GENERAL NOTES: •
All dimensions and levels to be verified on site, prior to the commencement of setting out ,working drawings or conctruction drawings are not to be scaled. Figured dimensions only are to be used. Any discrepancies, errors and omissions are to be reported to the Architect immeditely before commencing with any work. All shop drawings are to be submitted for designer's approval prior to manufacturign and installation. All work is to be in strict accordancen with the by-laws and regulations of the local authority. Where required, architects drawings are to be read in conjunction with engineers drawings. Copyright and right of reproduction of this drawing or any part thereof is reserved and remains with the architect. All structural concrete,brick work ,steel works and timber works are to the engineers specification & details. All timber to be grade 6/7 - section 1&2 All roof timber trusses to be as per the National building Regulations. Glazing to be as per the National building Regulations. Addional requirements recommended by supplier to be discussed with Archiect & Cient.
• •
WALL LEGEND:
•
NEW BRICK WALLS
• •
NEW CONCRETE WALLS - CLASS 1
•
NEW DRYWALLS
•
EXISTING WALLS
• • •
Please note: Plastering All external plaster to contain Perlite as per the manufacturer’s specification. All internal plaster to be two coat plaster finished perfectly smooth and hard, with steel reinforced corners.
Roof fascia board as per specialist specifications as per manufacturer.
Landscaping as per specialist
15°
Dpc
FILL
FILL
-255
Surface bed 85mm thick concrete surface bed with Ref 193 steel mesh on damproof course layer on sand.
D 1
Timber slats as per specialist -425
FILL
Dpc
Dpc
FILL
New Foundations to Engineers detail
NGL
1990
1960
3995
4590
170
600
FILL
Dpc
Dpc
50mmØ waste pipes COVERED CAR PARKING to be laid in slab as U/s slab @ 2875mm afsl per specialist Non Slip Tiles 330x330mm concrete column to Engineers detail
New Steel sheet surround panel as per specialist
Existing 110mmØ outlet pipe to soak pit to remain unaffected
2520 510
EXTERNAL POOL DECK BEHIND
SEPTIC TANK BELOW (To remain unaffected) Additional fittings & requirements as per specialist
2550
Galvanized 3mm aluminium panels on 50x50mm SHS sub-frame. waterproofing by specialsit Raised platform to Engineers detail & specifications
NGL
SOAK PIT Below to remain unaffected
AREA SCHEDULE:
Wood fire place to specialist detail and interiors position
0
Planter-no concrete Waterproofing as per specialist
FIRST STOREY
330x510mm concrete beam to Engineers detail New raised sculpture podium to Engineers detail
New 170mm concrete slab to Engineers detail Planter- concrete below Landscaping as per specialist Waterproofing as per specialist
-510
Existing 110mmØ uPVC soil pipe min. 1:60 (max. 1:10) to remain unaffected (To connect to Septic Tank as per specialist detail & specifications)
Dpc
Timber decking as per specialist
Precast Rectangular Column with Multi Layer Corbels to Engineers detail
Surface bed Dpc FILL 120mm thick concrete surface bed with Ref 193 steel mesh on damproof course layer on sand.
New Foundations to Engineers detail
228 600
170 60
510
U/s slab plastered /rhinolited and painted
1m high SANS approved glass balustrade (by specialist) Bulkhead and ceiling as per specialist
3014 Fire wood storage unit to specialist detail and interiors position 2750 2665 228 350
2380
2350
2950
3680
2665
New 340mm concrete slab to Engineers detail
NGL
Surface bed 120mm thick concrete surface bed with Ref 193 steel mesh on 50mm thick high density polystyrene on damproof course layer on sand
3265
2240
W 9
5270
Louvre fixed screen on subframe to specialist detail
2670
DOUBLE GARAGE
2750
330x510mm concrete beam to Engineers detail
New Concrete lintels @ 2125mm afsl
U/s slab @ 2835mm afsl Tiles
2750
Open Timber Decking
Raised platform to Engineers detail & specifications Wood fire place to specialist detail and interiors position
2440
330x510mm concrete beam to Engineers detail
Dpc
2750
D 5
2607
510
U/s slab plastered /rhinolited and painted
510
New 340mm concrete slab to Engineers detail
Ottoman by specialist
Aircon by Specialist 7770
7690
New vanity as per specialit
3530
4510 1030 New vanity as per specialit
U/s Ceiling to Rafter Tiles
WALL PLATE
New Steel sheet surround panel as per specialist
BALCONY 1
2440
2670
2670 330x330mm concrete column to Engineers detail
U/s Ceiling to Rafter Tiles 2750
5311
Vertical Dpc
-425
Surface bed to Engineers detail slope to be confirmed on site.
D 1
Ottoman by specialist
BEDROOM 1
7260
LOUVRE SCREEN 1
2240
New Concrete lintels @ 2125mm afsl
New whb
2670
510
510
170
Dpc
New whb
BATHROOM 1
ROOF LEVEL
Concrete roof (47m²) 170mm concrete roof to Engineers details at 2% fall towards rainwater outlets. Waterproofing by specialist
Vertical Dpc
0
New B.I.C by specialist
Lighting fixtures as per specialist
5311
W 10.
Revision Description
Roof fascia board as per specialist specifications as per manufacturer.
New Concrete lintels @ 2950mm afsl
Vertical Dpc
GROUND STOREY
220mm brick wall to Engineers detail
New B.I.C by specialist
U/s Ceiling to Rafter Tiles
Dpc
2750
Landscaping as per specialist
85mm Exposed aggregate surfacebed ramp
2840
Self Closing Motorised Sliding Gate as per specialist
New steel sheet window surround to specialist detail
Timber slats as per specialist
BATHROOM 2
2750
220mm brick walls to Engineers detail
Revision Revision Number Date
150x150 CFLC steel gutters to Engineers detail & specifications
W 25
6277
New steel sheet window surround to specialist detail
Timber slats as per specialist
Aircon by Specialist
2580
Timber slats as per specialist Open Exposed aggregate surfacebeds
980
BEDROOM 2
U/s Ceiling to Rafter Tiles
330x510mm concrete beam to Engineers detail New 170mm concrete slab to Engineers detail
DRIVEWAY
Lighting fixtures as per specialist
2350
600
3530
1000
4103
Ceiling to underside of rafters 150mm Mineral fibre insulation between rafters
New Concrete lintels @ 2950mm afsl
2750
New Steel sheet surround panel as per specialist
2550
W 9.
Ceiling to underside of rafters 150mm 330mm brick walls Mineral fibre insulation between rafters to Engineers detail
7690
Polystyrene infill below plastic modular panter boxes
1350
4680
Green square modular plastic tray planter boxes as per specialist. Irrigation system required to be confirmed by specialist
7690
Planter- concrete below Landscaping as per specialist Waterproofing as per specialist
FIRST STOREY
Dpc
590
New steel sheet window surround to specialist detail
5270
6277
580
220mm brick walls to Engineers detail
WALL PLATE
W 25
980
Roof fascia board as per specialist specifications as per manufacturer.
980
ROOF LEVEL 7260
Revision Schedule
Concrete Roof Tiles (23m2) Concrete Roof Tiles as per specialist @ 20° & 45°.On 75x50mm purlins to Engineers detail. on 50x150mm timber rafters to Engineers specifications. Waterproofing by specialist
New Foundations to Engineers detail
Vertical Dpc
Concrete Roof Tiles (23m2) Concrete Roof Tiles as per specialist @ 20° & 45°.On 75x50mm purlins to Engineers detail. on 50x150mm timber rafters to Engineers specifications. Waterproofing by specialist
STAMPS:
NGL
GROUND STOREY 0
NGL
EXISTING NEW WORK TOTALS: EXISTING NEW WORK TOTALS:
BASEMENT
G.FLOOR
1st FLOOR
2nd FLOOR
3rd FLOOR 4th FLOOR
COVERAGE F.A.R. TOTAL AREAS:
New Foundations to Engineers detail
Galvanized 3mm aluminium panels on 50x50mm SHS sub-frame. waterproofing by specialsit
SECTION A-A SCALE 1 : 50
Concrete Roof Tiles (53m2) Concrete Roof Tiles as per specialist @ 20° & 45°.On 75x50mm purlins to Engineers detail. on 50x150mm timber rafters to Engineers specifications. Waterproofing by specialist
New 170mm concrete slab to Engineers detail
New Foundations to Engineers detail
Dpc
SCALE 1 : 50
1990
1990
4510
330x510mm concrete beam to Engineers detail
2860
Green square modular plastic tray planter boxes as per specialist. Irrigation system required to be confirmed by specialist Line of 170mm concrete slab behind to Engineers detail
2750 2410
510
2750
50x150mm timber rafters to Engineers specifications.Waterproofing by specialsit
New 340mm concrete slab to Engineers detail U/s slab plastered /rhinolited and painted
330x510mm concrete beam to Engineers detail
Timber decking as per specialist specifications as per manufacturer. Precast Rectangular Column with Multi Layer Corbels to Engineers detail
0
NGL
260
260
Open Timber Decking -255
2240 1510
EXTERNAL POOL DECK
2240
2240
2500
New Concrete lintels @ 2125mm afsl
LOT 194,104 Glen drive,Zinkwazi Beach,Kwadukuza Municipality
Planter- concrete below Waterproofing as per specialist
D 7
170
New Steel sheet surround panel as per specialist 510
930 170 340
Rainwater drainage chain as per specialist
7520
340
260
7520
2520
New Concrete lintels @ 2125mm afsl
Vertical creepers as per landscaping specialist
330mm retaining wall to Engineers detail Existing landscaping behind
Bulkhead and ceiling as per specialist
Surface bed Dpc FILL Dpc 120mm thick concrete surface bed with Ref 193 steel mesh on 50mm thick high density polystyrene on New Foundations damproof course layer on sand to Engineers detail 1m high SANS approved glass balustrade (by specialist) Existing 110mmØ uPVC soil pipe min. 1:60 (max. 1:10) to remain unaffected (To connect to Septic Tank as per specialist detail & specifications)
SECTION B-B
2750
2410
11
12
Dpc 10 U/s slab @ 2720mm afsl 9 Tiles 8 330x330mm Aircon by Specialist 7 concrete column W 6 to Engineers detail 5 3 New Floating concrete 4 3 staircase to specialist detail 2 Treads: 300mm -170 1 Risers: 170mm
Dpc NGL
New Foundations to Engineers detail
2210 510
220X400mm concrete beam to Engineers detail
2720
2720 Landscaping as per specialist
-170
18 17 16 15 14 13
2410
5440
W 2
Existing wc behind
Surface bed Dpc 170mm thick concrete surface bed with Ref 193 steel mesh on New Foundations damproof course layer on sand. New Foundations to Engineers detail to Engineers detail
400
170
Dpc
2720
U/s Ceiling to Rafter W Tiles W 21 3675 22 Aircon by Specialist
7430
5440
2320
D 10
Dpc 304x76mm timber beam to Engineers detail
150x150 CFLC steel gutters to Engineers detail & specifications
Dpc
85
-680
Waterproofing as per specialist
-170
23°
Roof fascia board as per specialist specifications as per manufacturer.
20°
PASSAGE 1
Vertical Dpc
220mmbrick wall to Engineers detail
Landscaping as per specialist
Stainless steel water spillover by specialist
Water feature - 6m 2
W 23
NEW STAIRCASE LOBBY
Vertical Dpc
Vertical Dpc
NGL
Vertical Dpc
NGL
0
Galvanized 50x50mm SHS panels. waterproofing by specialsit
Dpc
Vertical Dpc
0
2720
Vertical Dpc
2240
Existing wall to remain unaffected
680
330x330mm concrete column to Engineers detail
1590
Landscaping as per specialist
Dpc 4333
2950
New opening in existing wall to Engineers detail Lintel height @ 2720mm.Existing window to be removed 2550
960
Vertical Dpc
GROUND STOREY
100
Existing RWDP to be cut back. Rainwater to discharge onto 170mm concrete slab to Engineers detail
New 170mm concrete slab to Engineers detail
Timber slated fence by specialist 2.0m high Boundary wall from NGL.220mm brick wall & clearvu fence above to Engineers details & specifications.
2550
2720 2750
1590
Existing wall to be platered & painted
Flashing/ waterproofing by specialist
Planter-concrete below Waterproofing as per specialist
5950
330x510mm concrete beam to Engineers detail
2550
3049
510
FIRST STOREY
New RWDP as per specialist specifications as per manufacturer. 2520
Green square modular plastic tray planter boxes as per specialist. Irrigation system required to be confirmed by specialist
20°
1960 5301
Roof fascia board as per specialist specifications as per manufacturer. Planter-no concrete Waterproofing as per specialist
°
5270
45
Existing rainwater gutters to remain unaffected
WALL PLATE
45°
Concrete Roof Tiles (73m2) Concrete Roof Tiles as per specialist @ 20° & 45°.On 75x50mm purlins to Engineers detail. on 50x150mm timber rafters to Engineers specifications. Waterproofing by specialist
45°
Concrete Roof Tiles (16m2) Concrete Roof Tiles as per specialist @ 20° & 45°.On 75x50mm purlins to Engineers detail. on 50x150mm timber rafters to Engineers specifications. Waterproofing by specialist
°
7260
Ceiling to underside of rafters 150mm Mineral fibre insulation between rafters
45
ROOF LEVEL
New Steel sheet surround panel as per specialist Planter-concrete below Waterproofing as per specialist
New Proposed Residence for (ANDILE ZULU)
20°
Roof pebbles as per specialist Waterproofing by specialist
Dpc New Foundations to Engineers detail New Foundations to Engineers detail
Galvanized 50x50mm SHS panels. waterproofing by specialsit Precast Rectangular Column with Multi Layer Corbels to Engineers detail Gas fire place to specialist detail and specialist position
NGL
2.0m high Boundary wall from NGL. 220mm brick wall as per Engineers details & specifications. Plastered & painted
T +27 (0)67 296 4386 E levizdesignz@outlook.com www.levizdesigns.com
Raised platform to Engineers detail & specifications New Foundations to Engineers detail
Project status:
WORKING DRAWINGS
SECTION A-A & B-B
Issue date:
1/6/2023 3:29:04 AM
Clients Signature Engineers Signature & Reg No. Architect Signature & Reg No. Scale:
1 : 50
Project number:
P10 Drawn by:
Checked by:
Drawing number:
DO
JW
WD 301
REV
Copyright of these drawings are prohibited and may not be copied without the consent of Leviz Designs. Copyright 2022