3. AC plug connection and DC plug
2. DC plug
(continued) -fix connection cable with strain relief device -close connection area, install cover
Advertisement
DC plug example: multicontact plug -max. current at MC3 = 20 A -max. current at MC4 = 30 A
Connection rail with 5 pairs of plugs
Strain relief for connection cablel DC sockets -
DC plug +
Illustration also applicable for connection rail with 1 - 5 pairs of plugs Note! When installing the DC plugs for connection with the solar modules, make sure that the poles of the solar modules correctly correspond with the symbols „+“ and „-“.
-install the multicontact plugs at plus and minus poles of solar module strings -connect the strings to the FRONIUS IG unit
Note! Never disconnect the DC plugs from the respective sockets during power feed operation of the FRONIUS IG unit. Before disconnecting the strings always first disconnect the mains supply or switch the FRONIUS IG to standby operation.
Not complying with this instruction may damage the connection plugs.
Should an electric arc develop during disconnecting, both plug and socket must be replaced. Do not re-use defective DC plugs.
To make installation and maintenance work easier, the solar modules and the mains are connected with plugs. Depending on which version is used, up to five pairs of DC plugs are available for connecting the solar modules. Connection to the mains is effected by means of a touchproof AC plug which can be latched.
-Fix the FRONIUS IG unit on the wall as shown in chapter „Installation“
Note! Only cables up to a cross section of 4 mm² are permitted for the AC-plug-type connector.
3. AC plug connection and DC plug
3. AC plug connection and DC plug
(continued)
5 mm
Connect phase (brown) Connection earth (yellow/green) Bare the mains cable as shown in the illustration for the AC-plug-type connector
Connect zero lead (blue) Install the AC plug as follows: -slide parts (2) and (3) on to the mains cable as shown in the illustration below -connect the mains cable leads with the AC plug as shown in opposite illustration
(1) (2) (3)
white: for main cable with 5 to 11 mm diameter
black: for main cable with 9,5 to 15 mm diameter
-assemble AC plug -connect AC plug to FRONIUS IG unit and latch
Note! Always shut off voltage before unplugging the AC connection by disconnecting fuse in the house distribution cabinet.
DC plug example: multicontact plug -max. current at MC3 = 20 A -max. current at MC4 = 30 A