1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
VINCINITY MAP: PROJECT INFORMATION:
SHEET INDEX:
PROJECT ADDRESS
610 NORTH SANTIAGO STREET, SANTA ANA, CA 92701
INFORMATION
4-STORY 65-UNIT TYPE MIXED-USE/ MULTIFAMILY RESIDENTIAL OVER 1-STORY TYPE 1A RETAIL
G-101 A-001 A-100 A-101 A-105 A-110 A-111 A-112 A-200 A-300 A-310 A-400 A-410 A-420 A-501 A-503 A-600 MECHANICAL M-100 ELECTRICAL E-100 PLUMBING P-100
B
COVER SHEET CODE ANALYSIS SITE PLAN SITE SECTION OCCUPANCY/EGRESS PLANS GROUND FLOOR PLAN PODIUM FLOOR PLAN SUBSEQUENT FLOOR PLAN BUILDING ELEVATIONS BUILDING SECTIONS WALL SECTION UNIT PLAN INTERIOR VISUALIZATIONS ENLARGED STAIR PLAN / SECTION WALL AND FLOOR ASSEMBLIES DETAILS WINDOW SCHEDULE MECHANICAL RCP AND DIAGRAM ELECTRICAL PLUMBING RCP AND DIAGRAM
620 N Santiago St, Santa Ana, CA 92701
BUILDING SUMMARY:
A
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
C
ABREVIATION:
Description MIDTERM FINAL
MIXED-USE MULTI-FAMILY COMPLEX
D
Issued by J.P. J.P.
SANTA ANA HOUSING
No. 01 02
GROSS SITE AREA
68,933 SF
STORIES ABOVE GRADE
5 STORIES
STORIES ABOVE GRADE
0 STORIES
ZONING GENERAL PLAN DESIGNATION
CR
MAXIMUM HEIGHT LIMIT
75'-0"
CONSTRUCTION TYPE
VA OVER 1A (5 LEVELS ABOVE GRD
PROPOSED USE
MIXED-USE RESIDENTIAL/PARKING/ RETAIL
FULLY SPRINKLERED BUILDING WITH NFPA 13 SPRINKLER SYSTEM (SECTION 903.2.11.3)
TITLE SHEET
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
G-101
FIRE ALARM AND DETECTION SYSYEM (SECTION 907.2.2) Scale
AS INDICATED
APPLICABLE CODE:
CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA PLUMBING CODE (CPC) 2022 CALIFORNIA MECHANICAL CODE (CMC) 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA GREEN STANDARDS STANDARDS CODE 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 2022 AMERICANS WITH DISABILITIES ACT (ADA) NATIONAL FIRE PROTECTION ASSOCIATION STANDARD (NFPA 13 AND 17) LOS ANGELES MUNICIPAL CODE SANTA ANA MUNICIPAL CODE
D CALIFORNIA BUILDING CODE 2022 SECTION 309 MERCANTILE GROUP M
MERCANTILE GROUP M OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A BUILDING OR STRUCTURE OR A PORTION THEREOF FOR THE DISPLAY AND SALE OF MERCHANDISE, AND INVOLVES STOCKS OF GOODS, WARES OR MERCHANDISE INCIDENTAL TO SUCH PURPOSES AND WHERE THE PUBLIC HAS ACCESS. MERCANTILE OCCUPANCIES SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
C
DEPARTMENT STORES DRUG STORES MARKETS GREENHOUSES FOR DISPLAY AND SALE OF PLANTS THAT PROVIDE PUBLIC ACCESS. MOTOR FUEL-DISPENSING FACILITIES RETAIL OR WHOLESALE STORES SALES ROOMS 310.1 RESIDENTIAL GROUP R RESIDENTIAL GROUP R INCLUDES, AMONG OTHERS, THE USE OF A BUILDING OR STRUCTURE, OR A PORTION THEREOF, FOR SLEEPING PURPOSES WHEN NOT CLASSIFIED AS AN INSTITUTIONAL GROUP I OR WHEN NOT REGULATED BY THE CALIFORNIA RESIDENTIAL CODE. GROUP R OCCUPANCIES NOT CONSTRUCTED IN ACCORDANCE WITH THE CALIFORNIA RESIDENTIAL CODE AS PERMITTED BY SECTIONS 310.4.1 AND 310.4.2 SHALL COMPLY WITH SECTION 420. 310.3 RESIDENTIAL GROUP R-2
B
RESIDENTIAL GROUP R-2 OCCUPANCIES CONTAINING SLEEPING UNITS OR MORE THAN TWO DWELLING UNITS WHERE THE OCCUPANTS ARE PRIMARILY PERMANENT IN NATURE, INCLUDING: APARTMENT HOUSES LARGE FAMILY CHILD CARE SMALL FAMILY CHILD CARE CONGREGATE RESIDENCES (NONTRANSIENT) WITH MORE THAN 16 OCCUPANTS BOARDING HOUSES (NONTRANSIENT) CONVENTS, DORMITORIES FRATERNITIES AND SORORITIES MONASTERIES HOTELS (NONTRANSIENT) LIVE/WORK UNITS MOTELS (NONTRANSIENT) VACATION TIMESHARE PROPERTIES [HCD 1] EFFICIENCY DWELLING UNITS (TRANSIENT) 703A.5.1 GENERAL MATERIAL AND MATERIAL ASSEMBLIES TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 703A SHALL MAINTAIN THEIR FIRE TEST PERFORMANCE UNDER CONDITIONS OF USE, WHEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS. 703A.5.3 SURFACE TREATMENT PROTECTION
A
THE USE OF PAINTS, COATINGS, STAINS OR OTHER SURFACE TREATMENTS ARE NOT AN APPROVED METHOD OF PROTECTION AS REQUIRED IN THIS CHAPTER.
4
5
703A.7 STANDARDS OF QUALITY
1202.3 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES
THE STATE FIRE MARSHAL STANDARDS FOR EXTERIOR WILDFIRE EXPOSURE PROTECTION LISTED BELOW AND AS REFERENCED IN THIS CHAPTER ARE LOCATED IN THE CALIFORNIA REFERENCED STANDARDS CODE, PART 12 AND CHAPTER 35 OF THIS CODE. SFM STANDARD 12-7A-1, EXTERIOR WALL SIDING AND SHEATHING. A FIRE RESISTANCE TEST STANDARD CONSISTING OF A 150 KW INTENSITY DIRECT FLAME EXPOSURE FOR A 10-MINUTE DURATION. SFM STANDARD 12-7A-2, EXTERIOR WINDOWS. A FIRE RESISTANCE TEST STANDARD CONSISTING OF A 150 KW INTENSITY DIRECT FLAME EXPOSURE FOR AN 8-MINUTE DURATION. SFM STANDARD 12-7A-3, HORIZONTAL PROJECTION UNDERSIDE A FIRE RESISTANCE TEST STANDARD CONSISTING OF A 300 KW INTENSITY DIRECT FLAME EXPOSURE FOR A 10-MINUTE DURATION. SFM STANDARD 12-7A-4, DECKING. A TWO-PART TEST CONSISTING OF A HEAT RELEASE RATE (PART A) DECK ASSEMBLY COMBUSTION TEST WITH AN UNDER DECK EXPOSURE OF 80 KW INTENSITY DIRECT FLAME FOR A 3-MINUTE DURATION, AND A (PART B) SUSTAINED DECK ASSEMBLY COMBUSTION TEST CONSISTING OF A DECK UPPER SURFACE BURNING EMBER EXPOSURE WITH A 12 MPH WIND FOR 40 MINUTES USING A 2.2LB (1KG) BURNING "CLASS A" SIZE 12" X 12" X 2.25" (300 MM X 300 MM X 57 MM) ROOF TEST BRAND. SFM STANDARD 12-7A-4A, DECKING ALTERNATE METHOD A. A HEAT RELEASE RATE DECK ASSEMBLY COMBUSTION TEST WITH AN UNDER DECK EXPOSURE OF 80 KW INTENSITY DIRECT FLAME FOR A 3-MINUTE DURATION. ASTM D2898 STANDARD PRACTICE FOR ACCELERATED WEATHERING OF FIRE-RETARDANT-TREATED WOOD FOR FIRE TESTING. ASTM D3909/D3909M STANDARD SPECIFICATION FOR ASPHALT ROLL ROOFING (GLASS FELT) SURFACED WITH MINERAL GRANULES. ASTM E84 STANDARD TEST METHOD FOR SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. ASTM E119 STANDARD TEST METHODS FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS. ASTM E2632/E2632M STANDARD TEST METHOD FOR EVALUATING THE UNDER-DECK FIRE TEST RESPONSE OF DECK MATERIALS. ASTM E2707 STANDARD TEST METHOD FOR DETERMINING FIRE PENETRATION OF EXTERIOR WALL ASSEMBLIES USING A DIRECT FLAME IMPINGEMENT EXPOSURE. ASTM E2726/E2726M STANDARD TEST METHOD FOR EVALUATING THE FIRE TEST RESPONSE OF DECK STRUCTURES TO BURNING BRANDS. ASTM E2768 STANDARD TEST METHOD FOR EXTENDED DURATION SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS (30-MINUTE TUNNEL TEST). ASTM E2886/E2886M STANDARD TEST METHOD FOR EVALUATING THE ABILITY OF EXTERIOR VENTS TO RESIST THE ENTRY OF EMBERS AND DIRECT FLAME IMPINGEMENT. ASTM E2957 STANDARD TEST METHOD FOR RESISTANCE TO WILDFIRE PENETRATION OF EAVES, SOFFITS AND OTHER PROJECTIONS. NFPA 257 STANDARD ON FIRE TEST FOR WINDOW AND GLASS BLOCK ASSEMBLIES. UL 263 STANDARD FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS. UL 723 STANDARD FOR TEST FOR SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS.
IN CLIMATE ZONES 5, 6, 7 AND 8, ANY AIR-IMPERMEABLE INSULATION SHALL BE A CLASS II VAPOR RETARDER OR SHALL HAVE A CLASS II VAPOR RETARDER COATING OR COVERING IN DIRECT CONTACT WITH THE UNDERSIDE OF THE INSULATION.WHERE AIR-PERMEABLE INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH ITEM 5.1.1. IN ADDITION TO THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE R-VALUES IN TABLE 1202.3 FOR CONDENSATION CONTROL.WHERE BOTH AIR-IMPERMEABLE AND AIR-PERMEABLE INSULATION ARE PROVIDED, THE AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT CONTACT WITH THE UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING AND SHALL BE IN ACCORDANCE WITH THE R-VALUES IN TABLE 1202.3 FOR CONDENSATION CONTROL. THE AIR-PERMEABLE INSULATION SHALL BE INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE INSULATION.ALTERNATIVELY, SUFFICIENT RIGID BOARD OR SHEET INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING TO MAINTAIN THE MONTHLY AVERAGE TEMPERATURE OF THE UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING ABOVE 45°F (7°C). FOR CALCULATION PURPOSES, AN INTERIOR AIR TEMPERATURE OF 68°F (20°C) IS ASSUMED AND THE EXTERIOR AIR TEMPERATURE IS ASSUMEDTO BE THE MONTHLY AVERAGE OUTSIDE AIR TEMPERATURE OF THE THREE COLDEST MONTHS.
704A.4 ALTERNATIVE METHODS FOR DETERMINING IGNITION-RESISTANT MATERIAL ANY ONE OF THE FOLLOWING SHALL BE ACCEPTED AS MEETING THE DEFINITION OF IGNITION-RESISTANT MATERIAL: NONCOMBUSTIBLE MATERIAL. MATERIAL THAT COMPLIES WITH THE DEFINITION FOR NONCOMBUSTIBLE MATERIALS IN SECTION 202. FIRE-RETARDANT-TREATED WOOD. FIRE-RETARDANT-TREATED WOOD IDENTIFIED FOR EXTERIOR USE THAT COMPLIES WITH THE REQUIREMENTS OF SECTION 2303.2. FIRE-RETARDANT-TREATED WOOD SHINGLES AND SHAKES. FIRE-RETARDANT-TREATED WOOD SHINGLES AND SHAKES, AS DEFINED IN SECTION 1505.6 AND LISTED BY STATE FIRE MARSHAL FOR USE AS "CLASS B" ROOF COVERING, SHALL BE ACCEPTED AS AN IGNITION-RESISTANT WALL COVERING MATERIAL WHEN INSTALLED OVER SOLID SHEATHING. 705A.2 ROOF COVERINGS WHERE THE ROOFING PROFILE HAS AN AIRSPACE UNDER THE ROOF COVERING, INSTALLED OVER A COMBUSTIBLE DECK, A 72 LB. (32.7 KG) CAP SHEET COMPLYING WITH ASTM D3909 STANDARD SPECIFICATION FOR "ASPHALT ROLLED ROOFING (GLASS FELT) SURFACED WITH MINERAL GRANULES," SHALL BE INSTALLED OVER THE ROOF DECK. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS, TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS. EXCEPTION: CAP SHEET IS NOT REQUIRED WHEN NO LESS THAN 1" OF MINERAL WOOL BOARD OR OTHER NONCOMBUSTIBLE MATERIAL IS LOCATED BETWEEN THE ROOFING MATERIAL AND WOOD FRAMING OR DECK. ALTERNATELY, A CLASS A FIRE RATED ROOF UNDERLAYMENT, TESTED IN ACCORDANCE WITH ASTM E108, SHALL BE PERMITTED TO BE USED. IF THE SHEATHING CONSISTS OF EXTERIOR FIRE-RETARDANT-TREATED WOOD, THE UNDERLAYMENT SHALL NOT BE REQUIRED TO COMPLY WITH A CLASS A CLASSIFICATION. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS, TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS. 705A.4 ROOF GUTTERS ROOF GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND DEBRIS IN THE GUTTER. 1202.2.1 VENTILATED ATTICS AND RAFTER SPACES ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE MOVEMENT OF AIR. AN AIRSPACE OF NOT LESS THAN 1 INCH (25 MM) SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL BE NOT LESS THAN 1/150 OF THE AREA OF THE SPACE VENTILATED. VENTILATORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. EXCEPTION: THE NET FREE CROSS-VENTILATION AREA SHALL BE PERMITTED TO BE REDUCED TO 1/300 PROVIDED BOTH OF THE FOLLOWING CONDITIONS ARE MET: IN CLIMATE ZONES 6, 7 AND 8, A CLASS I OR II VAPOR RETARDER IS INSTALLED ON THE WARM-IN-WINTER SIDE OF THE CEILING. AT LEAST 40 PERCENT AND NOT MORE THAN 50 PERCENT OF THE REQUIRED VENTING AREA IS PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF THE ATTIC OR RAFTER SPACE. UPPER VENTILATORS SHALL BE LOCATED NOT MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE, MEASURED VERTICALLY, WITH THE BALANCE OF THE VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. WHERE THE LOCATION OF WALL OR ROOF FRAMING MEMBERS CONFLICTS WITH THE INSTALLATION OF UPPER VENTILATORS, INSTALLATION MORE THAN 3 FEET (914 MM) BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE SHALL BE PERMITTED.
1202.5.2.1 BATHROOMS
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS No. 01 02
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
ROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE MECHANICALLY VENTILATED IN ACCORDANCE WITH THE CALIFORNIA MECHANICAL CODE. THE MINIMUM EXHAUST RATE SHALL NOT BE LESS THAN THAT ESTABLISHED BY TABLE 403.7 "MINIMUM EXHAUST RATES." SEE CALIFORNIA MECHANICAL CODE, CHAPTER 5, FOR ADDITIONAL PROVISIONS RELATED TO ENVIRONMENTAL AIR DUCTS. [HCD 1] IN ADDITION TO THE REQUIREMENTS IN THIS SECTION AND IN THE CALIFORNIA MECHANICAL CODE, BATHROOMS IN GROUP R OCCUPANCIES SHALL BE MECHANICALLY VENTILATED IN ACCORDANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), CHAPTER 4, DIVISION 4.5. 1204.2.1 ADJOINING SPACES FOR THE PURPOSE OF NATURAL LIGHTING, ANY ROOM IS PERMITTED TO BE CONSIDERED AS A PORTION OF AN ADJOINING ROOM WHERE ONE-HALF OF THE AREA OF THE COMMON WALL IS OPEN AND UNOBSTRUCTED AND PROVIDES AN OPENING OF NOT LESS THAN ONE-TENTH OF THE FLOOR AREA OF THE INTERIOR ROOM OR 25 SQUARE FEET (2.32 M2), WHICHEVER IS GREATER. EXCEPTION: OPENINGS REQUIRED FOR NATURAL LIGHT SHALL BE PERMITTED TO OPEN INTO A SUNROOM WITH THERMAL ISOLATION OR A PATIO COVER WHERE THE COMMON WALL PROVIDES A GLAZED AREA OF NOT LESS THAN ONE-TENTH OF THE FLOOR AREA OF THE INTERIOR ROOM OR 20 SQUARE FEET (1.86 M2), WHICHEVER IS GREATER. 1204.2.2 EXTERIOR OPENINGS EXTERIOR OPENINGS REQUIRED BY SECTION 1204.2 FOR NATURAL LIGHT SHALL OPEN DIRECTLY ONTO A PUBLIC WAY, YARD OR COURT, AS SET FORTH IN SECTION 1205. EXCEPTIONS: REQUIRED EXTERIOR OPENINGS ARE PERMITTED TO OPEN INTO A ROOFED PORCH WHERE THE PORCH MEETS ALL OF THE FOLLOWING CRITERIA: ABUTS A PUBLIC WAY, YARD OR COURT. HAS A CEILING HEIGHT OF NOT LESS THAN 7 FEET (2134 MM). HAS A LONGER SIDE AT LEAST 65 PERCENT OPEN AND UNOBSTRUCTED. SKYLIGHTS ARE NOT REQUIRED TO OPEN DIRECTLY ONTO A PUBLIC WAY, YARD OR COURT. 1204.3 ARTIFICIAL LIGHT ARTIFICIAL LIGHT SHALL BE PROVIDED THAT IS ADEQUATE TO PROVIDE AN AVERAGE ILLUMINATION OF 10 FOOTCANDLES (107 LUX) OVER THE AREA OF THE ROOM AT A HEIGHT OF 30 INCHES (762 MM) ABOVE THE FLOOR LEVEL. 505.2 MEZZANINES
620 N Santiago St, Santa Ana, CA 92701
E
3
MIXED-USE MULTI-FAMILY COMPLEX
CODE ANALYSIS:
2
SANTA ANA HOUSING
1
A MEZZANINE OR MEZZANINES IN COMPLIANCE WITH SECTION 505.2 SHALL BE CONSIDERED A PORTION OF THE STORY BELOW. SUCH MEZZANINES SHALL NOT CONTRIBUTE TO EITHER THE BUILDING AREA OR NUMBER OF STORIES AS REGULATED BY SECTION 503.1. THE AREA OF THE MEZZANINE SHALL BE INCLUDED IN DETERMINING THE FIRE AREA. THE CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE FLOOR CONSTRUCTION SHALL BE NOT LESS THAN 7 FEET (2134 MM). 1402.2 WEATHER PROTECTION
620 N Santiago St, Santa Ana, CA 92701
A WEATHER-RESISTANT EXTERIOR WALL ENVELOPE SHALL NOT BE REQUIRED OVER CONCRETE OR MASONRY WALLS DESIGNED IN ACCORDANCE WITH CHAPTERS 19 AND 21, RESPECTIVELY. COMPLIANCE WITH THE REQUIREMENTS FOR A MEANS OF DRAINAGE, AND THE REQUIREMENTS OF SECTIONS 1403.2 AND 1404.4, SHALL NOT BE REQUIRED FOR AN EXTERIOR WALL ENVELOPE THAT HAS BEEN DEMONSTRATED THROUGH TESTING TO RESIST WIND-DRIVEN RAIN, INCLUDING JOINTS, PENETRATIONS AND INTERSECTIONS WITH DISSIMILAR MATERIALS, IN ACCORDANCE WITH ASTM E331 UNDER THE FOLLOWING CONDITIONS: THE EXTERIOR WALL ENVELOPE DESIGN SHALL BE CONSIDERED TO RESIST WIND-DRIVEN RAIN WHERE THE RESULTS OF TESTING INDICATE THAT WATER DID NOT PENETRATE CONTROL JOINTS IN THE EXTERIOR WALL ENVELOPE, JOINTS AT THE PERIMETER OF OPENINGS OR INTERSECTIONS OF TERMINATIONS WITH DISSIMILAR MATERIALS. EXTERIOR WALL ENVELOPE TEST ASSEMBLIES SHALL INCLUDE NOT FEWER THAN ONE OPENING, ONE CONTROL JOINT, ONE WALL/EAVE INTERFACE AND ONE WALL SILL. TESTED OPENINGS AND PENETRATIONS SHALL BE REPRESENTATIVE OF THE INTENDED END-USE CONFIGURATION. EXTERIOR WALL ENVELOPE TEST ASSEMBLIES SHALL BE NOT LESS THAN 4 FEET BY 8 FEET (1219 MM BY 2438 MM) IN SIZE. EXTERIOR WALL ENVELOPE ASSEMBLIES SHALL BE TESTED AT A MINIMUM DIFFERENTIAL PRESSURE OF 6.24 POUNDS PER SQUARE FOOT (0.297 KN/M2). EXTERIOR WALL ENVELOPE ASSEMBLIES SHALL BE SUBJECTED TO A MINIMUM TEST EXPOSURE DURATION OF 2 HOURS.
CODE ANALYSIS
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-001 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
C
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
D
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
SITE PLAN
A
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-100 A1
Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
C
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
D
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
SITE SECTION
A A1
SHARED ELEVATION 1/16" = 1'0"
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-101 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027 UP Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
C GYM
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
D
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
EGRESS AND OCCUPANCY PLANS
KEY EGRESS CORE
CIRCULATION
A
PROJECT NUMBER
12 MAY 2023
DATE
0'1'
A2
EGRESS PLAN 1/16" = 1'-0"
M4
ISSUED BY
A.S.
CHECKED BY
A.S.
A-105
5'
Scale
AS INDICATED
1
2
3
4
5
P D1
A 14'
A-200
C - 0"
14'
B 14' -
- 0"
O
D 14'
0"
- 0"
'-
E - 0"
F
'-
14' -
0"
M
15' - 0"
G '-
14
L
07
15'
- 0"
'-
RETAIL
LIVE-WORK
101
103
2520 SF
350 SF
14
N 14'
06
E
'-
14
14
K 4'
LIVE-WORK
J
104
08
1
14
0"
0"
0"
0"
0"
CIVIC INDOOR
0"
111
UP
350 SF
2380 SF
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
LIVE-WORK 115 13
15'
- 0"
I
'
350 SF
" -6
LIVE-WORK
UP
09
14
H - 0"
114
"
0 '-
349 SF
15'
RETAIL LIVE-WORK
102 1051 SF
112
10
105
LIVE-WORK
10'
- 0"
1185 SF
REVISIONS
113 352 SF
CIVIC OUTDOOR
No. 01 02
UP
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
- 0"
0"
01
A1
'10
D
351 SF
RETAIL
11
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
15'
A-300
'-
15
02
0"
12
RETAIL 1135 SF
"
15'
-0
- 0"
106
' 15
03 Q
04 S
05 0"
14
T 14'
- 0"
U
15'
- 0"
14'
RETAIL
V 14' -
116
15
0"
W
2863 SF
14' -
0"
X 0"
Y
- 0"
14' -
D1
14'
20'
C
- 0"
A-200
16
- 0"
D1
Z
A-200 14' -
ELECTRIC
0"
AA
128 - 0"
14' -
RETAIL
324 SF
10'
117 805 SF
17
- 0"
AC 14'
- 0" 15'
AB 14'
ADA TRASH
- 0"
AD
RETAIL
127
18
0"
340 SF
118
ADA
802 SF
15'
- 0"
UP
19
BIKE PARKING 130 10' - 0"
Not Enclosed
ADA
20
620 N Santiago St, Santa Ana, CA 92701
14' -
MIXED-USE MULTI-FAMILY COMPLEX
0"
15'
- 0"
14' -
0"
R
'-
- 0"
SANTA ANA HOUSING
14'
10
13
RETAIL
21
ADA
9' -
B
6"
119 628 SF
UP
- 0"
UP
15'
LOADING DOCK 120
22
413 SF
15' -
0"
620 N Santiago St, Santa Ana, CA 92701
23
0"
UP
15' -
RETAIL
24
LIVE-WORK
126
125
2734 SF
350 SF
GROUND FLOOR PLAN
LIVE-WORK 124
0"
350 SF
15' -
LIVE-WORK 123
MECHANICAL
350 SF
25
LIVE-WORK 122
A
LOBBY
121
130
394 SF
1094 SF
350 SF
15'
- 0"
PROJECT NUMBER
12 MAY 2023
DATE
26
A
A-300
GROUND FLOOR 1 1/16" = 1'-0"
ISSUED BY
A.S.
CHECKED BY
A.S.
A-110
D1 A-200
0'1'
M4
5'
Scale
AS INDICATED
1
2
3
4
5
P
C1 A-200
A
06
14' 10'
07
'
C 14'
B 14'
D '
14'
14
N
E 14'
'
F
M
14'
15'
E
14
O
G
14
'
08
14
L 14
15'
K
'
'
14
09
J 10'
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
10
'
14
I '
H
UP
20'
14
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
11
15'
REVISIONS '
A1 A-300
No. 01 02
10
D
01
12
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
15'
'
15
02
Issued by J.P. J.P.
13
R
05 S 14'
15
T 14'
U 14'
V
20'
14'
W 14'
16
14'
Y
C1 A-200
10'
C
X C1 14'
17
A-200
Z 14'
AA
15'
14'
14'
GYM
18
AB AC AD
15'
14'
10'
19
10'
20
21
22
15'
B
620 N Santiago St, Santa Ana, CA 92701
15'
14'
MIXED-USE MULTI-FAMILY COMPLEX
14
'
04 14'
10
Q
SANTA ANA HOUSING
15'
' 15
03
23
15'
620 N Santiago St, Santa Ana, CA 92701
15'
24
PODIUM FLOOR PLAN
15'
25
26
A
PROJECT NUMBER
12 MAY 2023
DATE
0'1'
C1
2ND FLOOR 1/16" = 1'-0"
A-300
A2
A1 A-200
M4
ISSUED BY
A.S.
CHECKED BY
A.S.
A-111
5'
Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
O
C
14'
D
14'
N
E
14'
' 14
M
F
14'
G
15'
L
K
09
' 14
' 14
10'
14'
D
'
14'
O
E
14'
14'
07
14
K
14
A1
14'
A-200
B
14'
' 14
C
14'
O
'
14'
N
E
14'
14
REVISIONS
'
F
M
14'
14
No. 01 02
'
G L
14
'
09
K
14
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
'
14
'
'
14
'
D
08
' 14
P
'
14
J
'
J
14
I
14
I
'
' 14
H
14
' 10 15 ' 15
02
'
15
02
'
A-300
' 10
04
01
A1
' 15
A-300
' 15
03
01
A1
' 15
02
A1 A-300
M
UP
H
01
G
L
' 14
H
14
'
N
F
09
J
' 14
I
P
08
' 14
10
C
07
'
14
A
A-200
14'
15'
'
14
A1
B
15'
14'
14'
15'
10'
B
08
D
P
A-200
15'
07
A1
14'
15'
A A
06
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
03
03
14'
Q 11
T
14'
12 U
14'
10'
14
15
V
14'
14'
R
14'
S
14'
W
14'
T
14'
Y
14'
Z
14'
U
14'
UP 14'
AA
14'
AB
14'
AC
14'
C1 A-200
Q 17
18
13 X
C1 A-200
V
14'
14'
C1 A-200
R
14'
S
14'
T
14'
U
14'
W
14'
19 X
14'
Y
14'
Z
14'
AA
14'
AB
AD
14'
AC
14'
V
14'
W
14'
X
14'
Y
14'
Z
14'
AA
14'
AB
AD
UP
14'
AC
14'
AD
UP
620 N Santiago St, Santa Ana, CA 92701
S
C1 A-200
15'
14'
C1 A-200
15'
R
15'
GYM
14'
15'
13
15'
C
Q
12
15'
C1 A-200
10'
11
MIXED-USE MULTI-FAMILY COMPLEX
SANTA ANA HOUSING
05
B A1
A1
4TH FLOOR 1/32" = 1'-0"
5'
A1 C1
B2
0'1'
A-200
B4 3
A-300
C1
3RD FLOOR 1/32" = 1'-0"
5'
A-300
C1
A-300
B1
0'1'
A-200
0'1'
5'
A-200
5TH FLOOR 1/32" = 1'-0"
620 N Santiago St, Santa Ana, CA 92701
UPPER FLOOR PLANS
A
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-112 Scale
AS INDICATED
1
2
3 A-200
10'
14'
07
P
B
'
14'
14
O C 14'
'
D
14
N 14'
15'
E
5
A1
A
06
4
E
'
14'
08
14
M
F 14'
G
14
'
15'
L
'
14
K
09 '
10'
14
UP
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
J
10 '
14
I
'
14
H
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
A1
'
02
A-300
No. 01 02
' 15
D
REVISIONS
10
01
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
' 15
03
Issued by J.P. J.P.
'
10
04
C1 A-200
Q
10'
C
12
C1 14'
A-200 R
15'
14'
GYM
13
S 14'
T 14'
U
V
15'
14'
14'
14
W
10'
14'
X 14'
15
Y 14'
Z 14'
AA 14'
AB 14'
B
620 N Santiago St, Santa Ana, CA 92701
11
MIXED-USE MULTI-FAMILY COMPLEX
SANTA ANA HOUSING
05
AC 14'
AD
620 N Santiago St, Santa Ana, CA 92701
3RD FLOOR PLAN A
PROJECT NUMBER
12 MAY 2023
DATE
A1 C1
3RD FLOOR 1/16" = 1'-0"
A-300
1
A-200
0'1'
M4
ISSUED BY
A.S.
CHECKED BY
A.S.
A-113
5'
Scale
AS INDICATED
1
2
3
4
5
A 14'
A1 A-200
B 14'
P C 14'
07
'
D
O E
15'
14'
E
14
'
14'
N
F
08
14'
14
'
G
14
M
'
15'
14
L 09
'
14
K
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
4'
1
J '
14
I
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
'
14
H
REVISIONS
A1
01
A-300
' 15
D
No. 01 02
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
' 15
02
Issued by J.P. J.P.
11
C1 14'
A-200 R
15'
14'
S 14'
T
12 14'
U
V
15'
14'
14'
13
W 14'
X 14'
UP
Y 14'
Z 14'
AA 14'
AB 14'
B
620 N Santiago St, Santa Ana, CA 92701
Q
C1 A-200
MIXED-USE MULTI-FAMILY COMPLEX
C
SANTA ANA HOUSING
03
AC 14'
AD
UP
620 N Santiago St, Santa Ana, CA 92701
4TH FLOOR PLAN A
PROJECT NUMBER
12 MAY 2023
DATE
A1 C1
4TH FLOOR 1/16" = 1'-0"
A-300
A2
A-200
0'1'
M4
ISSUED BY
A.S.
CHECKED BY
A.S.
A-114
5'
Scale
AS INDICATED
1
2
3 A-200 14'
P
B 14'
'
14
O
C 14'
D
'
14'
15'
E
5
A1
A
07
4
14
N E 14'
08
'
F
M 14'
G
14
'
14
15'
L
'
09
14
K
'
14
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
J '
14
I
'
14
H
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
A1
01
' 15
D
No. 01 02
A-300
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
' 15
02
Issued by J.P. J.P.
17
C1 14'
A-200 R
15'
14'
S 14'
T
18 14'
U
V
15'
14'
14'
19
W 14'
X 14'
Y 14'
Z 14'
AA 14'
AB 14'
B
620 N Santiago St, Santa Ana, CA 92701
Q
C1 A-200
MIXED-USE MULTI-FAMILY COMPLEX
C
SANTA ANA HOUSING
03
AC 14'
AD
UP
620 N Santiago St, Santa Ana, CA 92701
5TH FLOOR PLAN A
PROJECT NUMBER
12 MAY 2023
DATE
A1 C1
A-300
5TH FLOOR A2 1/16" = 1'-0"
A-200
0'1'
M4
ISSUED BY
A.S.
CHECKED BY
A.S.
A-115
5'
Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027 T.O. ROOF 70' - 0" Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
ROOF 58' - 0"
REVISIONS 5TH FLOOR 48' - 0"
D
No. 01 02
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
4TH FLOOR 38' - 0"
3RD FLOOR 28' - 0"
2ND FLOOR
0' - 0"
C1
C
SOUTH ELEVATION 3/32" = 1' 0"
T.O. ROOF 70' - 0"
ROOF 58' - 0"
B
620 N Santiago St, Santa Ana, CA 92701
GROUND FLOOR
MIXED-USE MULTI-FAMILY COMPLEX
SANTA ANA HOUSING
18' - 0"
5TH FLOOR 48' - 0"
4TH FLOOR 38' - 0" 620 N Santiago St, Santa Ana, CA 92701 3RD FLOOR 28' - 0"
2ND FLOOR 18' - 0"
BUILDING ELEVATIONS GROUND FLOOR 0' - 0"
A
A1
EAST ELEVATION 3/32" = 1' 0"
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-200 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
T.O. ROOF 70' - 0"
ROOF 58' - 0"
D
5TH FLOOR 48' - 0"
REVISIONS No. 01 02
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
4TH FLOOR 38' - 0"
3RD FLOOR 28' - 0"
2ND FLOOR
0' - 0"
C
C1
NORTH ELEVATION 3/32" = 1' 0"
T.O. ROOF 70' - 0"
ROOF 58' - 0"
B
620 N Santiago St, Santa Ana, CA 92701
GROUND FLOOR
MIXED-USE MULTI-FAMILY COMPLEX
SANTA ANA HOUSING
18' - 0"
5TH FLOOR 48' - 0"
4TH FLOOR 38' - 0" 620 N Santiago St, Santa Ana, CA 92701 3RD FLOOR 28' - 0"
2ND FLOOR 18' - 0"
BUILDING ELEVATIONS
GROUND FLOOR 0' - 0"
A
A1
WEST ELEVATION
PROJECT NUMBER
3/32" = 1' 0"
DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-201 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
VIEW FROM N SANTIAGO STREET
C3
VIEW FROM COURTYARD
C
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
C1
Description MIDTERM FINAL
MIXED-USE MULTI-FAMILY COMPLEX
D
Issued by J.P. J.P.
SANTA ANA HOUSING
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
EXTERIOR BUILDING VISUALIZATIONS A
A1
VIEW FROM PEDESTRIAN WALKWAY
A3
VIEW FROM COURTYARD PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-210 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
T.O. ROOF 70' - 0"
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
ROOF 58' - 0"
5TH FLOOR
REVISIONS
48' - 0"
D
4TH FLOOR
No. 01 02
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
38' - 0"
3RD FLOOR 28' - 0"
2ND FLOOR
0' - 0"
C1
C
ELEVATION A 3/32" = 1' 0"
T.O. ROOF 70' - 0"
ROOF 58' - 0"
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
GROUND FLOOR
MIXED-USE MULTI-FAMILY COMPLEX
18' - 0"
5TH FLOOR 48' - 0"
B 4TH FLOOR 38' - 0"
3RD FLOOR 28' - 0"
620 N Santiago St, Santa Ana, CA 92701
2ND FLOOR 18' - 0"
BUILDING SECTIONS
GROUND FLOOR 0' - 0"
A
A1
ELEVATION B 3/32" = 1' 0"
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-300 Scale
AS INDICATED
1
2
3
4
5
T.O. ROOF 56' - 0"
E 2 A-503
RA-01
ROOF
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
48' - 0"
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
1
No. 01 02
A-503
D
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
A-502 3RD FLOOR FA-01
C
28' - 0"
2ND FLOOR 18' - 0"
620 N Santiago St, Santa Ana, CA 92701
3
MIXED-USE MULTI-FAMILY COMPLEX
38' - 0"
SANTA ANA HOUSING
FA-01
4TH FLOOR
B 1 A-502
620 N Santiago St, Santa Ana, CA 92701
WALL SECTION
A
PROJECT NUMBER
12 MAY 2023
DATE GROUND FLOOR 0' - 0"
A1
ELEVATION OF BUILDING CHUNK 3/8" = 1'0"
A3
WALL SECTION OF STACK 3/8" = 1'-0"
M4
ISSUED BY
A.S.
CHECKED BY
A.S.
A-310 Scale
AS INDICATED
1
B 14' - 0"
1
B
C
28' - 8" 14' - 0"
14' - 0"
LIVING ROOM
BEDROOM
102
101
130 SF
130 SF
2
BEDROOM
LIVING ROOM
101
103
102
191 SF
193 SF
191 SF
3
10' - 0"
1
1 1
1 15' - 0"
1
BATHROOM
103
104
219 SF
98 SF 0'
% CIRCULATION PER UNIT: 22.1%
1'
1
TWO BEDROOM AREA: 1059 SF
5'
1
B
C
1
28' - 8" 14' - 0"
KITCHEN
105
104
BATHROOM 106
78 SF
291 SF
99 SF 0'
1'
5'
B
14' - 0"
A
1
2
2
B
14' - 0"
14' - 0"
2
32' - 0"
LIVING/WORK
4
KITCHEN 102
201
260 SF
141 SF
15' - 0"
83 SF
BEDROOM
101
620 N Santiago St, Santa Ana, CA 92701 1 1
2 STUIO AREA: 395 SF
BED-LIVING
CLOSET
101
104
103
192 SF
36 SF
62 SF
1
POWDER ROOM
KITCHEN
103
102
202
49 SF
90 SF
81 SF
BATHROOM
BATHROOM
0'
2 1'
5'
2 LIVE - WORK AREA: 832 SF
% CIRCULATION PER UNIT: 22.1%
0'
1'
UNIT PLANS
5'
% CIRCULATION PER UNIT: 22.3%
4
STUDIO 1/8" = 1'-0"
Date 3/24/2022 5/12/2022
2 BEDROOM 1/8" = 1'-0"
A
1
BATHROOM
% CIRCULATION PER UNIT: 14.1%
2
Description MIDTERM FINAL
1
3
1 BEDROOM 1/8" = 1'-0"
Issued by J.P. J.P.
620 N Santiago St, Santa Ana, CA 92701
KITCHEN
No. 01 02
MIXED-USE MULTI-FAMILY COMPLEX
3
REVISIONS
32' - 0"
15' - 0"
3
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
1
19' - 4"
BEDROOM
SANTA ANA HOUSING
1
34' - 10"
10' - 0"
2
1
14' - 0"
1
4
ONE BEDROOM AREA: 666 SF
D
14' - 0"
3
1
C
42' - 8"
3
LIVE -WORK 1/8" = 1'-0"
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-400 Scale
AS INDICATED
1
2
3
4
5
E
9' - 8"
7' - 6"
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
2' - 2" 2' - 0"
2' - 0"
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
D
B.0. SOFFIT 7' - 6"
B.0. SOFFIT 7' - 6"
F.F. 0' - 0"
F.F. 0' - 0"
No. 01 02
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
C
C1
ENLARGED ADA BATHROOM PLAN 1/2" = 1'-0"
C3
Elevation A 1/2" = 1'-0"
B
C4
SANTA ANA HOUSING
2' - 7"
C
Elevation B 1/2" = 1'-0"
B.0. SOFFIT 7' - 6"
620 N Santiago St, Santa Ana, CA 92701
B
MIXED-USE MULTI-FAMILY COMPLEX
C-5 A-405
10' - 11"
D
3' - 11"
A
5' - 0"
ø 5' - 0"
B.0. SOFFIT 7' - 6"
LT-03
620 N Santiago St, Santa Ana, CA 92701
ADA BATHROOM DETAIL
LT-01
F.F. 0' - 0"
A
A1
ENLARGED ADA BATHROOM RCP 1/2" = 1'-0"
A3
Elevation C 1/2" = 1'-0"
F.F. 0' - 0"
A4
Elevation D 1/2" = 1'-0"
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-405 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
C
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
D
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
INTERIOR VISUALIZATION A
PROJECT NUMBER
A1
INTERIOR VISUALIZATION
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-410 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
C
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
D
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
EXTERIOR BUILDING VISUALIZATION A
PROJECT NUMBER
A1
EXTERIOR BUILDING VISUALIZATION
DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-411 Scale
AS INDICATED
2
E
3
4
5
1' - 0"
1
63
62
61
60
59
58
T.O. LEVEL 3
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
8' - 11"
28' - 0"
B4 A-420
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027 1 INCH NOSING REVISIONS CONCRETE TREAD
D
1' - 0" 1' - 0"
2 INCH NON-SLIP STRIP 45
No. 01 02
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
BENT METAL SHEET
44
3' - 3"
43
42
STRINGER
41
40
T.O. PODIUM
C
6' - 9"
1' - 0"
5' - 6"
3' - 0"
56
55
54
B4
3' - 8"
53
52
STAIR DETAIL 3" = 1'0"
51
DN
50
48
4' - 7"
4' - 11"
49
620 N Santiago St, Santa Ana, CA 92701
STAIR SECTION 1/2" = 1'0"
MIXED-USE MULTI-FAMILY COMPLEX
B2
SANTA ANA HOUSING
18' - 0"
47
B
3' - 4"
46
620 N Santiago St, Santa Ana, CA 92701
UP
B1 A-420
40
41
42
43
44
45
ENLARGED STAIR PLAN AND SECTION
30" BY 40" AREA OF REFUGE
A1
A
STAIR PLAN 1/2" = 1'-0"
PROJECT NUMBER
M4 12 MAY 2023
DATE ISSUED BY
A.S.
CHECKED BY
A.S.
A-420 Scale
AS INDICATED
1
E
2
3
WA-01
WA-02
R-0 MIN. R- 24.7 STC: 36
R-0 MIN. R- 18.7 STC: 57
4
5
WA-03 R-0 MIN. R- 23.8 STC: NONE
CEMENT PANELS Z FURRING CHANNEL
FURRING STRIPS
SECTION
SECTION
PLYWOOD SHEATING 2 X 6 STUD
AIR SPACE
GYPSUM WALLBOARD AIR GAP 2 X 4 STUD
MINERAL WOOL INSULATION
WEATHER RESISTANT BARRIER
GYPSUM WALLBOARD
GYPSUM WALLBOARD
PLYWOOD SHEATHING
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
MINERAL WOOL INSULATION
PLYWOOD SHEATING
RIGID INSULATION
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
GYPSUM WALLBOARD
2 X 6 STUD
REVISIONS
RA-01
PVC MEMBRANE
INT WOOD FLOORING PLYWOOD SHEATHING
R-0 MIN. R- 50.3 STC: N/A
C1 1
WOOD DECKING SLEEPER SLEEPER SLEEPER RIGID INSULATION PLYWOOD SHEATHING MINERAL WOOL INSULATION 2 X 12 STUD GYPSUM WALLBOARD
2 X 12 STUD
GYPSUM WALLBOARD SECTION
SLOPE 1/4 : 12
MINERAL WOOL INSULATION
FLOOR STUD
INT
EXT
RIGID INSULATION PLYWOOD SHEATHING
INT.
GYPSUM WALLBOARD
INT
Date 3/24/2022 5/12/2022
INT
GYPSUM ROOFING MATERIAL
MINERAL WOOL INSULATION
C
16' O.C. TYP.
PLAN
EXT.
INT
Description MIDTERM FINAL
SECTION
SECTION
ASSEMBLIES 1 1/2" = 1'-0"
620 N Santiago St, Santa Ana, CA 92701
16" O.C. TYP
INT
Issued by J.P. J.P.
SANTA ANA HOUSING
R-0 MIN. R- 38.3 IRC: 53
INT
INT
FA-01
16" O.C. TYP
GYPSUM WALLBOARD
No. 01 02
RA-02
EXT
PLYWOOD SHEATHING PLAN
PLAN
D
16" O.C. TYP.
MINERAL WOOL INSULATION
MIXED-USE MULTI-FAMILY COMPLEX
SECTION
ANCHOR
GYPSUM WALLBOARD
B
620 N Santiago St, Santa Ana, CA 92701
ASSEMBLIES
A
PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-501 Scale
AS INDICATED
1
2
3
4
5
E GALV. SHT. CAP FLEXIBLE FLASHING TOP PLATE WEATHER RESISTANT MEMBRANE SEAL TAPE
WA-01
PLYWOOD SHEATHING WEATHER RESISTANT MEMBRANE CEMENT PANELS VERTICAL FURRING STRIPS WATERPROOFING TERMINATIONS WOOD PLANK DECKING SLEEPERS PVC MEMBRANE SLOPE 1/4 : 12 RIGID INSULATION
ANCHOR BOLT BASEBOARD MOLDING ENGINEERED FLOORING PLYWOOD SHEATHING
WEATHERING RIGID VINYL SPACER TRI-FIN PILE HEAD TRACK PAN FLASHING
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
ALUMINUM SLIDING DOOR ALUMINUM THRESHOLD WOOD NAILER
REVISIONS No. 01 02
D
Date 3/24/2022 5/12/2022
WALL TO PODIUM 1 1/2" = 1'-0"
C3
BALCONY FLOOR 1 1/2" = 1'-0"
C4
WALL TO ROOF 1 1/2" = 1'-0"
C
TUBE STEEL
620 N Santiago St, Santa Ana, CA 92701
WA-01
SANTA ANA HOUSING
C1
Description MIDTERM FINAL
SLOPE 1/4 : 12
FA-01
SUPPORTS FLASHING ALUMINUM PLATE ALUMINUM HEADER SEALANT FASTENER GLAZING
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
ANCHOR Z CLIPS FLASHING SEALANT
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
WIRE MESH TENSION CABLE
B
ANGLED SLEEPERS
SHELF SPACE EXT
RIM JOISTS
SLOPE EXT 1/4 : 12
4" MIN
STRAINER HIGH
FA-01
DA-01
RA-01
SLOPE 1/4 - 12
INT
LOW
GLASS SKYLIGHT STEEL FRAME
620 N Santiago St, Santa Ana, CA 92701
METAL GUTTER CUSTOM STEEL CHANNEL
INT
INT
SKYLIGHT DETAIL A1 1 1/2" = 1'-0"
A
GUARDRAIL DETAIL A3 1 1/2" = 1'-0"
DETAILS
SKYLIGHT DRAINAGE DETAIL A4 1 1/2" = 1'-0"
PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-502 Scale
AS INDICATED
1
2
3
4
E
5
STEEL PIPE GUARDRAIL TENSION CABLE TIES
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
WIRE MESH
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
GLASS SKYLIGHT REVISIONS
STEEL FRAME
D
No. 01 02
WELDED CONNECTION
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
METAL GUTTER CUSTOM STEEL CHANNEL
SKYLIGHT DRAINAGE DETAIL
WEATHER RESISTANT BARRIER
NTS
C
CEMENT PANELS SLEEPERS AIR GAP RIGID INSULATION PLYWOOD SHEATHING
WOOD PLANKS PLYWOOD SHEATHING SLEEPER PLYWOOD SHEATHING FLOOR JOIST FIBER WOOL INSULATION
WEATHER RESISTANT BARRIER WEATHER RESISTANT BARRIER B3
B
GUARDRAIL DETAIL NTS
620 N Santiago St, Santa Ana, CA 92701
C1
SANTA ANA HOUSING
ANGLED FURRING STRIPS
MIXED-USE MULTI-FAMILY COMPLEX
FIBER CEMENT PANEL
GYPSUM DRYWALL PLYWOOD SHEATHING FIBER WOOL INSULATION ENGINEERED WOOD FLOORING
620 N Santiago St, Santa Ana, CA 92701
DOUBLE RIM JOIST
WOOD PLANKS SLEEPERS PVC MEMBRANE
3D - DETAILS
A
A1
STUDIO SKYLIGHT DETAIL NTS
PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-503 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
REVISIONS
C
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
SANTA ANA HOUSING
D
Issued by J.P. J.P.
MIXED-USE MULTI-FAMILY COMPLEX
No. 01 02
B
620 N Santiago St, Santa Ana, CA 92701
MODEL PHOTOS
A
PROJECT NUMBER DATE
A1
MODEL PHOTOS
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-505 Scale
AS INDICATED
1
2
3
13' - 4"
4
5
9' - 4"
FIXED
FIXED
FIXED
FIXED
7' - 6"
7' - 6"
E
FIXED
FIXED
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
FIXED
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
2
1
REVISIONS
HEIGHT
WINDOW TYPE
MATERIAL
1
13'-4"
7'-6"
HINGED
ALUMINUM
2
9'-4"
7'-6"
HINGED
ALUMINUM
MANUFACTURER
NOTES
WINDOW SCHEDULE 1/2" = 1'-0"
C
13' - 4"
FIXED
B
TYP. 1
A
7' - 6"
3' - 6"
3' - 6"
7' - 0"
7' - 6"
3' - 0"
7' - 0"
2' - 8"
9' - 4"
TYP. 2
FIXED
TYP. 3
TYPE
WIDTH
HEIGHT
1
2'-8"
7'-0"
DOOR TYPE HINGED
MATERIAL
FIXED
FIXED
TYP. 4
MANUFACTURER
620 N Santiago St, Santa Ana, CA 92701
NOTES
WOOD
2
3'-0"
7'-0"
HINGED
ALUMINUM
3
13'-4"
7'-6"
SLIDING
ALUMINUM
DOOR AND WINDOW SCHEDULE
PROJECT NUMBER DATE
4 A1
DOOR SCHEDULE 1/2" = 1'-0"
9'-4"
7'-6"
SLIDING
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
WIDTH
Description MIDTERM FINAL
MIXED-USE MULTI-FAMILY COMPLEX
C1 1
TYPE
Issued by J.P. J.P.
SANTA ANA HOUSING
D
No. 01 02
ALUMINUM
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
A-600 Scale
AS INDICATED
1
2
3
4
5
E
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
58 A
11 B
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
12 C
28' - 8"
REVISIONS
14' - 0"
14' - 0"
No. 01 02
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
LT - 03
D
Issued by J.P. J.P.
13 1
+ CLG. HT. 7'- 6"
15' - 0"
LT - 02
+ CLG. HT. 7'- 6"
LT - 04
LT - 04
LT - 04
LT - 02
LT - 03
+ CLG. HT. 7'- 6"
15 3
GFCI
LT - 02
LT - 02
LT - 02
GFCI
LT - 01
LT - 03
620 N Santiago St, Santa Ana, CA 92701
LT - 04
+ CLG. HT. 8'- 6"
MIXED-USE MULTI-FAMILY COMPLEX
SANTA ANA HOUSING
LT - 04 + CLG. HT. 7'- 6" LT - 03
14 2
+ CLG. HT. 8'- 6"
D
LT - 04
C
D
LT - 03
10' - 0"
LT - 04
LT - 03
KEY
B
RECESSED DOWNLIGHT
HATCH INDICATES SOFFIT
UNDER CABINET MOUNTED LINEAR LIGHTING
LINE INDICATES WIRED CONNECTION
LT - 01
LT - 02 LT - 03
LT - 04
ELECTRICAL REFLECTED CEILING PLAN 1 BED B2 1/4" = 1'-0"
D
WALL MOUNTED LINEAR LIGHT - LARGE
PENDANT LIGHT
WALL MOUTED SINGLE SWITCH
GFCI
WALL MOUNTED GFCI DUPLEX
WALL MOUNTED DATA
WALL MOUNTED DUPLEX
620 N Santiago St, Santa Ana, CA 92701
LT - 07
POWER, ELECTRICAL, AND LIGHTING PLANS A
PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
E-102 Scale
AS INDICATED
1
2
3
4
5
E
CONDENSER
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
ELECTRICAL PANEL METER
A
CITY GRID SUPPLY OUTFLOW RETURN INTAKE
B
SUPPLY OUTFLOW
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
C
28' - 8" 14' - 0"
14' - 0" REVISIONS No. 01 02
D
SUPPLY OUTFLOW RETURN INTAKE
Issued by J.P. J.P.
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
SUPPLY OUTFLOW
+ CLG. HT. 8'-6"
+ CLG. HT. 8'-6"
+ CLG. HT. 7'-6"
15' - 0"
+ CLG. HT. 7'-6"
+ CEILING HT 7'-6"
3
620 N Santiago St, Santa Ana, CA 92701
SUPPLY OUTFLOW
2
C
SANTA ANA HOUSING
RETURN INTAKE
30' - 11"
SUPPLY OUTFLOW
CEILING HT 7'-6"
MIXED-USE MULTI-FAMILY COMPLEX
10' - 0"
1
B HVAC SECTION DIAGRAM B1 1/4" = 1'-0"
MECHANICAL REFLECTED CEILING PLAN 1 BED B3 1/4" = 1'-0" 620 N Santiago St, Santa Ana, CA 92701
KEY SUPPLY RETURN
HVAC DISTRIBUTION PLAN
12" X 12" DUCT
EXHAUST HATCH INDICATES SOFFIT
A
PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
M-101 Scale
AS INDICATED
1
2
3
4
5
E
BOILER HOT LINE
3801 W Temple Ave Pomona, CA 91768 jpajer@cpp.edu (916) 693-9027
COLD LINE
CIRCUL ATION PUMP
Consultant: Anton Schneider 3801 W Temple Ave, Pomona, CA 91768 abschneider@cpp.edu (916) 693-9027
58 A
11 B
12 C
28' - 8" 14' - 0"
D
REVISIONS 14' - 0" 7' - 6"
SINK
Description MIDTERM FINAL
Date 3/24/2022 5/12/2022
620 N Santiago St, Santa Ana, CA 92701
15' - 0"
14 2
30' - 7"
C
MIXED-USE MULTI-FAMILY COMPLEX
13 1
WATER CLOSET
SANTA ANA HOUSING
WASHER/ DRYER STACKED
Issued by J.P. J.P.
10' - 0"
SINK
2' - 9"
No. 01 02
15 3 B FRESH WATER MAIN
SEWER MAIN
PLUMBING DIAGRAM B1 1/4" = 1'-0"
WATER METER PER UNIT
620 N Santiago St, Santa Ana, CA 92701
PLUMBING REFLECTED CEILING PLAN 1 BED B3 1/4" = 1'-0"
KEY
PLUMBING DISTRIBUTION PLAN
EXHAUST VENT COLD WATER LINE HOT WATER LINE
A
WASTE WATER HATCH INDICATES PLUMBING WALL
PROJECT NUMBER DATE
M4 12 MAY 2023
ISSUED BY
A.S.
CHECKED BY
A.S.
P-101 Scale
AS INDICATED