3 minute read

System Operation

The compressor inlet is low pressure and the outlet is high pressure. The reed valves are one way. They open to allow refrigerant gas to enter the compressor on the down stroke and exit on the upstroke. Note the open valves in the illustrations.

The clutch is mounted on the shaft of the compressor and is engaged by electromagnetic action. Part of the clutch assembly is an electromagnetic wire coil. The coil is energized through a thermostat that senses the temperature in the evaporator coil. If the evaporator is too warm the electrical contacts close and allows power to flow to the clutch. The compressor shaft is engaged and moves the refrigerant around inside the system. Figure 2-4 is a cutaway view of the clutch mounted on the compressor

The clutch shown here has its electromagnetic coil mounted on the compressor body. When the coil is energized, magnetic force pulls the clutch drive plate into the pulley. This action locks the pulley to the compressor drive shaft and drives the compressor

2. Condenser

The refrigerant gas leaves the compressor and moves through a high pressure hose to the condenser. Inside the condenser the gas “changes state” and becomes a liquid. It is still hot and under pressure. Remember in Chapter 1 when we talked about water at 212 degrees Fahrenheit? Heat energy was involved in the “change of state,” but the temperature did not change. The same kind of action happens inside the AC system. The refrigerant gas gives up a lot of heat energy to the outside air as it “changes state” in the condenser. Figure 2-5 illustrates a condenser. Air moving through the condenser absorbs heat from the refrigerant. The amount of air flow through the condenser is the major factor in how well the condenser functions.

As the refrigerant gas moves through the tubing coil from top to bottom, it condenses (changes state) into a liquid. For ease of installation, condenser fittings are often routed close together

This cutaway view of a receiver-drier shows the filter elements, inlet, outlet and refrigerant path. The sight glass is a small window into the system used in diagnosis and when adding refrigerant (charging the system).

3. Receiver-Drier

The liquid refrigerant continues to move inside the system, out of the condenser through a tube or hose to the receiver-drier. The receiver-drier serves as a small storage tank and filter for the refrigerant. It is also a good location to mount pressure switches and often contains a sight glass (small window) used to view activity inside the system. The receiver-drier, Figure 2-6, also separates gas (bubbles) from the liquid with a pick-up tube as shown in this illustration. Some receiver-driers have a spring to preload the desiccant pack.

System Operation

4. Expansion Valve (Refrigerant Metering Device)

When refrigerant moves from the receiver-drier, it travels through another high pressure hose to a metering device at the inlet of the evaporator coil. The metering device can be an expansion valve, an expansion tube or a combination (multiple function) valve. Between the compressor and this point inside the system, the pressure is high and can range from 150 to 250 pounds per square inch. The expansion valve (TXV) is closely connected to the evaporator. A diaphragm opens the valve by exerting pressure on the spring. Pressure comes from gas inside the diaphragm housing on top of the valve and in the sealed sensing bulb. The sensing tube is located in the outlet of the evaporator and picks up heat from warm refrigerant leaving the evaporator. The gas in the valve diaphragm housing and sensing tube expands when it gets warmer and forces the expansion valve open at the metering orifice.

This block type expansion valve cutaway view will give you a better idea how these valves work. Spring pressure holds the valve closed.

5. Evaporator Coil

The expansion valve or other type of metering device bleeds high pressure refrigerant into the evaporator coil, where the pressure is low. The refrigerant expands rapidly in this low pressure environment. When it expands it “changes state”. The sudden drop in pressure brings the refrigerant temperature down quickly inside the evaporator coil.

Figure 2-8 shows an evaporator coil and thermostat. Refrigerant is sprayed into the evaporator by the high side pressure when the expansion valve opens. The refrigerant absorbs heat from the air when the blower forces the air through the fins. When the thermostat probe senses the upper limit of the thermostat heat setting, a circuit closes. The compressor clutch engages and the compressor operates and moves more refrigerant to the high side of the system.

This article is from: