Product Technical Statement ClimaGuard™ Issue B | 13 November 2026
Product Type and Application
Evidence of Suitability
ClimaGuard™ is a Class 4 vapour permeable, non-reflective and electrically non-conductive pliable building membrane for external wall applications. It is classified as Light Wall duty and as a water barrier in accordance with AS 4200.1.
Independent laboratory testing has been completed against the material-property and classification requirements of AS 4200.1.
The non-woven membrane is intended for installation to the exterior side of framed walls, behind brick veneer and lightweight cladding systems including fibre cement, timber and weatherboard claddings. ClimaGuard allows water vapour to escape while helping control external water, wind and dust before the exterior cladding is installed.
AWTA Product Testing Report 25-005104 • Resistance to dry delamination • Resistance to wet delamination • Moisture shrinkage • Tensile strength • Edge tear resistance • Burst strength • Resistance to water penetration
Compliance with the NCC When correctly specified and installed, ClimaGuard supports compliance with the following condensation-management provisions:
NCC 2025 • Volume One F8D3 and ABCB Housing Provisions 10.8.1, through compliance with AS 4200.1 and installation in accordance with AS 4200.2. • Class 4 vapour permeance supports use where the applicable wall design requires a vapour-permeable control layer. Project-specific climate-zone and wall-system requirements must be confirmed by the designer.
NCC 2022 Amendment 2
• Electrical conductivity • Water vapour transmission and Class 4 classification • Surface emittance and non-reflective classification
AWTA Product Testing Report 25-005103 • Resistance to UV exposure in accordance with AS 4200.1 Appendix A2 following 500 hours of ASTM G154 UVA-340 exposure - complies.
Additional Product Information • Nominal mass per unit area: 130 g/m². • Flammability Index: 1 (Low) when tested to AS 1530.2. • Colour: blue with white print.
• Volume One F8D3 and ABCB Housing Provisions 10.8.1 for pliable building membranes used in external walls. • The applicable NCC edition and any state or territory variations must be confirmed for each project.
This statement summarises the referenced product test evidence. It must be read with the current ClimaGuard installation instructions, the relevant cladding-system requirements and the project documentation.
Document Reference ClimaGuard PTS001 B | ITI Australia | climaguard.com.au
Page 1 of 3
Product Technical Statement ClimaGuard™ Issue B | 13 November 2026
Limitations of Use
Specific Design and Installation Instructions
• Product configuration. Compliance is supported only for the ClimaGuard product and configuration identified by the product markings and referenced test evidence.
• Electrical safety. Isolate electrical power before installation and observe all site electrical-safety procedures.
• Wall applications only. ClimaGuard is intended for external wall applications and is not covered by this statement for use as roof sarking.
• Application suitability. Install on the exterior side of the building frame and primary insulation layer, behind a compatible external cladding system.
• Not an internal lining. The product has not been assigned a Group Number and must not be used as an exposed internal wall or ceiling lining.
• Cladding compatibility. Confirm the membrane classification, cavity arrangement, fixing method and tape compatibility with the cladding manufacturer.
• No reflective R-value. The product is non-reflective and does not provide a claimed reflective air-space R-value.
• Drainage and drying. Where direct-fixed or profiled cladding restricts drainage and drying, provide a drained cavity where required by the project design or cladding instructions.
• Facade applications. The product has not been assessed in this statement for pressure-equalised or open-jointed facade applications. • Exposure before cladding. ClimaGuard may remain exposed for up to 60 days before installation of the exterior cladding, subject to the installation instructions and inspection for damage before cladding. • Harsh conditions. Provide additional mechanical restraint where wind or construction exposure may exceed normal conditions. • Chemical contact. Do not allow contact with wet concrete, mortar, alkaline materials, incompatible coatings or solvents. • Ground and water contact. The product is not suitable for submersion, waterproofing applications or continuous contact with soil. • Design responsibility. ClimaGuard does not replace project-specific assessment of condensation, drainage, wind pressure, fire, cladding compatibility or structural support.
Storage and Maintenance • Store rolls in their original packaging in a clean, cool and dry area, protected from direct sunlight and weather. • Keep rolls off the ground and protect them from physical damage during transport and storage. • Do not pressure clean the installed membrane or use mineral-based or incompatible chemical cleaners.
Document Reference ClimaGuard PTS001 B | ITI Australia | climaguard.com.au
• Support and fixing. Support, tension and fix the membrane in accordance with AS 4200.2, the wind classification, framing layout and current ITI installation instructions. Use mechanical fixings where required by the application and the current installation guide. • Vapour and air control. Where continuity is required, seal overlaps, end laps, discontinuities and penetrations using ClimaGuard façade tape or a compatible heat- and moisture-resistant tape. • Water control. Use minimum 150 mm overlaps, or minimum 50 mm overlaps taped on the exterior face, unless the approved project detail requires a greater overlap. • Vertical joints. Improve water control by taping vertical joints and sealing penetrations, end laps and discontinuities. • Damage prevention. Do not puncture, crease, crush, sharply fold or drag the membrane over the frame. Repair penetrations and damage with compatible materials before cladding. • Condensation risk. The designer should assess the complete wall system, climate zone, internal humidity, insulation, control-layer position and drying potential. Hygrothermal analysis may be required for higher-risk assemblies.
Installation Standard Install ClimaGuard in accordance with AS 4200.2 and all applicable NCC, project, cladding-system and ITI requirements. Where requirements differ, obtain project-specific direction from the building designer or relevant certifier before installation.
Page 2 of 3
Product Technical Statement ClimaGuard™ Issue B | 13 November 2026
Available Roll Sizes Product
Width mm
Length m
Nominal area m²
ClimaGuard wall wrap
1350
30
40.5
ClimaGuard wall wrap
1500
30
45.0
ClimaGuard wall wrap
2700
30
81.0
ClimaGuard wall wrap
3000
30
90.0
Additional Product Data to AS 4200.1 Property
Result
Notes
Nominal mass per unit area
130 g/m²
Duty classification
Light Wall
Burst strength AS 2001.2.19
222 N
Mean
Tensile strength AS 1301.448s
4.2 kN/m
Machine
Tensile strength AS 1301.448s
2.7 kN/m
Lateral
Edge tear resistance
214 N
Machine
Edge tear resistance
141 N
Lateral
Water control classification
Water Barrier
Pass
Vapour control classification
Class 4
6.230 µg/N.s
Water vapour transmission
821 g/m²/24 h
Mean
Electrical conductivity
Non-conductive
>1 × 10¹² Ω
Emittance classification
IR Non-Reflective
Category NN
Near-normal emittance
0.77 / 0.76
White / Blue
Dry delamination
Pass
Wet delamination
Pass
Moisture shrinkage
0.3%
Mean
Flammability Index AS 1530.2
1
Low
UV resistance Appendix A2
Complies
500 h UVA-340
UV result: after 500 hours of ASTM G154 UVA-340 exposure, mean tensile strength was 3.9 kN/m in the machine direction and 2.4 kN/m in the lateral direction. Report 25-005103 records compliance with AS 4200.1 Appendix A2.
Technical enquiries ITI Australia 02 8805 5000 | sales@climaguard.com.au | www.climaguard.com.au
Document Reference ClimaGuard PTS001 B | ITI Australia | climaguard.com.au