER SKIM FINISHED, SECURED ONTO TIMBER FRAME WITH C/S SCREWS . KINGSPAN NILVENT BREATHABLE MEMBRANE, FIXED ONTO INSULATED PLASTERBOARD. 140mm THK C16 TIMBER STUD PARTITION WALL SECURED WITH SUITABLE FIXINGS & LAID ONTOP OF 140x100mm TIMBER SOLEPLATE
A
Revision Description
SUSPENDED FLOOR CONNECTION DETAIL
Mr A O'Roake
40
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Suspened Flr Technical Detail West Bridgeford, Nottingham 1:5@ A3
SCALE 1:5
4B
Craig Greogry - N0726862
26/03/18
Mr R. Dundass
1500 x 1200mm DOUBLE GLAZED WINDOW INSTALLED TO MANUFACTURES SPECIFICATION & SUPPLIED BY CRITTAL 10mm THK ADVENTEC OSB BOARD WITH DUPONT AIRGUARD REFLECTIVE VAPOUR BARRIER MEMBRANE SECURED ON WITH C/S SCREWS TO TIMBER STUD WALL.
CJG
17/05/18
CJG
C020
Technology & Design Studio 01.
n/a A
LIGHT TRACKER REFLECTOR, SOUTH FACING IN ROOF CONSTRUCTION, FITTED TO MANUFACTURES SPECIFICATIONS
X X X
Preliminary Client Approval Planning
TOP TUBE ANGLE ADAPTOR 0-30°, PROTRUDING THROUGH SUSPENDING CEILING / ROOF TRUSS CONSTRUCTION & SUITABLY FINISHED (ACCORDING TO ROOM SCHEDULES)
1.
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER.
2.
ALL TECHNICAL COMPONENTS HAVE BEEN REFERENCED VIA MANUFACTURES DWGS, BROCHURES & DOWNLOADABLE CONTENT. 2.1. MANUFACTURER - SOLATUBE PRODUCTS
EXPANSION JOINT SEAL, SPECIFIED BY MANUFACTURE REQUIREMENT AROUND ROOF OPENING. EXPANSION TUBE, RUNNING THROUGH ROOF JOIST CONSTRUCTION TO DESIGNATED OPENING IN CEILING / ROOF JOIST.
3.
PROPOSED SOLATUBE SYSTEMS ARE TO BE CONSTRUCTED & FITTED INTO ROOF SYSYEM, WITH ALL SERVICES & MECHANICAL COMPONENTS HIDDEN FROM VIEW.
4.
ADDITIONAL PV16 SOLAR PHOTOVOLTAIC PANELS (SUPPLIED BY CLEARLINE FUSION) TO BE FITTED ONTO PROPOSED EXTENSIONS ROOF STRUCTURE, TO ADD IN ELECTRICAL SUPPLY FOR SOLATUBE LED LIGHTING
A
Revision Description
200 x 255 x 10mm THK GREY SLATE, SECURED TO 25x35mm TIMBER NOGGINS WITH C/S SCREWS 15mm THK OSB BOARD & VAPOUR BARRIER LAID OVER & SECURED TO EASI-JOIST ROOF BEAMS WITH SUITABLE FIXINGS 4000 x 195 x 97mm THK EASI-JOIST ROOF BEAMS @ 600mm C/C (UNLESS OTHERWISE STATED) 120mm THK KINGSPAN KOOLTHERM (K70) INSULATED PANEL, PLACED INBWETWEEN TIMBER STUD FRAME. 32.5mm THK KINGSPAN KOOLTHERM (K118) INSULATED PLASTERBOARD WITH PLASTER SKIM FINISHED, SECURED ONTO TIMBER FRAME WITH C/S SCREWS .
JUNCTION BOX ASSEMBLY INCLUDING DC DRIVER (ONLY REQUIRED FOR PRIMARY SYSTEM) BOTTOM TUBE ANGLE ADAPTOR 0-30°, PROTRUDING THROUGH SUSPENDING CIELING / ROOF TRUSS CONSTRUCTION & SUITABLEY FINISHED (ACCORDING TO ROOM SCHEDULES) SOLAR TUBE LED SYSTEM LUMINAIRE, FITTED & ASSEMBLED TO MANUFACTURES SPECIFICATIONS
26/03/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
OCCUPANCY ROOM SENSOR (OPTIONAL TO CLIENTS SPECIFICATION)
Coach House Extension & Refurbishment.
SOLA-TUBE FITTING DETAIL
SolaTube Technical Detail West Bridgeford, Nottingham
SCALE 1:5
1:5@ A3
4B
41
CJG
Craig Greogry - N0726862
17/05/18
CJG
C021
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
AS BUILT BEAVER-GREEN HOUSE (ONGOING)
1. 2.
WHITE COATED TIMBER BARGEBOARD.
3.
GREY SLATE ROOFING.
4.
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING RED BRICK VICTORIAN MASONRY EXTERNAL FINISH. ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. ALL GUTTERING HAS BEEN UPDATED TO BLACK UPVC MATERIAL ROOF MATERIAL IS A GREY/BLACK CERAMIC SLATE.
100mm Ø BLACK UPVC DRAINAGE
EXISTING DWELLING
TIMBER CLADDING SYSTEM BUFF NATURAL STONE FACING
B
ROOF REDESIGN
CJG
30/04/18
A
SHADOWS ALTERED
CJG
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
EAST ELEVATION SCALE 1:50
Coach House Extension & Refurbishment.
Proposed East Elevation West Bridgeford, Nottingham 1:50@ A3
4B
42
Craig Greogry - N0726862
17/05/18
CJG
C022
Technology & Design Studio 01.
n/a B
X X X
Preliminary Client Approval Planning
MARLEY ETERNET CLAY RIDGE TILES GREY SLATE ROOFING.
1. 2. 3. 4.
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING RED BRICK VICTORIAN MASONRY EXTERNAL FINISH. ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. ALL GUTTERING HAS BEEN UPDATED TO BLACK UPVC MATERIAL ROOF MATERIAL IS A GREY/BLACK CERAMIC SLATE.
PV16 SOLAR PHOTOVOLTAIC PANELS
PROPOSED SOLA-TUBE FIXTURE
TIMBER CLADDING SYSTEM FL
FL
SVP DOWNPIPE
EXISTING HEDGEROW KEPT TO NHBC REGULATIONS
EXISTING DWELLING
FL
FL
FL
BUFF NATURAL STONE FACING GL
SOUTH ELEVATION
B
ROOF REDESIGN
CJG
30/04/18
A
SHADOWS ALTERED
CJG
23/04/18
ENTRANCE LOBBY, SAME FACADE AS GROUND FLOOR
Mr A O'Roake
Mr R. Dundass
SCALE 1:50
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Proposed South Elevation West Bridgeford, Nottingham 1:50@ A3
4B
43
Craig Greogry - N0726862
17/05/18
CJG
C023
Technology & Design Studio 01.
n/a B
X X X
Preliminary Client Approval Planning
1. 2. 3. 4.
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
EXISTING RED BRICK VICTORIAN MASONRY EXTERNAL FINISH. ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. ALL GUTTERING HAS BEEN UPDATED TO BLACK UPVC MATERIAL ROOF MATERIAL IS A GREY/BLACK CERAMIC SLATE.
EXISTING DWELLING
WEST ELEVATION
SCALE 1:50
B
ROOF REDESIGN
CJG
30/04/18
A
SHADOWS ALTERED
CJG
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Proposed West Elevation West Bridgeford, Nottingham 1:50@ A3
4B
44
Craig Greogry - N0726862
17/05/18
CJG
C024
Technology & Design Studio 01.
n/a B
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
MARLEY ETERNET CLAY RIDGE TILES GREY SLATE ROOFING. 1. 2. 3. 4.
EXISTING RED BRICK VICTORIAN MASONRY EXTERNAL FINISH. ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. ALL GUTTERING HAS BEEN UPDATED TO BLACK UPVC MATERIAL ROOF MATERIAL IS A GREY/BLACK CERAMIC SLATE.
100mm Ø BLACK UPVC DRAINAGE PROPOSED SOLA-TUBE FIXTURE
EXISTING DWELLING
GL
NORTH ELEVATION SCALE 1:50
BUFF NATURAL STONE FACING TIMBER CLADDING SYSTEM
B
ROOF REDESIGN
CJG
30/04/18
A
SHADOWS ALTERED
CJG
23/04/18
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Proposed North Elevation West Bridgeford, Nottingham 1:50@ A3
4B
45
Craig Greogry - N0726862
17/05/18
CJG
C025
Technology & Design Studio 01.
n/a B
X X X
Preliminary Client Approval Planning
Doors & Windows Schedule: Coach House Extension. Internal or External
Material
Opening Condition
Additional Information
Ground Floor, Entrance
1
1250
1300
External
Mild steel
Fixed Light
RAL colour finish
X
Ground Floor, Entrance
1
1600
1300
External
Mild steel
Fixed Light
RAL colour finish
W 03
X
Ground Floor, Living Area
1
1150
1500
External
Mild steel
Fixed Light
RAL colour finish
W 04
X
Ground Floor, Living Area
1
2350
1500
External
Mild steel
Fixed Light
RAL colour finish
Reference Number
Existing or Proposed
Location
W 01
X
W 02
QTY
W (mm)
H (mm)
W 05
X
First Floor, Cupboard
1
1200
500
External
Mild steel
Fixed Light & Top Hung Casement
RAL colour finish
W 06
X
First Floor, Bathroom
1
1100
500
External
Mild steel
Fixed Light & Top Hung Casement
Frosted Glass, RAL colour finish
W 07
X
First Floor, Bathroom
1
1100
1100
External
Mild steel
Top-Hung casment
Skylight, RAL colour finish
W 08
X
First Floor, Bed 02
1
2350
820
External
Mild steel
Fixed Light
RAL colour finish
W 09
X
First Floor, Bed 02
1
2350
820
External
Mild steel
Fixed Light
RAL colour finish
W 10
X
First Floor, Ensuite
1
500
820
External
Mild steel
Fixed Light & Top Hung Casement
Frosted Glass, RAL colour finish
D 01
X
Ground Floor, Entrance
1
920
2100
External
Mild steel
Left Side Hung Casement
Proposed Extension's Crittal Door set & RAL finish
X
Ground Floor, Extension
1
920
2100
Internal
Timber
Right Side Hung Casement
Proposed living area. Wood stained
D 03
X
First Floor, Cupboard
1
920
2100
Internal
Timber
Left Side Hung Casement
Existing doorframe, Wood stained reapply.
D 04
X
First Floor, Bathroom
1
920
2100
Internal
Timber
Right Side Hung Casement
Existing doorframe, Wood stained reapply & pretreated
1
920
2100
Internal
Timber
Right Side Hung Casement
Proposed. Wood stained
Timber
Left Side Hung Casement
Proposed. Wood stained
Timber
Left Side Hung Casement
Proposed. Wood stained & pretreated
D 02
D 05
X
First Floor, Bedroom 01
D 06
X
First Floor, Bedroom 02
D 07
X
First Floor, Ensuite
1 1
920 920
2100 2100
Internal Internal
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
1.
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH EACH OTHER.
2.
ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE STATED.
3.
ALL OPENINGS ARE TIMBER FRAME CONSTRUCTION. 3.1. BUILT INTO PROPOSED TIMBER STUD FRAMES 3.2. CRITTAL OPENINGS BUILT TO MANUFACTURES' SPECIFICATIONS INTO TIMBER FRAMES (SEE DETALS).
MANUFACTURE'S SPECIFICATION: ACOUSTIC: DOUBLE GLAZING GLASS 28-30 dB FIRE RESISTANCE: 60 Min FR TO BS 476 pt 22:1987 THERMAL: MANUFACTURE'S SPECIFICATION TO PART L OF BR. CONDENSATION: N/A WITH CRITTAL SYSTEMS. IF CONDENSATION OCCURS, WILL BE PRESENT IN THE WINDOW FRAME ITSELF. VENTILATION APPLIED IF NEEDED.
OUTSIDE
OUTSIDE GLAZING BEAD 12255 SECTION FOR 24MM GLASS (SHOWN)
IGU
12254 SECTION FOR 16 & 18MM GLASS
SILICONE CAP
Mr A O'Roake Mr R. Dundass
DISTANCE PIECES
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
TAPE (TIMBER SUB-FRAME, MADE TO MANUFACTURE) SETTING BLOCK
BEAD CLIPS
Coach House Extension & Refurbishment.
DOOR & WINDOW SCHEDULE West Bridgeford, Nottingham AS SHOWN @ A3
4B
46
Craig Greogry - N0726862
17/05/18
CJG
C026
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
7
6 5 4 3 2 1
X X X
Building Control Fire Precautions Pre-Tender
Measurement Tender Contract
X X X
X X
Site As Built
CUPBOARD
DINING ROOM
BEDROOM 01 EM BOX
EM BOX BATHROOM KITCHEN
1.
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH SUBMITTED DRAWING PACKAGE
2.
ALL FIRST FLOOR SERVICES ARE TO BE LOCATED WITHIN EASI-JOIST FLOOR BEAMS, MANUFACTURED BY WOLF-SYSTEMS 2.1. SUITABLY INSULATED & WITH PROTECTIVE COVERINGS. 2.2. BUILT TO CONTRACTOR'S SPECIFICATION
LOBBY
3.
LIVING ROOM
BEDROOM 02
ENSUITE
GROUND FLOOR PLAN
ELECTRICAL SYSTEM IS TO BE CONNECTED TO EXISTING SERVICES LOCATED IN DWELLING 3.1. SITE INVESTIGATION WILL BE NEEDED FOR EXISTING ELECTRICAL LAYOUT & DISPOSITION 3.2. ELCTRICAL DISTRUBUTION BOX TO BE UPDATED & REINSTALLED. 3.3. DEMOLITION WORK WILL BE NEEDED FOR PROPOSED SOLA-TUBES TO BE INSTALLED THROUGH EXISTING FIRST FLOOR & ROOF CONSTRUCTION.
FIRST FLOOR PLAN SCALE 1:100
SCALE 1:100
LUMINARIES 2-WAY POWER SOCKET 2 WAY LIGHT SWITCH SOLA-TUBES INSTALLED TO MANUFACTURES SPECIFICATIONS
Mr A O'Roake
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Prop' Electrical System Layout West Bridgeford, Nottingham 1:100@ A3
4B
47
Craig Greogry - N0726862
17/05/18
CJG
E001
Technology & Design Studio 01.
n/a A
RE
RE
TAG
TAG
X X X
Preliminary Client Approval Planning
7
6 5 4 3 2 1
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
CUPBOARD
BEAMOVER
KITCHEN
EM BOX
BEDROOM 01 DINING ROOM EM BOX BATHROOM
1.
ALL DRAWINGS ARE TO BE READ IN CONJUCTION WITH SUBMITTED DRAWING PACKAGE.
2.
ALL DOMESTIC DRAINAGE TO BE UPVC MATERIAL & FITTED TO MANUFACTURES SPECIFICATIONS WITHIN BATHROOM/ENSUITE.
3.
BATHROOM FITTINGS TO BE CHOSEN BY CLIENT & INSTALLED TO MANUFACTURERS SPECIFICATION.
4.
KITCHEN FITTINGS TO BE CHOSEN BY CLIENT & INSTALLED TO MANUFACTURERS SPECIFICATION
BEAMOVER LOBBY
LIVING ROOM
BEDROOM 02
FOUL WATER RUN IC 02
FOUL WATER RUN
IC 01
IC 02
IC 01
D08
DRAINAGE: 5. ALL DRAINAGE WORKS TO BE IN ACCORDANCE WITH BS EN 12056 & 752 6.
ALL PROPOSED GUTTER DRAINAGE IS TO BE 100mm DIA UPVC PIPEWORK AND DRAINAGE OUTLETS TO BE 63mm DIA
7.
ALL PROPOSED UNDERGROUND DRAINAGE PIPEWORK TO BE VITRIFIED CLAY BY HEPWORTH NOMINAL 100mm DIAMETER UNLESS STATED OTHERWISE
8.
ALL DRAINAGE PIPEWORK TO BE BEDDED IN GRANULAR MATERIAL AGGREGATE CLASS F BEDDING 10mm
2400mm ENSUITE
GROUND FLOOR PLAN
FIRST FLOOR PLAN SCALE 1:100
SCALE 1:100
SANITARY PIPEWORK NOTES: BATHROOM:
WHB TO DRAIN VIA 32mm DIAM OUTLET TO A BOTTTLE TRAP TO A COMMON WASTE PIPE 40mm DIA FROM BATH TO 100mm DIA STACKPIPE (SVP) W/C TO DRAIN VIA 100mm DIA WC CONNECTOR AND BRANCH TO 100mm DIA STACK BATH/SHOWER TO DRAIN VIA 40mm OUTLET TO BATH TRAP TO 40mm DIA WASTE TO 100mm STACKPIPE (SVP) A
Revision Description
CJG
26/03/18
KITCHEN: Mr A O'Roake
SINK TO DRAIN VIA A 40mm DIA OUTLET TO A BOTTTLE TRAP TO 40mm DIA COMMON WASTE PIPE (THROUGH WALL TO VERTICAL PIPE TO GULLY)
Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
GENERALLY: Coach House Extension
ALLOW ACCESS CAPS AT ALL CHANGES OF DIRECTIONS
& Refurbishment.
STACK TO CONNECT TO DRAIN SYSTEM VIA A REST BEND
Proposed Drainage Layout West Bridgeford, Nottingham
TRAPS TO WASTE FITTINGS TO BE 75mm DEEP UNLESS OTHERWISE STATED
1:100@ A3
4B
48
Craig Greogry - N0726862
17/05/18
CJG
M001
Technology & Design Studio 01.
n/a A
X X X
Preliminary Client Approval Planning
Building Control Fire Precautions Pre-Tender
X X X
Measurement Tender Contract
X X X
X X
Site As Built
TA 7
TB
6 5 4 3 2 1 CUPBOARD
BEAMOVER
NEWLY INSTALLED COMBI-BOILER LOCATED IN KITCHEN
EM BOX
BEDROOM 01 DINING ROOM EM BOX BATHROOM
1.
KITCHEN BEAMOVER
ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH SUBMITTED DRAWING PACKAGE
2.
ALL FIRST FLOOR SERVICES ARE TO BE LOCATED WITHIN EASI-JOIST FLOOR BEAMS, MANUFACTURED BY WOLF-SYSTEMS 2.1. SUITABLY INSULATED & WITH PROTECTIVE COVERINGS. 2.2. BUILT TO CONTRACTOR'S SPECIFICATION
LOBBY
LIVING ROOM
3.
HEATING SYSTEM IS TO BE A SEALED SYSTEM 3.1. CONNECTED TO NEWLY INSTALLED COMBI-BOILER SYSTEM LOCATED IN KITCHEN.
BEDROOM 02
D08 2400mm ENSUITE
GROUND FLOOR PLAN
FIRST FLOOR PLAN SCALE 1:100
SCALE 1:100
A
Revision Description
CJG
26/03/18
Mr A O'Roake Mr R. Dundass
104 Arkwright Studio, Nottingham, Nottinghamshire, England NG1 4BU Tel : 123456789
Coach House Extension & Refurbishment.
Prop' Heating System Layout West Bridgeford, Nottingham 1:100@ A3
4B
49
Craig Greogry - N0726862
17/05/18
CJG
M002
Technology & Design Studio 01.
n/a A
50
Craig Greogry - N0726862
Technology & Design Studio 01.
51
Craig Greogry - N0726862
Technology & Design Studio 01.
52
Craig Greogry - N0726862
Technology & Design Studio 01.
53
Craig Greogry - N0726862
Technology & Design Studio 01.