EXTERNAL FLOOR & ROOF - N3
SPECIFICATION GUIDE SPEC BEAM 13.2 GREEN LVL
SPE SP ECBEAM13.2 13.2GREEN ISSUE 1.0 3.0--OCTOBER OCTOBER2026 2020
2 Growth through premier brands and innovation Since its establishment in 1987 in Five Dock, NSW, Independent Timber Importers (ITI) has been on a mission to redefine the timber wholesale and distribution landscape. ITI has worked closely with industry suppliers, customers, and associations to promote the strength, beauty, and environmental benefits of timber construction. At the same time, ITI redefined the role of the wholesaler through its distribution and service models. With significant investment in distribution centres, product development, people, and service standards, ITI transitioned from the name Independent Timber Importers in early 2002, adopting the ITI brand and introducing the “Innovative Timber Ideas” logo to more accurately reflect the company’s philosophy. Today, ITI operates nine distribution sites across Australia with over 140,000 m2 of undercover storage, a state-of-the-art re-manufacturing, treating, and priming facility in Chile, an office in Indonesia, four distribution locations in New Zealand, and a growing presence in the United States. True to its name, ITI’s success lies in its commitment to innovation in both service and product development. This commitment has led to the creation of premier brands such as Design Pine, EziTrim Plus, and Spec Frame, along with the distribution of market-leading products including James Hardie, Weathertex, and ModWood. ITI has also been recognised with numerous industry awards for service excellence.
ITI Engineered Wood Products ITI sources engineered wood products from leading manufacturers to ensure the needs of building designers through to end users are met with high-quality, reliable solutions.
ABOUT ITI
The ITI Engineered Wood Products range comprises three primary systems, each designed to complement the next: Laminated Veneer Lumber (LVL), I-Joists, and glue-laminated timber beams (GLT). These products, together with innovative construction details and dedicated technical support staff, form an integrated platform that sets ITI Engineered Wood Products apart.
3
SPE SP ECBEAM13.2 13.2GREEN H3 TREATED Spec Beam® 13.2 Green H3 is an economical LVL E13.2 solution, available in all commonly specified sizes used by engineering professionals. The range provides suitable options for beams, rafters, and joists which are exposed to the weather (Harzard Class 3).
Individual Veneer Treatment Each sheet of 2.2mm veneer used in ITI Spec Beam Green is flooded with an an anti-decay agent, mouldicide and termiticide prior to being used in the production of LVL. Following the treatment of each veneer, they are conditioned prior to being laid up, glued, and pressed to the required section thickness. This modern process ensures the protection is delivered throughout the entire cross section of the finished beams. Traditional methods of treating LVL require a pressure cylinder to force the treatment chemicals through the full end section of the LVL beams, including the marine-grade glue lines. This process can lead to the product becoming unstable and can result in the preservative not penetrating through to the core of the LVL.
Prepared for Construction Spec Beam® 13.2 Green H3 is supplied with a light sealant coating for temporary protection against the elements during construction and features pencil-round corners for splinter-free handling and ease of installation. Spec Beam® LVL is subject to more than 70 quality control checks from log receipt through to export of the finished product. Structural performance is verified through destructive bending tests every two production hours and bond strength testing every four production hours. All Spec Beam® manufacturing facilities are audited twice annually to verify the effectiveness of quality assurance systems and production controls. Properties (MPa)
E 13,200
G 660
f’b 40.01
f’c 33.0
f’t
f’s
f’sj
30.02
4.0 3.54
f’p
5.2 4.64
3
9.8 6.44
3
3
(1)
Value based on a 300mm deep section on edge. Use 40.0x(300/Depth)
(2)
Value based on a 150mm deep section on edge. Use 30.0x(150/Depth)0.15 for sections over 150mm deep
(3)
Value shown for use on edge as a beam
(4)
Value shown for use on face or flat
Joint Group
Nails - Face & Edge Lateral Withdrawal Min. JD4
0.15
Weight kg/m3
Strength Group
580
SD6
for sections over 300mm
Screws - Face & Edge Lateral Withdrawal Min. JD4
Bolts - Face Perpendicular Parallel Min. JD4
Ethically sourced wood fibre Suppliers responsible for the provision of logs used in the manufacture of Spec Beam® 13.2 Green LVL are required to demonstrate compliance with the Australian Government’s Illegal Logging Prohibition Amendment Act. The wood fibre used in Spec Beam® 13.2 LVL is sourced from Pinus massoniana (China) or Picea abies (Europe). FSC® certification is available upon request.
QUEENSLAND | NEW SOUTH WALES Width
(1)
Depths
45
90
1301
150
1701
200
240
300
360 4001
63
90
1301
150
1701
200
240
300
360
Queensland only
-
ABOUT ITI SPEC BEAM 13.2 GREEN LVL
Production Testing
4
INSTALLATION REQUIREMENTS
SPEC BEAM 13.2 GREEN USED IN EXPOSED APPLICATIONS MUST BE SEALED Spec Beam 13.2 Green must only be used in exposed applications where wetting is periodic and can dry efficiently. ITI Spec Beam 13.2 Green must not be used in exposed structural applications where the installed product can not be regularly inspected for signs of moisture damage. Care is to be taken to avoid situations where water can pool or become trapped between the product and its supports or joints.
Internal, Fully Protected
External, Above Ground, Unprotected
INSTALLATION REQUIREMENTS
Exposure
300
External, Above Ground, Fully Protected
External, Above Ground, Mostly Protected
Requirements
Internal, Fully Protected
Additional Treatment required for Termites & Insects only
External, Above Ground, Fully Protected
Additional Treatment required for Termites & Insects. If adequate ground clearance is not available products should be treated as if they are External, Above Ground, Mostly Protected.
External, Above Ground, Mostly Protected External, Above Ground, Unprotected
H3 Treatment required in addition to being installed per the below guidelines H3 Treatment required in addition to being installed per the below guidelines
Coating System Clear penetrating water repellent oils and sealants Semi-transparent to full colour penetrating exterior timber stains Solid colour exterior acrylic paints Solid colour exterior gloss enamel Clear or semi-transparent exterior gloss or varnish
Recommendation Apply as per manufacturer’s directions. May require frequent re-application (6–12 months). Apply 2 to 3 coats as per manufacturer’s directions. Apply a good quality, oil-based exterior wood primer followed by two coats of premium quality exterior acrylic paint according to the manufacturer’s recommendations. Not recommended. Not recommended.
Installation requirements of H3 Treated LVL Products: 1. The builder / end user is to retain photos as evidence of installation methods and maintenance. 2. All edges and faces of members are to be painted / sealed prior to installation using an acceptable coating method, such as an acrylic system, using the manufacturer’s installation requirements. 3. Always install a protective barrier to the top edge and exposed ends of all LVLs in exposed applications using either tesa JoistSeal, a malthoid-type barrier flashing or similar. 4. Coating systems are to be regularly maintained in accordance with the manufacturer’s requirements. 5. Refer to AS1684.2 Appendix B for additional information on Timber Durability. 6. ITI offers alternative products which are specifically developed for use in high moisture and exposed applications. Please discuss alternative options with your timber supplier if you feel the above requirements are not practical for your intended application. Failure to install H3 Treated SPEC BEAM® 13.2 GREEN LVL in accordance with the recommendations above will result in a retraction of liability by ITI towards the product and associated treatments
5 Tesa Joist Seal Tape, or similar, sealant tape to top edges and high risk joins Caulk / Seal joints between members
Create a free drainage point where sealing / caulking is not possible
Stagger fixings to avoid splitting of members which could create moisture traps
Seal members to prevent moisture ingress 1. 2. 3.
Seasoned timber kept dry (MC < 20%) will not decay Pre-paint / finish members prior to installation to ensure all surfaces are adequately covered Provide capping or sloping cuts to top edges
Minimise moisture traps and contact areas 4. 5. 6. 7. 8. 9.
Tape top edges Tape ends where they are not in a maintainable position Caulk / seal joints between members Create free draining joints Avoid joist hangers where possible Leave gaps between abutting members supported by joist hangers
Provide additional care to high risk zones such as connections between beams and posts
Fastener selection and installation 10. Stagger decking screws to prevent splitting or cracking
Corrosion resistant fasteners 12. Stainless steel within 200 m of a breaking surf zone or within 50m of sheltered bays 13. Stainless recommended within 1km of breaking surf zone 14. Refer to fixing manufacturers’ details for requirements relating to their own specific products 15. Members in the splash zone of an outdoor swimming pool should be treated the same being within 200m of breaking surf 16. The specifications for fixings used for indoor pool enclosures must be designed by a suitably qualified professional 11.
Tesa Tape Stock Profile Code
Description
Tape Width
Tape Length
Total Metres
JT050X020B
JoistSeal Tape 50mm x 20m (Each)
50mm
20m
20m
JT100X020B
JoistSeal Tape 100mm x 20m (Each)
100mm
20m
20m
JT050X020B54
JoistSeal Tape 50mm x 20m Box of 54.
50mm
20m
1,080m
JT100X020B27
JoistSeal Tape 100mm x 20m Box of 27.
100mm
20m
540m
Refer to Wood Solutions Guides for additional information on using timber products in exposed applications: WS TDG 05 Timber Service Life Design WS TDG 13 Finishing Timber Externally WS TDG 21 Domestic Timber Deck Design
6
LOADINGS & DEFINITIONS
Determining Roof Load Width (RLW) at Supports - Trussed Roof Overhang
Span 1 RLW at = Support 1 RLW at = Support 2
Support 1
Span 1 2
+ Overhang Span 1 2
Support 2
Determining Roof Load Width (RLW) at Supports - Pitched Roof Overhang
Span 1
Support 1
Span 2
Support 2
LOADINGS & DEFINITIONS
Span 1 RLW at = + Overhang Support 1 2 ( Span 1 + Span 2 ) RLW at = Support 2 2
Span 3
Support 3
Support 4
( Span 2 + Span 3 ) RLW at = Support 3 2 Span 3 RLW at = Support 4 2
Rafter & Beam Span Types
Single Span
Continuous Span
Span A
Span A
Single Span
Span B
Continuous Span
Span A
Span A
Span B
A continuous span only applies when the smaller of the spans is no less than half the larger span. Where this does not apply, both spans are to be treated as single spans or further design analysis is required. Measure spans between internal faces of the supports.
7
Domestic Deck / Balcony Loads Domestic Floor Loadings per AS 1170.1 Table 3.1 Specific uses Self-contained Dwellings
Uniform Distributed Actions
Concentrated Actions
Balconies (<1m off ground)
1.5 kPa
1.8 kN
Balconies (>1m off ground)
2.0 kPa
1.8 kN
Floor Framing Deflection Floor Framing Limits on Deflection per AS1720.3 Single or Continuous Spans Overhang Span / 300 or 15mm Max. Cantilever / 150 or 6mm Max.
Load Dead Load Floor Live Load
Span / 360 or 9mm Max.
Cantilever / 180
Dynamic (1kN)
2mm
-
Bearer & Joist Span Types Single Span
Continuous Span
Span A
Span A
Span B
A continuous span only applies when the smaller of the spans is no less than half the larger span. Where this does not apply; both spans are to be treated as a single span or further design analysis is required. Measure spans between internal faces of the supports.
Determining Floor Load Width (FLW) at Supports Span 1
Support 1
Cantilever
Support 2
FLW at Support 1
=
FLW at Support 2
=
FLW at Support 3
=
Birdsmouth
Span 2
Support 3
Span 1 2 Span 1 + Span 2 2 Span 2 + Cantilever 2
Rafter Support Types ‘D’
Wedge or Tapered Plate
‘D’/3 Max. Wedge or Tapered Plate
Maximum allowable birdsmouth to be no greater than 1/3 the rafter depth
Edges to be fixed down to the support without any splitting. Tie down the rafters directly to supports
8
FLOOR JOISTS
Floor / Balcony Joist
FLOOR JOISTS
Floor / Balcony Bearer
A deck joist is a horizontal structural member that spans between bearers and directly supports the decking boards, which are fixed across the joists at right angles. Spec Beam 13.2 Green H3 treated LVL is well suited to this role. Its E13.2 stiffness rating (a modulus of elasticity of 13,200 MPa) gives it predictable, consistent performance, so it can span further or bounce less than comparable sawn timber. Its laminated veneer construction makes it straight, true and dimensionally stable. That means a flatter deck surface, less crowning or twisting between joists, and fewer rejected lengths on site. The H3 treatment makes it suitable for outdoor, above-ground use where the timber is exposed to weather, and protects it against decay and termite attack. It is not rated for in-ground or ground-contact use, where H4 or H5 is needed. Connections to bearers or pole plates should use galvanised or stainless steel fixings rated for treated timber, and any cut or drilled surfaces should be resealed with a compatible preservative. Refer to AS1684 for fixing and blocking requirements.
Size
Span Type Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous
90x45 130x45 130x63 150x45 150x63 170x45 170x63 200x45 200x63 240x45 240x63 300x45 300x63 360x45 360x63 400x45
BALCONY JOISTS Hardwood Decking, No Ceiling - 25kg/m2 <1.0m off Ground (1.5 kPa) >1.0m off Ground (2.0 kPa) 300mm Centres 450mm Centres 300mm Centres 450mm Centres 2100 1700 1600 1300 2800 2000 2100 1800 3100 2600 2300 2000 3800 3100 3100 2700 3400 2900 2500 2200 4200 3500 3400 3000 3600 3000 2600 2300 4300 3700 3600 3100 3900 3500 2900 2600 4700 4200 4000 3500 4000 3500 3000 2600 4700 4300 4000 3500 4400 3900 3300 2900 5200 4700 4500 4000 4600 4200 3500 3100 5300 4800 4700 4200 4900 4600 3900 3400 5800 5300 5000 4600 5300 4800 4200 3700 6100 5500 5300 4800 5600 5200 4600 4100 6700 6000 5800 5200 6100 5700 5000 4600 7300 6600 6300 5700 6500 6000 5400 4900 7900 7100 6700 6100 7000 6500 5700 5200 8000 7500 7100 6500 7300 6900 6100 5700 8000 8000 7700 7000 7500 7000 6200 5700 8000 8000 7700 7100
Minimum Member Bearing Lengths
Support A
Support B
Support C
Required Bearing at Supports for all Member Types End Support (A)
Intermediate Support (B)
Cantilever Support (C)
30mm
60mm
60mm
Where floor joists run continuously over the top of bearers, bearers must be a minimum of 60 mm wide. Where floor joists run continuously over a bearer or cantilever from a bearer, the bearer must be a minimum of 60 mm wide, with 30 mm minimum support at the ends.
9
10
FLOOR BEARERS
Floor / Balcony Joist
Floor / Balcony Bearer
FLOOR BEARERS
Post / Support
A deck bearer is the primary horizontal structural member in a deck frame. It spans between posts, stumps, or a primary structure, and carries the joists, which in turn support the decking boards. Because bearers collect the loads from every joist above them and transfer them down to the footings, they are usually deeper, thicker sections than the joists, and they are sized for longer or more heavily loaded spans. Spec Beam 13.2 Green H3 treated LVL is well suited to this role. Its E13.2 stiffness rating (a modulus of elasticity of 13,200 MPa) and consistent engineered properties allow for longer spans between posts, which can mean fewer footings and a simpler substructure than sawn timber of the same size. Its straight, dimensionally stable laminated veneer construction gives a level platform for the joists, reducing the need for packing and helping keep the finished deck flat. The H3 treatment makes it suitable for outdoor, above-ground use exposed to the weather, protecting against decay and termite attack. Bearers must be kept clear of the ground and supported on posts or stumps, because ground-contact applications require H4 or H5 treatment. Bearer size should be selected from the Spec Beam span tables to suit the post spacing, the joist span it carries and the design loads. Connections to posts should use galvanised or stainless steel fixings rated for treated timber, and any cut or drilled surfaces should be resealed with a compatible preservative.
Size
BALCONY BEARERS Hardwood Decking, No Ceiling - >1.0m off Ground (2.0 kPa) - 25kg/m2 Floor Load Width (FLW) Span Type 1.0m 2.0m
11 3.0
90x45
Single Continuous
1200 1500
1000 1000
0 0
2/90x45
Single Continuous
1500 2000
1200 1500
1000 1200
90x63
Single Continuous
1400 1700
1100 1200
0 1000
130x45
Single Continuous
1800 2200
1400 1500
1200* 1200*
2/130x45
Single Continuous
2200 2900
1800 2100
1500 1700
130x63
Single Continuous
2000 2600
1600 1800
1400 1400
150x45
Single Continuous
2100 2500
1700* 1800*
1400* 1400*
2/150x45
Single Continuous
2600 3300
2100 2500
1800 2000
150x63
Single Continuous
2300 3000
1800 2100
1600* 1700*
170x45
Single Continuous
2400 2800
1900* 2000*
1600* 1700**
2/170x45
Single Continuous
2900 3600
2400 2800
2000 2300*
170x63
Single Continuous
2600 3300
2100 2400*
1800* 1900*
200x45
Single Continuous
2800 3400*
2200* 2400**
1900* 1900**
2/200x45
Single Continuous
3500 4100
2800 3400*
2400* 2700*
200x63
Single Continuous
3100 3800
2400* 2800*
2100* 2300**
240x45
Single Continuous
3300 3900*
2600* 2700**
2300* 2000**
2/240x45
Single Continuous
4000 4700
3300* 3800*
2800* 3100**
240x63
Single Continuous
3600 4300
2900* 3400**
2600* 2800**
300x45
Single Continuous
4000* 4400*
3300* 3100**
2800* 2000**
2/300x45
Single Continuous
4700 5600
4000* 4300*
3600* 3600**
300x63
Single Continuous
4300 5100*
3600* 4300**
3200* 2800**
360x45
Single Continuous
4500* 4600**
3800* 3100**
3200* 2000**
2/360x45
Single Continuous
5300 6400*
4500* 4500**
4100* 3700**
360x63
Single Continuous
5000* 5900*
4200* 4300**
3800* 2800**
400x45
Single Continuous
5000* 4500**
4200* 3100**
3200* 2000**
Single
5700
4900*
4500*
Continuous
6400*
4500**
3700**
2/400x45
Refer to page 18 for specification notes * 90mm bearing to end & intermediate supports. ** 90mm bearing to end & 135mm bearing intermediate supports.
12
ROOF RAFTERS Roof Rafter Roof Beam
Roof Beam
ROOF RAFTERS
A roof rafter is an inclined structural member that runs from the ridge or a supporting beam down to the wall plate or outer beam, and carries the roof battens or purlins and the roofing material above. Rafters must resist the downward loads from the roof covering, maintenance traffic and any snow. They must also resist wind uplift, so they are sized to suit the roof material (sheet or tile), the rafter span and spacing, the roof pitch and the site’s wind classification. Spec Beam 13.2 Green H3 treated LVL suits rafters in exposed or external roof structures such as pergolas, verandahs, patios, carports and exposed rafter tails, where the timber is open to the weather rather than enclosed within a roof space. Spec Beam 13.2 Green H3’s consistent engineered properties allow longer, cleaner spans with minimal sag, which matters when the underside of the roof is on show. Its straight, dimensionally stable laminated veneer construction helps keep the roof plane true, so battens and roof sheeting sit flat without packing. The H3 treatment protects against decay and termite attack in above-ground exterior conditions. Rafter size should be selected from the Spec Beam span tables to suit the roof load, spacing and wind classification. Rafters must be tied down to their supports with connectors rated for treated timber and designed for the uplift forces on the roof. Any cut, notched or drilled surfaces, including birdsmouth cuts and shaped rafter tails, should be resealed with a compatible preservative.
13
ROOF RAFTERS
Sheet Metal Roofing (20 kg/m2) Size
90x45 130x45 150x45 170x45 200x45 240x45 300x45 360x45 400x45
Span Type Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous
Rafter Centres (mm) 450 600 900 <5 Degree Roof Pitch
1200
2400 2700 3500 4000 4100 4600 4600 5200 5500 6100 6600 7300 7800 8000 8700 8000 9300 8000
2400 2700 3400 4000 3900 4600 4400 5200 5100 6100 6000 7300 7000 8000 7900 8000 8500 8000
2200 2700 3100 4000 3600 4600 4100 5200 4800 6100 5700 7100 6600 8000 7600 8000 8100 8000
2300 2600 3300 3800 3700 4500 4200 5000 4900 5900 5800 7100 6700 8000 7600 8000 8200 8000
2100 2600 3000 3800 3500 4500 3900 5000 4600 5900 5400 6900 6400 8000 7300 8000 7800 8000
2100 2500 3000 3600 3500 4100 3900 4700 4600 5500 5400 6700 6300 7800 7100 8000 7600 8000
1900 2500 2800 3600 3200 4100 3600 4700 4200 5500 5000 6400 5900 7400 6700 8000 7200 8000
2400 2700 3500 4000 4100 4600 4600 5200 5500 6100 6500 7300 7500 8000 8400 8000 9000 8000
<15 Degree Roof Pitch 90x45 130x45 150x45 170x45 200x45 240x45 300x45 360x45 400x45
Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous
2300 2600 3400 3800 4000 4500 4500 5000 5300 5900 6400 7100 7500 8000 8400 8000 9000 8000
Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous Single Continuous
2200 2500 3200 3600 3700 4100 4200 4700 5000 5500 6000 6700 7000 8000 7800 8000 8300 8000
2300 2600 3400 3800 4000 4500 4500 5000 5300 5900 6200 7100 7200 8000 8100 8000 8700 8000
<25 Degree Roof Pitch 90x45 130x45 150x45 170x45 200x45 240x45 300x45 360x45 400x45
Refer to page 18 for specification notes
2200 2500 3200 3600 3700 4100 4200 4700 5000 5500 5800 6700 6700 8000 7500 8000 8100 8000
14
ROOF BEAMs
Roof Rafter Roof Beam
Roof Beam
A roof beam is a primary horizontal structural member that supports the roof framing above it. It typically carries rafters or purlins and transfers their loads to posts, columns or walls below. Roof beams include ridge beams in raked or exposed-ceiling roofs, as well as the outer, fascia and intermediate beams of pergolas, verandahs, patios and carports.
ROOF BEAMS
Because they gather load from many rafters and often span wide openings between few supports, roof beams are usually the most heavily loaded members in the roof structure. They are sized for the roof area they support, the span between posts, the roof material and the site’s wind classification. Spec Beam 13.2 Green H3 treated LVL is well suited to roof beams in exposed or external structures. Its consistent engineered properties allow long spans with controlled deflection. That means fewer posts, more open outdoor spaces and a clean, straight beam line that stays true when the structure is on show. Its dimensionally stable laminated veneer construction resists the bowing, twisting and checking that can affect large sawn sections, and it is available in deep sections and long lengths without the need for joins. The H3 treatment protects against decay and termite attack in above-ground exterior conditions. Beam size should be selected from the Spec Beam span tables to suit the roof load width, span and wind classification. Connections to posts and rafters must use brackets and tie-downs rated for treated timber and designed to resist both gravity loads and wind uplift. Any cut or drilled surfaces should be resealed with a compatible preservative.
15
ROOF BEAM Sheet Metal Roofing (20 kg/m2) Roof Load Width (RLW) 2.0m 3.0m 4.0m 5.0m <5 Degree Roof Pitch
6.0m
Single Continuous
1700 2300
1500 2000
1300 1700
1200 1600
1000 1400
2/90x45
Single Continuous
2200 2900
1800 2500
1600 2200
1500 2000
1400 1900
90x63
Single Continuous
1900 2600
1600 2200
1500 2000
1300 1800
1200 1600
130x45
Single Continuous
2500 3400
2200 2900
1900 2600
1700 2300
1600 2100
2/130x45
Single Continuous
3100 4200
2700 3600
2400 3300
2200 2900
2000 2800
130x63
Single Continuous
2800 3800
2400 3300
2200 2900
1900 2600
1800 2400
150x45
Single Continuous
2900 4000
2500 3400
2200 3000
2000 2700
1800 2400
2/150x45
Single Continuous
3600 4800
3100 4200
2800 3700
2500 3400
2300 3200
150x63
Single Continuous
3300 4400
2800 3800
2500 3400
2200 3000
2100 2800
170x45
Single Continuous
3300 4500
2800 3800
2500 3400
2200 3100
2100 2800
2/170x45
Single Continuous
4000 5400
3500 4700
3100 4200
2800 3900
2700 3500
170x63
Single Continuous
3600 4900
3200 4200
2800 3800
2600 3400
2300 3200
200x45
Single Continuous
3900 5200
3400 4500
2900 4000
2700 3600
2500 3300
2/200x45
Single Continuous
4700 6300
4100 5600
3700 5000
3400 4600
3100 4200
200x63
Single Continuous
4300 5800
3700 5000
3300 4500
3000 4000
2800 3800
240x45
Single Continuous
4600 6100
4000 5400
3500 4600
3300 4100
3000 3700
2/240x45
Single Continuous
5600 7100
4900 6500
4400 5900
4000 5400
3700 5100
240x63
Single Continuous
5100 6600
4400 5900
4000 5300
3600 4900
3400 4500
300x45
Single Continuous
5800 7200
5000 6100
4500 5200
4000 4600
3800 4100
2/300x45
Single Continuous
6600 8000
6000 7600
5500 7000
5100 6500
4600 5900
300x63
Single Continuous
6200 7700
5500 7000
4900 6500
4500 6000
4200 5600
360x45
Single Continuous
6600 7900
5900 6500
5300 5500
4900 4900
4500 4100
2/360x45
Single Continuous
7600 8000
6900 8000
6400 7700
6000 6900
5600 6300
360x63
Single Continuous
7100 8000
6400 8000
5900 7400
5400 6900
5000 5800
400x45
Single Continuous
7100 7900
6500 6500
5800 5500
5200 4900
4700 4100
Size
Span Type
90x45
2/400x45
Single
8100
7400
6900
6500
6100
Continuous
8000
8000
7700
6900
6300
Refer to page 18 for specification notes
16
ROOF BEAM Sheet Metal Roofing (20kg/m2) Roof Load Width (RLW) 2.0m 3.0m 4.0m 5.0m <15 Degree Roof Pitch
6.0m
Single Continuous
1700 2300
1500 2000
1300 1700
1100 1600
1000 1400
2/90x45
Single Continuous
2200 2900
1800 2500
1600 2200
1500 2000
1400 1800
90x63
Single Continuous
1900 2600
1600 2200
1500 2000
1300 1800
1200 1600
130x45
Single Continuous
2500 3400
2200 2800
1900 2600
1700 2300
1600 2100
2/130x45
Single Continuous
3100 4100
2700 3600
2300 3200
2200 2900
2000 2700
130x63
Single Continuous
2800 3700
2400 3200
2100 2800
1900 2600
1700 2400
150x45
Single Continuous
2800 3900
2500 3400
2200 2900
2000 2700
1800 2400
2/150x45
Single Continuous
3500 4800
3100 4100
2800 3700
2500 3400
2300 3100
150x63
Single Continuous
3200 4300
2800 3700
2400 3300
2200 3000
2100 2800
170x45
Single Continuous
3300 4400
2800 3800
2500 3400
2200 3000
2100 2800
2/170x45
Single Continuous
4000 5400
3400 4600
3100 4200
2800 3800
2600 3500
170x63
Single Continuous
3600 4900
3100 4200
2800 3700
2500 3400
2300 3100
200x45
Single Continuous
3900 5200
3300 4500
2900 4000
2700 3500
2400 3200
2/200x45
Single Continuous
4600 6200
4000 5500
3600 4900
3400 4500
3100 4100
200x63
Single Continuous
4200 5700
3600 4900
3300 4400
2900 4000
2800 3700
240x45
Single Continuous
4600 6100
4000 5300
3500 4600
3200 4000
2900 3700
2/240x45
Single Continuous
5600 7100
4900 6400
4400 5800
4000 5400
3700 5000
240x63
Single Continuous
5100 6500
4400 5900
3900 5200
3500 4800
3300 4500
300x45
Single Continuous
5700 7100
4900 6000
4400 5200
4000 4600
3700 4000
2/300x45
Single Continuous
6600 8000
6000 7500
5400 7000
5000 6500
4600 5800
300x63
Single Continuous
6200 7700
5400 7000
4900 6400
4500 5900
4100 5500
360x45
Single Continuous
6500 7800
5800 6400
5200 5400
4800 4800
4500 4000
2/360x45
Single Continuous
7500 8000
6800 8000
6400 7700
5900 6800
5500 6200
360x63
Single Continuous
7000 8000
6400 7900
5800 7300
5300 6800
4900 5600
400x45
Single Continuous
7100 7700
6400 6300
5700 5400
5100 4800
4600 4000
Size
Span Type
90x45
2/400x45
Single
8100
7400
6800
6500
6100
Continuous
8000
8000
7700
6800
6100
Refer to page 18 for specification notes
17
ROOF BEAM Sheet Metal Roofing (20kg/m2) Roof Load Width (RLW) 2.0m 3.0m 4.0m 5.0m <25 Degree Roof Pitch
6.0m
Single Continuous
1600 2200
1400 1900
1200 1700
1100 1500
1000 1400
2/90x45
Single Continuous
2100 2800
1800 2400
1600 2200
1500 2000
1300 1800
90x63
Single Continuous
1900 2500
1600 2200
1400 1900
1300 1700
1100 1600
130x45
Single Continuous
2400 3300
2100 2800
1800 2500
1600 2200
1600 2000
2/130x45
Single Continuous
3000 4000
2600 3500
2300 3100
2100 2800
1900 2600
130x63
Single Continuous
2700 3600
2300 3100
2100 2800
1800 2500
1700 2300
150x45
Single Continuous
2800 3800
2400 3300
2200 2800
1900 2600
1700 2300
2/150x45
Single Continuous
3400 4600
3000 4000
2700 3600
2400 3300
2200 3000
150x63
Single Continuous
3100 4200
2700 3600
2400 3200
2200 2900
2000 2700
170x45
Single Continuous
3200 4300
2800 3700
2400 3300
2200 2900
2000 2600
2/170x45
Single Continuous
4000 5200
3400 4600
3000 4000
2800 3700
2500 3400
170x63
Single Continuous
3500 4700
3000 4100
2700 3600
2400 3300
2200 3000
200x45
Single Continuous
3700 5100
3200 4300
2800 3900
2600 3400
2400 3100
2/200x45
Single Continuous
4600 6100
4000 5300
3500 4800
3300 4400
3000 4000
200x63
Single Continuous
4100 5600
3500 4800
3200 4300
2800 3900
2700 3600
240x45
Single Continuous
4500 5900
3900 5200
3400 4500
3100 4000
2800 3500
2/240x45
Single Continuous
5400 7000
4700 6300
4300 5800
3900 5200
3600 4800
240x63
Single Continuous
4900 6500
4300 5800
3800 5200
3400 4600
3200 4300
300x45
Single Continuous
5600 7100
4800 5800
4300 5000
3900 4500
3600 3700
2/300x45
Single Continuous
6500 8000
5900 7400
5300 6800
4800 6300
4500 5700
300x63
Single Continuous
6100 7600
5300 6800
4700 6300
4300 5800
4000 5200
360x45
Single Continuous
6500 7600
5800 6100
5200 5200
4600 4600
4300 3700
2/360x45
Single Continuous
7400 8000
6700 8000
6200 7400
5800 6500
5300 5900
360x63
Single Continuous
6900 8000
6200 7800
5700 7100
5200 6400
4800 5200
400x45
Single Continuous
7000 7500
6300 6100
5500 5200
5000 4600
4600 3700
Size
Span Type
90x45
2/400x45
Single
7900
7200
6700
6300
5900
Continuous
8000
8000
7400
6500
5900
Refer to page 18 for specification notes
18
Guide Notes - General Refer to pages 6 and 7 of this guide for span and span type definitions 2. Member sizes specified based on serviceability criteria outlined in the tables in AS1720.3 Section 2 3. Member sizes nominated are based on the product being exsposed to moisture and maintaining an average moisture content of >30% i.e. K4 per AS1720.1 clause 2.4.2 4. Member sizes nominated are based on construction in all regions of Australia. k6 = 0.9 per AS1720.1 clause 2.4.3 5. Bearers and joists sizes and spans are subject to minimum bearing requirements shown on Page 9. 6. Spec Beam® LVL may be cut, drilled, or notched using standard woodworking tools, subject to the limitations outlined in the AS1684 series of standards. 7. All fixings must be compatible with timber construction and suitable for the exposure conditions of the application. Corrosion protection must comply with the requirements of the relevant Australian Standards. 1.
Guide Notes - Floor Framing 8.
Floor joist centres should be selected so as to obtain adequate support for the floor covering
9.
Floor framing members are to be installed per AS1684.2, AS1684.3 and good building practice
GUIDE NOTES - ROOF & FLOOR FRAMING
10. Floor bearers designed as Category 2 Primary Elements per Table 2.1 of AS1720.1 11.
Floor bearer details shown are based on the floor joists supported continuously over the bearer
12.
Continuos spans are capped at 8.0m
Floor Bearerer spans may be govered by bearing strength. The following conditions apply as noted on the span tables: * 90mm bearing required to end & intermediate supports ** 90mm bearing required to end supports & 135mm bearing required to Intermediate supports 13.
Guide Notes - Roof Framing 14.
All members are designed using a wind classification N3
Rafter spacings / centres should be selected so as to obtain adequate support for roof battens or ceiling materials respectively. Refer to product manufacturer for details 15.
16.
Roof framing members to be installed per AS1684.2 and good building practice
17.
Beam details shown are based on the rafter being supported continuously over the beam
18.
Continuos spans are capped at 8.0m
Design Responsibility This guide provides span and sizing information for common residential applications only. It does not replace project-specific engineering design. Where conditions fall outside the scope of this guide, including but not limited to: • Non-standard loading conditions • Commercial or industrial applications • Irregular framing layouts Design must be undertaken by a suitably qualified structural engineer.
Information in the guide is to be used for ITI Spec Beam 13.2 GREEN H3 only
Product Handling & Storage Spec Beam® 13.2 Green H3 LVL should be stored flat, off the ground, and protected from weather exposure prior to installation. Temporary exposure during construction is acceptable; however, prolonged exposure to moisture should be avoided.
19
Transport While transporting or storing the product, increased moisture caused by rain or splashing must be avoided. If Spec Beam products are moved with a forklift truck, sufficiently wide enough forks must be used in order to avoid damaging the product. When lifting several packs at a time, the distance between forks must be wide enough to ensure safe lifting. Surface-treated products should be delivered direct to site without additional, unnecessary off-loading during delivery.
Storage Spec Beam products must be stored under cover. When storing the products temporarily on site, a solid, straight and dry platform should be used. The height of ground bearers must be at least 300 mm. To avoid twisting of the product, the bearers between packs must be aligned vertically with the ground bearing timbers. The plastic wrapping of each pack must be cut open from underneath to enable moisture to evaporate from the bundles. If the products are stored on site for longer than one week, the bundles must be covered with an additional protective covering. Conditions of the products and protective cover must be monitored regularly during storage.
Handling Spec Beam product packs may be unloaded on site with either a forklift or a crane. Approved webbing slings must be used if unloading with crane. It is forbidden to use chains or wires. If unloading is done manually, the pack is opened and the products are carried one-by-one. While cutting the banding, beware of the band ends. Spec Beam products should not be dragged or dropped. Spec Beam is a lightweight material and is easy to shape, which means notable time and cost savings in construction. Spec Beam products can be processed with conventional wood working and power tools. There is no need for separate specialist tools.
Product Identification
This identification provides traceability and confirms compliance with applicable standards. Disclaimer This document has been prepared as a technical guide to assist designers, builders, and industry professionals. While every effort has been made to ensure accuracy, ITI does not accept liability for errors or omissions arising from reliance on this guide. Users must ensure that all designs and installations comply with current building regulations, standards, and project-specific requirements.
PRODUCT HANDLING
Each Spec Beam® 13.2 LVL member is clearly marked with: • Product name • Strength grade • Joint group classification • Manufacturing information
NT QLD WA SA NSW ACT VIC
TAS
ITI LOCATIONS: ITI Technical Support Centre 68-80 Kirkham Road West, Keysborough, Victoria 3173 P || 03 9392 8400 E || ewp@iti.net.au
ITI Queensland (Brisbane) 63 Creek Street, Bundamba, Queensland 4034 P || 07 3436 8400 E || ewpqld@iti.net.au
ITI Victoria (Melbourne) 68-80 Kirkham Road West, Keysborough, Victoria 3173 E || ewpvic@iti.net.au P || 03 9392 8400
ITI New South Wales (Sydney) 59 Dunheved Circuit, St Marys, New South Wales 2760 P || 02 8805 5000 E || ewpnsw@iti.net.au
ITI Queensland (Townsville) 54-62 Enterprise Street Bohle, Queensland 4818 P || 07 4724 5509 E || ewpqld@iti.net.au
ITI Western Australia (Perth) 102-108 Bannister Road, Canning Vale, Western Australia 6155 P || 08 9256 5700 E || ewpwa@iti.net.au
ITI New South Wales (Newcastle) 19 Nelson Road, Cardiff, New South Wales 2285 P || 02 4953 7666 E || ewpnsw@iti.net.au
ITI South Australia (Adelaide) 82-94 Grand Trunkway, Gillman, South Australia 5013 P || 08 8447 0400 E || ewpsa@iti.net.au
ITI TASMANIA (BELL BAY) 17 Bell Bay Road, Bell Bay, Tasmania 7253 P || 03 9111 9300 E || ewptas@iti.net.au