UCLA LOS ANGELES, CA CEE 141
Westwood Nanoelectronics Laboratory
Structural Calculation Report 12/09/2023 Kevin Ho, 405535877 Connor Achziger, 105919674 Colby Martin Brown, 005613235 Jake Mumford, 805486785
Table of Contents Page 1. Loading Criteria
2
2. Column Load Tabulations
4
2.1. Loading
4
2.2. Tributary Area
4
2.3. Live Load Reductions
7
2.4. LRFD Load Combinations
7
3. Column Design
9
3.1. Splice Locations
9
3.2. Effective Lengths
10
3.3. Column Selection
10
4. Beam and Girder Design
12
4.1. Beam Layout Study
12
4.2. Roof Framing
17
4.3. Typical Floor Beams and Girders
31
4.4. Floor 2 Beams and Girders
43
5. Connection Design
60
5.1. Typical Beam to Girder Connection at Roof Level
60
5.2. Typical Girder to Column Connection at Office Level
61
6. Secondary Steel β Wind Girt Design
62
6.1. Layout
62
6.2. Loading
63
6.3. Final HSS Design
63
6.4. D-3 Column Check
66
7. Steel Member take-off and cost estimate
69
7.1. Columns
69
7.2 Beams
70
7.3 Girders
71
7.4 Wind Girt
71
7.5 Total Cost
71
1. Loading Criteria Table 1.1. Typical Floor Dead and Live Load Tabulations Typical Floor and Floor 2 Dead Load
Load (psf)
3 ΒΌβ LWC over 3" Deck (18-GA)
49.7
MEP
10
Ceiling/Lights
4
Flooring/Misc.
5
Slab Total
68.7
Gravity Beam
4
Beam Total
72.7
Gravity Girder
4
Girder Total
76.7
Gravity Column
2
Column Total
78.7
Typical Floor Live Loads
Load (psf)
Office Occupancy (reducible)
50
Partitions
15
Floor 2 Live Loads
Load (psf)
Light Manufacturing (reducible, max 80%)
125
Partitions (Not required when the minimum specified load is greater than 80 psf)
0
2
Table 1.2. Roof Dead and Live Load Tabulations Roof Dead Load
Load (psf)
Bare Metal Deck (20-GA; N-24)
3
MEP
10
Ceiling/Lights
4
Flooring/Misc.
5
Roofing
10
Slab Total
32
Gravity Beam
4
Beam Total
36
Gravity Girder
4
Girder Total
40
Gravity Column
2
Column Total
42
Typical Floor Live Loads
Load (psf)
Flat Roof (reducible)
20
Partitions (none on the roof)
0
3
2. Column Load Tabulation 2.1. Loading Table 2.1.1. Dead and Unreduced Live Loading (excluding partitions) by Floor Dead Load (psf)
Live Load (psf)
Roof
42
20
Floor 6
78.7
50
Floor 5
78.7
50
Floor 4
78.7
50
Floor 3
78.7
50
Floor 2
78.7
125
2.2. Tributary Area 2.2.1. Floor Tributary Area The floor tributary area for a column is calculated by finding the area of the slab that the column takes load. Using the tributary width and length, we can easily multiply to get the tributary area of a column. Some conditions to consider are the slab overhang and the differing tributary dimensions. Typical E-W Edge = πππππ’π‘πππ¦ ππππ‘β β (πππππ’π‘πππ¦ πΏππππ‘β + ππ£ππβπππ) 36'
= 24' β ( 2 + 1') 2
= 456 ππ‘
Typical N-S Edge = πππππ’π‘πππ¦ ππππ‘β β (πππππ’π‘πππ¦ πΏππππ‘β/2 + ππ£ππβπππ) 24'
= 36' β ( 2 + 1') 2
= 468 ππ‘
4
Typical Corner = (πππππ’π‘πππ¦ ππππ‘β/2 + ππ£ππβπππ) β (πππππ’π‘πππ¦ πΏππππ‘β/2 + ππ£ππβπππ) 36'
24'
= ( 2 + 1') β ( 2 + 1') 2
= 247 ππ‘
Typical Interior = πππππ’π‘πππ¦ ππππ‘β β πππππ’π‘πππ¦ πΏππππ‘β = 36' β 24' 2
= 864 ππ‘
Typical Interior = πππππ’π‘πππ¦ ππππ‘β β πππππ’π‘πππ¦ πΏππππ‘β = 36' β 24' 2
= 864 ππ‘ Floor 2 C-2, C-4
= ππ¦πππππ πΌππ‘πππππ β (πππππ’π‘πππ¦ ππππ‘β/2 β ππ£ππβπππ) β (πππππ’π‘πππ¦ πΏππππ‘β/2 β ππ£ππβπππ) 2
24'
36'
= 864 ππ‘ β ( 2 β 1) β ( 2 + 1') 2
= 655 ππ‘
Floor 2 C-3 (see Typical E-W Edge) 2
= 456 ππ‘
Floor 2 D-2, D-4 (see Typical Corner) 2
= 247 ππ‘ Floor 2 D-3 2
= 0 ππ‘
2.2.2. Exterior Wall Tributary Area Roof Tributary Height = πππππππ‘ + ππππ π»πππβπ‘ ππππ π πππ π‘π πΉππππ 6 / 2 = 5' +
13' 2
= 11. 5'
5
Floor Tributary Height Example (Floor 6) = ππππ π»πππβπ‘ ππππ π πππ π‘π πΉππππ 6 / 2 + ππππ π»πππβπ‘ ππππ πΉππππ 5 π‘π πΉππππ 6 / 2
=
13' 2
+
13' 2
= 13' Exterior Wall Tributary Area Example (Floor 6 on N-S Wall) = πππππ’π‘πππ¦ ππππ‘β β πππππ’π‘πππ¦ πΏππππ‘β = 24' β 13' 2
= 312 ππ‘ *The N-S wall uses a tributary width of 24β and the E-W wall uses a tributary width of 36β Table 2.2.2.1. N-S Exterior Wall Tributary Area Tabulation (Tributary Width = 24β) N-S Wall
Tributary Height (feet)
Tributary Area (ft^2)
Roof
11.5
276
Level 6
13
312
Level 5
13
312
Level 4
13
312
Level 3
16.5
396
Level 2
19
456
Table 2.2.2.2. E-W Exterior Wall Tributary Area Tabulation (Tributary Width = 36β) E-W Wall
Tributary Height (feet)
Tributary Area (ft^2)
Roof
11.5
414
Level 6
13
468
Level 5
13
468
Level 4
13
468
Level 3
16.5
594
Level 2
19
684
6
2.3. Live Load Reductions For floor live load reduction, we used ACSE-7 Eq. 3.7-1. The reduction is limited to 40% of the original value for floors supporting more than one floor and 50% for floors supporting one floor. The tributary area used includes the tributary area of the above floors excluding the roof. For roof live load reduction, we used ACSE-7 Eq. 4.8-1. The minimum reduced roof live load is 12 psf. Roof Live Load Reduction Example (A-3) = πΏ0π 1π 2 = πΏ0 β (1. 2 β 0. 001(π΄π)) β 1 = 50 β (1. 2 β 0. 001(456)) β 1 = 50 β 0. 744 β 1 = 14. 88 ππ π Floor 4 Live Load Reduction Example (A-3) =πΏ (0. 25 + 0
=50(0. 25 +
15 πΎπΏπΏπ΄π
)
15 4β1368
)
=50(0. 45) =22. 6 ππ π The second floor has a special condition according to ASCE-7 4.7.3 that limits the maximum live load reduction factor to be 80%.
2.4. LRFD Load Combinations Now that we have the tributary wall area and, the tributary floor area, dead loads, and reduced live loads, we can use the LRFD Load Combinations 1.4D and 1.2D+1.6L to calculate the load transferred from each floor to the column. Roof LRFD Example (A-3) 2
2
2
2
1.4D = 1. 4(42ππ π β 456ππ‘ + 15ππ π β 276ππ‘ )/1000 = 32. 6 ππππ 2
1. 2π· + 1. 6πΏ = [1. 2(42ππ π β 456ππ‘ + 15ππ π β 276ππ‘ ) + 1. 6(14. 9ππ π * 456ππ‘ )]/1000 = 38. 8 ππππ
7
Table 2.4. Sum of Factored Loads At Each Floor Columns
Roof (Kips)
Floor 6 (Kips)
Floor 5 (Kips)
Floor 4 (Kips)
Floor 3 (Kips)
Floor 2 (Kips)
A-2/A-3/A-4 (North Edge)
38.8
120.4
198.2
274.3
351.0
475.2
B-1/B-5/C-1/C-5 (East/West Edge)
42.0
128.2
210.6
291.3
373.3
504.7
A-1/A-5/D-1/D-5 (Corners)
26.2
80.7
131.4
180.3
230.1
303.2
B-2/B-3/B-4 (Typ. Interior)
60.1
136.9
264.1
389.9
519.9
1272.0
D-2/D-4
38.8
120.4
198.2
274.3
351.0
422.0
D-3
38.8
120.4
198.2
274.3
351.0
359.2
C-2/C-4
33.8
109.8
182.0
252.5
322.0
409.0
C-3
33.8
109.8
182.0
252.5
322.0
380.0
8
3. Column Design 3.1. Splice Locations Maximum column length is 43', so column splices were introduced in each column. Column splices were placed 4 to 5 feet above the floor heights to avoid points of maximum moment and for ease of construction.
3.2. Effective Lengths Effective length was calculated between each floor with each floor having a K factor. The roof and base sections were idealized to pin to fixed connections and the other sections were idealized to fixed to fixed connections. The recommended value was used rather than the theoretical value for the K factor. Table 3.2.1. Typical Effective Length Tabulation Height Section
K factor
Length (ft)
Effective Length (ft)
6-R
1
13
13
5-6
1
13
13
4-5
1
13
13
3-4
1
13
13
2-3
1
20
20
1-2
1
18
18
3.3. Column Selection With the effective lengths and load transfer from each floor to the column, we can use AISC Table 4-1 to design the columns. All columns that are spliced together are selected to have the same depth.
Table 3.3.1. Column Selection and Capacities for all Columns
9
Columns
Top Section
KL Capacity (ft) (Kips)
Middle Section
KL (ft)
Capacity (Kips)
Bottom Section
KL Capacity (ft) (Kips)
A-2/A-3/A-4 (North Edge)
W8x31
13
266
W12x53
20
354
W12x65
18
591
B-1/B-5/C-1/C-5 (East/West Edge)
W8x31
13
266
W10x54
20
374
W12x65
18
591
A-1/A-5/D-1/D-5 (Corners)
W8x31
13
266
W8x48
20
239
W10x49
18
382
B-2/B-3/B-4 (Typ. Interior)
W8x31
13
266
W12x65
20
542
W14x132
18
1370
D-2/D-4
W8x31
13
266
W12x53
20
354
W12x58
18
445
D-3*
W8x31*
13
266
W12x53*
20
403
W12x53*
38
403
C-2/C-4
W8x31
13
266
W10x49
20
337
W10x54
18
422
C-3
W8x31
13
266
W10x49
20
337
W10x49
18
382
* D-3 Subject to change after wind girt calculation
4. Beam and Girder Design 4.1. Beam Layout Study 4.1.1. Loading Using the loading criteria calculated in Table 1.1., we can calculate the reduced live load for the typical interior bay. The reduced live load will be different from the reduced live load for the columns because the beams and girders will have a different KLL factor. In our case, the KLL for all the beams and girders will be 2. Table 4.1.1.1. Typical Beam Dead and Live Load Tabulations
Long Length (36β) Floor
10
Dead Load (psf)
71.7
Live Load, Unreduced (psf)
50
Live Load, Reduced + Partition (psf)
58.75
Short Length (24β) Floor Dead Load (psf)
71.7
Live Load, Unreduced (psf)
50
Live Load, Reduced + Partition (psf)
63.6
4.1.2. Typical Interior Bay 4.1.2.1. Typical Interior Beam Calculations for the design of the typical interior beam members. The maximum moment and shear are calculated using the loading in Table 4.1.1.1. as distributed loads and a beam size is selected per Table 3-2. Deflection is calculated using the selected beam and is reiterated if needed. 4.1.2.2. Typical Interior Girder The beams apply point loads on the girders which are calculated using the loading in Table 4.1.1.1 and the girderβs tributary width. Then the same procedure as the typical interior beam occurs, where the maximum moment and shear are calculated, beam size is selected, and deflection is checked.
4.1.3. Final Interior Bay Design
11
The final interior bay design selected was that of the long length (36β). The long length design provided the necessary support from the typical interior beams and girders while maintaining the least amount of self-weight.
4.2. Roof Framing 4.2.1. Loading Using the loading criteria calculated in Increment 1, we are able to calculate the reduced live load for the roof. Table 4.2.1.1. Dead and Live Loads on the Roof Frame Roof Dead Load (psf)
42
Live Load, Unreduced (psf)
20
Live Load, Reduced (psf)
18.24
4.2.2. Roof Members 4.2.2.1. Typical Interior Roof Beam The maximum moment and shear are calculated using the loading in Table 4.2.1.1 as distributed loads and a beam size is selected per AISC Table 3-2a. Deflection is calculated using the selected beam and is reiterated if needed. 4.2.2.2. Typical Interior Roof Girder The beams apply point loads on the girders which are calculated using the loading in Table 4.2.1.1 and the girderβs tributary width. Then the same procedure as the roof beam occurs, where the maximum moment and shear are calculated, beam size is selected, and deflection is checked. 4.2.2.3. Exterior Beam The exterior beam is calculated in the same way as the typical interior roof beam, but now there is an exterior wall on the beam and the beam has a smaller tributary width. 4.2.2.4. Exterior Girder
12
The exterior girder is calculated in the same way as the typical interior roof girder, but now there is an exterior wall on the girder and the girder has fewer beams connecting to the girder, which can also be seen as the girder has a smaller tributary width.
4.2.3. Final Roof Frame Design Table 4.2.3.1. Final Roof Frame Design WF Size Typical Interior Beam
W16x31
Typical Interior Girder
W18x35
Exterior Beam
W16x31
Exterior Girder
W18x35
4.2.3.1 Roof Framing Calculations Beam
ππ€ = 1. 2π·πΏ + 1. 6πΏπΏ 2
π΄π = 8 ππ‘ * 36 ππ‘ = 288 ππ‘
13
2
π 1 = 1. 2 β 0. 001π΄π = 1. 2 β 0. 001(288ππ‘ ) = 0. 912 π 2 = 1 πΏπ = πΏ0π 1π 2 = 20 πππΉ * 0. 912 * 1 = 18. 24 πππΉ π·πΏ = 42 πππΉ ππ€ = 1. 2(42 πππΉ * 8 ππ‘) + 1. 6(18. 24 πππΉ * 8ππ‘) = 636. 67 ππΏπΉ 2
ππππ₯ =
ππ€πΏ 8
2
=
(636.67 ππΏπΉ)(36 ππ‘) 8
= 103. 14 πΎππ Β· ππ‘
AISC Table 3-2 Select W16x31
Οππππ₯ = 203 πΎππ Β· ππ‘ Οππππ₯ β₯ ππππ₯
OK
Shear
Οπ£πππ₯ = 131 πΎπππ ππππ₯ = ππ€πΏ/2 = (636. 67 ππΏπΉ)(36 ππ‘)/2 = 11. 46 πΎππ Οπ£πππ₯ β₯ ππππ₯
OK
Deflection LL only: 4
5π€πΏ 384πΈπΌ
π€ =
πΏ
β€ 360
18.24 πππΉ *8 ππ‘*1 πΎππ 12 ππ *1000 ππ
= 0. 01216 πΎππ/ππ 4
5(0.01216 πΎππ/ππ)(36 ππ‘* 12ππ/ππ‘)
β€
4
384(29000 πΎππΌ)(375 ππ )
36 ππ‘* 12ππ/ππ‘ 360
0. 507" β€ 1. 2" OK LL + DL: 4
5π€πΏ 384πΈπΌ
π€ =
πΏ
β€ 240
(18.24+42 πππΉ) *8 ππ‘*1 πΎππ 12 ππ *1000 ππ
14
= 0. 04016 πΎππ/ππ
4
5(0.04016 πΎππ/ππ)(36 ππ‘* 12ππ/ππ‘) 4
384(29000 πΎππΌ)(510 ππ )
β€
36 ππ‘* 12ππ/ππ‘ 240
1. 675" β€ 1. 8" OK Girder
ππ’ =
636.67 ππΏπΉ*36 ππ‘ 1000
= 22. 92 πΎπππ
ππππ₯ = ππ = 22. 92 πΎπππ * 8 ππ‘ = 183. 36 πΎππ Β· ππ‘ πΏπ = 8ππ‘ πΆπ = 1. 00 AISC Table 3-10 Select W18x35 AISC Table 3-2
Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 0)[249 πΎπππ β 12. 3(8 ππ‘ β 4. 31 ππ‘)] β€ 249 πΎπππ 203. 613 πΎπππ β€ 249 πΎπππ ππππ₯ β€ 203. 613 πΎπππ OK Shear
Οπ£πππ₯ = 159 πΎπππ
15
ππππ₯ = ππ’ = 22. 92 πΎπππ Οπ£πππ₯ β₯ ππππ₯
OK
Deflection LL only: 3
23ππ 648πΈπΌ
π=
πΏ
β€ 360
18.24 πππΉ *8 ππ‘*36ππ‘ *1 πΎππ 1000 ππ
= 5. 25 πΎπππ
3
23(5.25 πΎππ)(24ππ‘* 12ππ/ππ‘)
β€
4
648(29000 πΎππΌ)(510 ππ )
0. 30" β€ 0. 8"
24ππ‘* 12ππ/ππ‘ 360
OK
LL+DL: 3
23ππ 648πΈπΌ
π=
πΏ
β€ 240
(18.24+42 πππΉ) *8 ππ‘*36ππ‘ *1 πΎππ 1000 ππ 3
23(17.35 πΎππ)(24ππ‘* 12ππ/ππ‘) 4
648(29000 πΎππΌ)(510 ππ )
1. 00" β€ 1. 2"
β€
= 17. 35 πΎπππ 24ππ‘* 12ππ/ππ‘ 240
OK
Beam I
ππ€ = 1. 2π·πΏ + 1. 6πΏπΏ π·πΏ = 42 πππΉ + πΈπ₯π‘πππππ πππππ 2
π΄π = 36 ππ‘ * 5 ππ‘ = 180 ππ‘ π 1 = 1 π 2 = 1
πΏπ = πΏ0π 1π 2 = 20 πππΉ * 1 * 1 = 20 πππΉ π·πΏ = (42 πππΉ * 5 πΉπ) + (15 πππΉ * 11. 5 ππ‘) = 382. 5 ππΏπΉ 16
πΏπΏ = 20 πππΉ * 5 ππ‘ = 100 ππΏπΉ ππ€ = 1. 2(382. 5 ππΏπΉ) + 1. 6(100 ππΏπΉ) = 619 ππΏπΉ 2
ππππ₯ =
ππ€πΏ 8
2
=
(619 ππΏπΉ)(36 ππ‘) 8
= 100. 278 πΎππ Β· ππ‘
AISC Table 3-2 Select W16x31
Οππππ₯ = 203 πΎππ Β· ππ‘ Οππππ₯ β₯ ππππ₯
OK
Shear
Οπ£πππ₯ = 131 πΎπππ ππππ₯ = ππ€πΏ/2 = (619 ππΏπΉ)(36 ππ‘)/2 = 11. 142 πΎππ Οπ£πππ₯ β₯ ππππ₯
OK
Deflection LL only: 4
5π€πΏ 384πΈπΌ
π€ =
β€ 3/8"
20 πππΉ *5ππ‘*1 πΎππ 12 ππ *1000 ππ
= 0. 0083 πΎππ/ππ 4
5(0.0083 πΎππ/ππ)(36 ππ‘* 12ππ/ππ‘) 4
384(29000 πΎππΌ)(375 ππ )
β€
36 ππ‘* 12ππ/ππ‘ 360
0. 347" β€ 0. 375" OK LL + DL: 4
5π€πΏ 384πΈπΌ
π€ =
πΏ
β€ 240
(382.5+100 ππΏπΉ) *1 πΎππ 12 ππ *1000 ππ
= 0. 0402 πΎππ/ππ
4
5(0.0402 πΎππ/ππ)(36 ππ‘* 12ππ/ππ‘) 4
384(29000 πΎππΌ)(510 ππ )
β€
36 ππ‘* 12ππ/ππ‘ 240
1. 676" β€ 1. 8" OK 17
Beam II
ππ€ = 1. 2π·πΏ + 1. 6πΏπΏ π·πΏ = 42 πππΉ 2
π΄π = 36 ππ‘ * 8 ππ‘ = 288 ππ‘
π 1 = 1. 2 β 0. 001π΄π = 1. 2 β 0. 001(288) = 0. 912 π 2 = 1 πΏπ = πΏ0π 1π 2 = 20 πππΉ * 0. 912 * 1 = 18. 24 πππΉ ππ€ = 1. 2(42 πππΉ * 8 ππ‘) + 1. 6(18. 24 πππΉ * 8ππ‘) = 636. 67 ππΏπΉ 2
ππππ₯ =
ππ€πΏ 8
2
=
(636.67 ππΏπΉ)(36 ππ‘) 8
= 103. 14 πΎππ Β· ππ‘
AISC Table 3-2 Select W16x31
Οππππ₯ = 203 πΎππ Β· ππ‘ Οππππ₯ β₯ ππππ₯
OK
Shear
Οπ£πππ₯ = 131 πΎπππ ππππ₯ = ππ€πΏ/2 = (636. 67 ππΏπΉ)(36 ππ‘)/2 = 11. 46 πΎππ Οπ£πππ₯ β₯ ππππ₯
OK
Deflection LL only: 4
5π€πΏ 384πΈπΌ
π€ =
πΏ
β€ 360
18.24 πππΉ *8 ππ‘*1 πΎππ 12 ππ *1000 ππ
= 0. 01216 πΎππ/ππ 4
5(0.01216 πΎππ/ππ)(36 ππ‘* 12ππ/ππ‘) 4
384(29000 πΎππΌ)(375 ππ )
β€
36 ππ‘* 12ππ/ππ‘ 360
0. 507" β€ 1. 2" OK LL + DL:
18
4
5π€πΏ 384πΈπΌ
π€ =
πΏ
β€ 240
(18.24+42 πππΉ) *8 ππ‘*1 πΎππ 12 ππ *1000 ππ
= 0. 04016 πΎππ/ππ
4
5(0.04016 πΎππ/ππ)(36 ππ‘* 12ππ/ππ‘) 4
384(29000 πΎππΌ)(510 ππ )
β€
36 ππ‘* 12ππ/ππ‘ 240
1. 675" β€ 1. 8" OK Perimeter Girder
ππ€ = 1. 4(15 πππΉ * 11. 5 ππ‘) = 241. 5 ππΏπΉ ππ’ =
636.67 ππΏπΉ*36 ππ‘ 1000
= 22. 92 πΎπππ
2
ππππ₯ = ππ +
π€πΏ 8
2
= (22. 92 πΎπππ * 8 ππ‘) +
241.5 ππΏπΉ*24ππ‘ 8
= 200. 75 πΎππ Β· ππ‘
πΏπ = 8ππ‘ πΆπ = 1. 00 AISC Table 3-10 AISC Table 3-2
Select W18x35
Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 0)[249 πΎπππ β 12. 3(8 ππ‘ β 4. 31 ππ‘)] β€ 249 πΎπππ 203. 613 πΎπππ β€ 249 πΎπππ ππππ₯ β€ 203. 613 πΎπππ OK Shear
Οπ£πππ₯ = 159 πΎπππ 241.5 ππΏπΉ(24 ππ‘) πΎπππ = 2000
ππππ₯ = ππ’ + π€πΏ/2 = 22. 92 πΎπππ + Οπ£πππ₯ β₯ ππππ₯
OK
Deflection LL only: 3
23ππ 648πΈπΌ
4
5π€πΏ
+ 384πΈπΌ β€ 3/8" 19
25. 818 πΎπππ
π =
18.24 πππΉ *8 ππ‘*36ππ‘ *1 πΎππ 1000 ππ
= 5. 25 πΎπππ
3
23(5.25 πΎππ)(24ππ‘* 12ππ/ππ‘) 4
648(29000 πΎππΌ)(510 ππ )
+ 0β€
0. 30" β€ 0. 375"
24ππ‘* 12ππ/ππ‘ 360
OK
LL+DL: 3
23ππ 648πΈπΌ
π =
4
+
5π€πΏ 384πΈπΌ
πΏ
β€ 240
(18.24+42 πππΉ) *8 ππ‘*36ππ‘ *1 πΎππ 1000 ππ
= 17. 35 πΎπππ
π€ = 241. 5 ππΏπΉ * 1/1000 πΎππ * 1/12 ππ 3
23(17.35 πΎππ)(24ππ‘* 12ππ/ππ‘) 4
648(29000 πΎππΌ)(510 ππ )
β1
= 0. 0201 πΎππ/ππ 4
+
5(0.0201 πΎππ/ππ)(24ππ‘* 12ππ/ππ‘) 4
384(29000 πΎππΌ)(510 ππ )
1. 00" + 0. 12" = 1. 12" β€ 1. 2"
20
β€
OK
24ππ‘* 12ππ/ππ‘ 240
4.3. Typical Floor Beams and Girders Figure 4.3.1. Layout Table 4.3.1.1. Loading Criteria for Typical Floor Typical Floor
Loading (PSF)
Composite Beam and Slab Self Weight
53.7
Superimposed Dead Load
19
Exterior Wall
15
Construction Live Load
20
Post Composite Live Load
50
Reduced Post Composite Live Load (Interior Beam)
38
Reduced Post Composite Live Load (Exterior Beam)
45.9
Reduced Post Composite Live Load (Interior Girder)
38.02
Reduced Post Composite Live Load (Exterior Girder)
50
Partitions
15
Table 4.3.1.2. Final Beam and Girder Design WF Size
Studs
Interior Beam
W16x31 <1.5β>
40
Interior Girder
W16x40
36
Exterior Beam
W18x40
72
Exterior Girder
W16x31
24
4.3.3. Typical Floor Girder Calculations Girders
21
Interior 2
π΄π = 12ππ‘ * 36 ππ‘ = 432 ππ‘ Pre-composite
ππ π€ = ππ πππ + πππππ + πππππ = 49. 7 πππΉ + 8 πππΉ = 57. 7 πππΉ ππΏπΏ, πΆπππ π‘ππ’ππ‘πππ = 20 πππΉ Post Composite
ππ·πΏ = ππ π€ + πππΌπ·πΏ = 57. 7 πππΉ + 19 πππΉ = 76. 7 πππΉ ππΏπΏ = 50 πππΉ * (0. 25 + 0
15 πΎπΏπΏπ΄π
) = 50 πππΉ * (0. 25 +
15
ππΏπΏ = 38. 02 πππΉ + 15 πππΉ = 53. 02 πππΉ Pre-composite strength
ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ ππ’ = (1. 2(57. 7 πππΉ * 12 ππ‘) + 1. 6(20 πππΉ * 12 ππ‘)) * 36 ππ‘ ππ’ = 43736 πππ = 43. 7 πΎπππ ππππ₯ =
ππΏ 4
=
43.7 πΎπππ * 24 ππ‘ 4
2
2*432 ππ‘
= 262. 41 πΎππ Β· ππ‘
πΏπ = 12ππ‘ πΆπ = 1. 67 22
) = 38. 02 πππΉ
AISC Table 3-2 Select W16x40
Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 67)[274 πΎπππ β 10(12 ππ‘ β 5. 55 ππ‘)] β€ 274 πΎπππ 349. 86 β₯ 274 πΎπππ Οππππ₯ = 274 πΎπππ Οππππ₯ β₯ ππππ₯ π = (57. 7 πππΉ * 12 ππ‘) * 36 ππ‘ = 24. 92 πΎπππ 3
βππ =
ππΏ 48πΈπΌ
3
24.92 πΎπππ *(24*12 ππ)
=
4
48(29000 πΎππΌ)(518 ππ )
= 0. 83"
Camber
0. 8(0. 83") = 0. 66" NO CAMBER Post Composite Strength
ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ ππ’ = (1. 2(76. 7 πππΉ * 12 ππ‘) + 1. 6(45. 54 πππΉ * 12 ππ‘)) * 36 ππ‘ ππ’ = 71. 24 πΎπππ ππππ₯ =
ππΏ 4
71.24 πΎπππ * 24 ππ‘ 4
=
= 427. 43 πΎππ Β· ππ‘
1 stud/ft
Ξ£ππ = 24/2 * (17. 1 πΎπππ ) = 205. 2 πΎπππ πΏ
π
ππππ = 2 * πππ( 8 , 20 ) = 2 * πππ( π=
Ξ£ππ 0.85ππ'ππππ
=
205.2 πΎπππ 0.85(3πΎππΌ)(72ππ)
π
π2 = π‘ β 2 = 6. 25" β
1.12 ππ 2
24 ππ‘ , 8
36 ππ‘ ) 2
= 72 ππ
= 1. 12 ππ = 5. 69 ππ β π2 = 5. 5"
AISC Table 3-18 Use Ξ£π = 192 πΎπππ , π = 5. 5" π
2
Οπππ = 423 πΎππ Β· ππ‘ Οπππ β€ ππππ₯ Try 1.5 stud/ft Ξ£ππ = (24/2) * 1. 5 * (17. 1 πΎπππ ) = 307. 8 πΎπππ π=
Ξ£ππ 0.85ππ'ππππ
=
π
307.8 πΎπππ 0.85(3πΎππΌ)(72ππ)
π2 = π‘ β 2 = 6. 25" β
1.68 ππ 2
= 1. 68 ππ = 5. 41 ππ β π2 = 5"
AISC Table 3-18
23
Use Ξ£π = 237 πΎπππ , π = 5" π
2
Οπππ = 436 πΎππ Β· ππ‘ AISC Table 3-19 4
πΌπΏπ΅ = 1090 ππ
Check Deflection LL only:
π = 45. 54 πππΉ * 12 ππ‘ * 36 ππ‘ = 19. 67 πΎπππ 3
βπΏπΏ =
3
ππΏ 48πΈπΌ
=
19.67 πΎπππ *(24*12 ππ)
= 0. 31" β€
4
48(29000 πΎππΌ)(1090 ππ )
24*12 ππ 360
= 0. 8"
DL Post-Composite:
π = 19 πππΉ * 12ππ‘ * 36 ππ‘ = 8. 21 πΎπππ 3
βπ·πΏ, ππΆ =
ππΏ 48πΈπΌ
3
=
8.21 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(1090 ππ )
= 0. 13 "
Total Deflection
βπ·πΏ, ππΆ + βπΏπΏ + βππ = 0. 13 " + 0. 31" + 0. 70" βπππ‘ππ = 1. 14" β€
12*24 ππ 240
= 1. 2"
W16x40 w/ (36) studs Exterior
2
π΄π = 12ππ‘ * 36/2 ππ‘ = 216 ππ‘ Pre-composite
ππ π€ = ππ πππ + πππππ + πππππ = 49. 7 πππΉ + 8 πππΉ = 57. 7 πππΉ ππΏπΏ, πΆπππ π‘ππ’ππ‘πππ = 20 πππΉ 24
Post Composite
ππ·πΏ = ππ π€ + πππΌπ·πΏ = 57. 7 πππΉ + 19 πππΉ = 76. 7 πππΉ ππΏπΏ = 50 πππΉ * (0. 25 + 0
15
) = 50 πππΉ * (0. 25 +
πΎπΏπΏπ΄π
15 2
) = 63. 54 πππΉ β₯ 50
1*216 ππ‘
ππΏπΏ = 50 πππΉ 0
ππΏπΏ = 50 πππΉ + 15 πππΉ = 65 πππΉ ππ€ = 1. 2(15 πππΉ * 13 ππ‘) = 234 ππΏπΉ ππ‘ππ‘ππ = 234 ππΏπΉ + 1. 2(76. 7 πππΉ * 1 ππ‘) + 1. 6(50 πππΉ * 1 ππ‘) = 406. 04 ππΏπΉ Pre-composite strength
ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) *
πΏππππ 2
ππ’ = (1. 2(57. 7 πππΉ * 12 ππ‘) + 1. 6(20 πππΉ * 12 ππ‘)) * 18 ππ‘ ππ’ = 21865 πππ = 21. 87 πΎπππ ππππ₯ =
ππΏ 4
2
+
π€πΏ 8
=
21.87 πΎπππ * 24 ππ‘ 4
2
+
406.04 ππΏπΉ*(24ππ‘) 8000
= 131. 19 + 29. 23 πΎππ Β· ππ‘
ππππ₯ = 160. 42 πΎππ Β· ππ‘ πΏπ = 12ππ‘ πΆπ = 1. 67 AISC Table 3-2 Select W16x31
Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 67)[203 πΎπππ β 10. 3(12 ππ‘ β 4. 13 ππ‘)] β€ 166 πΎπππ 203. 63813 β₯ 203 πΎπππ Οππππ₯ = 203πΎπππ Οππππ₯ β₯ ππππ₯ π = 57. 7 πππΉ * 12 ππ‘ * 18 ππ‘ = 12. 46 πΎπππ 3
βππ =
ππΏ 48πΈπΌ
3
=
12.46 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(375 ππ )
= 0. 20"
NO CAMBER Post Composite Strength
ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ/2 ππ’ = (1. 2(76. 7 πππΉ * 12 ππ‘) + 1. 6(45. 54 πππΉ * 12 ππ‘)) * 18 ππ‘ ππ’ = 35. 62 πΎπππ
25
ππππ₯ =
2
ππΏ 4
+
π€πΏ 8
35.62 πΎπππ * 24 ππ‘ 4
=
2
+
406.04 ππΏπΉ*(24ππ‘) 8000
= 213. 72 + 29. 23 πΎππ Β· ππ‘
ππππ₯ = 242. 95 πππ Β· ππ‘ 1 stud/ft
Ξ£ππ = 24/2 * (17. 1 πΎπππ ) = 205. 2 πΎπππ π
πΏ
ππππ = 12" + πππ( 8 , 20 ) = 12" + πππ( π=
Ξ£ππ 0.85ππ'ππππ
205.2 πΎπππ 0.85(3πΎππΌ)(48ππ)
=
π
1.68 ππ 2
π2 = π‘ β 2 = 6. 25" β
24 ππ‘ , 8
36 ππ‘ ) 2
= 48 ππ
= 1. 68 ππ = 5. 41ππ β π2 = 5"
AISC Table 3-18 Use Ξ£π = 164 πΎπππ , π = 5" π
2
Οπππ = 325 πΎππ Β· ππ‘ Οπππ β₯ ππππ₯ OK AISC Table 3-19 4
πΌπΏπ΅ = 780 ππ
Check Deflection LL only:
π = 45. 54 πππΉ * 12 ππ‘ * 18 ππ‘ = 9. 835 πΎπππ 1 πΎππ
π€πΏ = 50 ππΏπΉ * 12000 ππ = 0. 0041 πΎππ/ππ 4
5π€πΏπΏ
3
βπΏπΏ =
ππΏ 48πΈπΌ
3
+ 384πΈπΌ =
4
9.835 πΎπππ *(24*12 ππ)
+
4
48(29000 πΎππΌ)(780ππ )
5*0.0041 πΎππ/ππ(24*12 ππ)
= 0. 23" β€ 3/8"
4
384(29000 πΎππΌ)(812 ππ )
DL Post-Composite:
π = 19 πππΉ * 12ππ‘ * 18 ππ‘ = 8. 21 πΎπππ 1 πΎππ
π€π· = (15 πππΉ * 13 ππ‘ + 76. 7ππΏπΉ) * 12000 ππ = 0. 023 πΎππ/ππ 4
3
βπ·πΏ, ππΆ =
ππΏ 48πΈπΌ
+
5π€π·πΏ
384πΈπΌ
3
=
8.21 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(812 ππ )
4
+
Total Deflection
βπ·πΏ, ππΆ + βπΏπΏ + βππ = 0. 30 " + 0. 23" + 0. 20" βπππ‘ππ = 0. 73" β€
12*24 ππ 240
= 1. 2"
OK
W16x31 w/ (24) studs
26
5*0.023 πΎππ/ππ(24*12 ππ) 4
384(29000 πΎππΌ)(812 ππ )
= 0. 30"
4.4. Floor 2 Beams and Girders Table 4.4.1. Loading Floor 2
Loading (PSF)
Composite Beam and Slab Self Weight
53.7
Superimposed Dead Load
19
Exterior Wall
15
Construction Live Load
20
Post Composite Live Load
125
Table 4.4.2. Final Beam and Girder Design WF Size
Studs
Interior Beam
W21x73
72
Interior Girder
W24x84
48
Exterior Beam
W33x152 <2 ΒΌβ>
100
Exterior Girder
W21x44
24
Special Beam
W16x31
24
Special Exterior Girder
W12x14
0
Special Girder
W21x44
24
4.4.3. Floor Members Using the loading criteria calculated in Increment 1, we are able to calculate the reduced live load for the floor. The reduced live load will be different from the reduced live load for the columns because the beams and girders will have a different KLL factor. In our case, the KLL for all the beams and girders will be 2. 4.4.4. Typical Interior Floor Beam
27
The maximum moment and shear are calculated using the loading in Table 4.4.1 as distributed loads, and a beam size is selected per AISC Table 3-2a. Deflection is calculated using the selected beam and is reiterated if needed. 4.4.5. Typical Interior Floor Girder The beams apply point loads on the girders which are calculated using the loading in Table 4.4.1 and the girderβs tributary width. Then the same procedure as the floor beam occurs, where the maximum moment and shear are calculated, beam size is selected, and deflection is checked. 4.4.6. Exterior Beam The exterior beam is calculated in the same way as the typical interior floor beam, but now there is an exterior wall on the beam and the beam has a smaller tributary width. 4.4.7. Exterior Girder The exterior girder is calculated in the same way as the typical interior floor girder, but now there is an exterior wall on the girder and the girder has fewer beams connecting to the girder, which can also be seen as the girder has a smaller tributary width. 4.4.8. Floor 2 Beam Calculations Lvl 2: Interior Beam (Longways Beam Orientation) π = 36ππ‘ 2
π΄π = 12ππ‘ Γ 36ππ‘ = 432ππ‘
Pre-Composite Loads & Deflections (DL & Construction LL) π·πΏ = π€ = π€π πππ + π€ππππ + π€ππππ = 53. 7ππ π π
πΏπΏ πΆπππ π‘ππ’ππ‘πππ = 20. 0 ππ π Pre-Composite Strength π€ = (1. 2π·πΏ + 1. 6πΏπΏ) Γ 12ππ‘ = 1157. 28 πππ 2
ππππ₯ =
π€π 8
2
=
1157.28 πππ Γ 36ππ‘ 8
= 187. 47 πππ Β· ππ‘
AISC Table 3-2 Select: W16x31 Οπππ = 203 πππ Β· ππ‘ β₯ ππππ₯ = 187. 47 πππ Β· ππ‘ 4
5π€π
βπππ₯ = 384πΈπΌ =
4
5Γ 1.157πππ Γ(36Γ12)
4
384Γ(29000ππ π)(375ππ )
= 2. 24ππ
Specify Camber
28
Camber: (0. 8) Γ 2. 24 = 1. 79 1.5β CAMBER Post-Composite Loads & Deflections π·πΏ = 72. 7 ππ π (Table 1.1) πΏπΏ = 125 Post-Composite Strength π€ = (1. 2π·πΏ + 1. 6πΏπΏ) Γ 12ππ‘ = 3. 45 πππ 2
2
π€π 8
ππππ₯ =
3.45 πππ *(36ππ‘) 8
=
= 558. 39 πππ Β· ππ‘
Determine Ξ£ππ (Assuming 1 stud per foot) Ξ£ππ = 18 Γ 17. 1π = 307. 8π πΏ
π
72
24
Determine ππππ = πππ( 8 , 20 ) = πππ( 8 , 2 ) = 9' Ξ£π
307.8π
π = 0.85π'ππ
= 0.85 Γ 3ππ π Γ (9ππ‘ π₯ 12ππ) = 1. 12ππ
π πππ
π
1.12 2
Determine π2 = π β 2 = 6. 25 β
= 5. 69ππ β π2 = 5"
AISC Table 3-19 Select: W18x46 Composite Οπππ β 565 πππ Β· ππ‘ > ππππ₯ = 558. 39 πππ Β· ππ‘ OK Post-Composite Deflection 4
πΌπΏπ΅ β 1550ππ
Add Studs as Required Ξ£ππ = 307. 8π 4
4
5π€π
βπΏπΏ = 384πΈπΌ =
5(125ππ π*12ππ‘)(36Γ12)
πΏ
= 1. 26 β₯ 720 = 0. 6
4
384(29000 ππ π) 9510ππ
4
4
5π€π
πΌπππ = 384πΈβ
=
5(125ππ π*12ππ‘)(36Γ12)
πΏπΏ
4
384(29000 ππ π)0.6ππ
= 3257. 87
Upsize to W21x62 788π
(94) π π‘π’ππ 36 ππ‘
=
(2.6) π π‘π’π 1 ππ‘
>
(2)π π‘π’ππ 1 ππ‘
NO
717π
(84) π π‘π’ππ 36 ππ‘
=
(2.3) π π‘π’π 1 ππ‘
>
(2)π π‘π’ππ 1 ππ‘
NO
614π
(72) π π‘π’ππ 36 ππ‘
=
(2) π π‘π’π 1 ππ‘
Ξ£π'π = 788π, π = 17.1π = 47 π π‘π’ππ , Upsize to W21x68 Ξ£π'π = 717π, π = 17.1π = 42 π π‘π’ππ , Upsize to W21x73 Ξ£π'π = 614π, π = 17.1π = 36 π π‘π’ππ , Use W21x73 w/ (72) Studs
29
=
(2)π π‘π’ππ 1 ππ‘
OK
Exterior Beam 2
π΄π = 7ππ‘ Γ 36ππ‘ = 252ππ‘
Pre-Composite Loads & Deflections (DL & Construction LL) π·πΏ = π€ = π€π πππ + π€ππππ + π€ππππ + π€π€πππ = 68. 7ππ π π
πΏπΏ πΆπππ π‘ππ’ππ‘πππ = 20. 0 ππ π Pre-Composite Strength (Laterally Supported) π€ = (1. 2π·πΏ + 1. 6πΏπΏ) Γ 7ππ‘ = 0. 801 πππ 2
π€π 8
ππππ₯ =
2
=
0.686πππ Γ 36ππ‘ 8
= 129. 77πππ Β· ππ‘
AISC Table 3-2 Select: W12x26 Οπππ = 140πππ Β· ππ‘ β₯ ππππ₯ = 129. 77 πππ Β· ππ‘ 4
4
5π€π
βπππ₯ = 384πΈπΌ =
5Γ0. 801πππ Γ(36Γ12)
4
384Γ(29000ππ π)(204ππ )
= 2. 95ππ
Specify Camber Camber: (0. 8) Γ 2. 95 = 2. 36, 2.25β CAMBER Post-Composite Loads & Deflections π·πΏ = 72. 7 ππ π + 19 ππ π = 87. 7 (Table 1.1) πΏπΏ = 125ππ π Post-Composite Strength π€ = (1. 2π·πΏ + 1. 6πΏπΏ) Γ 7ππ‘ = 2. 17 πππ 2
π€π 8
ππππ₯ =
2
=
2.17 πππ *(36ππ‘) 8
= 351. 58 πππ Β· ππ‘
Determine Ξ£ππ (Assuming 1 stud per foot) Ξ£ππ = 36 Γ 17. 1π = 615. 6π πΏ
π
72
24
Determine ππππ = πππ( 8 , 20 ) = πππ( 8 , 2 ) = 9ππ‘ = 108ππ Ξ£π
π = 0.85π'ππ
π πππ
615.6π
= 0.85 Γ 3ππ π Γ 108 = 2. 235ππ π
Determine π2 = π‘ β 2 = 6. 25" β
2.23" 2
= 5. 135ππ β π2 = 5"
AISC Table 3-19 Select: W14x26 Composite
30
Ξ£ππ = 385π Οπππ β 359πππ Β· ππ‘ > ππππ₯ = 351. 58 πππ Β· ππ‘ OK Post-Composite Deflection 4
πΌπΏπ΅ β 794ππ
Add Studs as Required 4
4
5π€π
βπΏπΏ = 384πΈπΌ =
5(2.17πππ)(36Γ12)
3
= 3. 561 β₯ 8
4
384(29000 ππ π)794ππ
4
4
5π€π
πΌπππ = 384πΈβ
=
πΏπΏ
4
5(125ππ π*36ππ‘)(36Γ12)
= 7540. 9 ππ
4
384(29000 ππ π) 0.375ππ
AISC Table 3-20 Select: W27x94 Composite 1190π
Ξ£π'π = 1190π, π = 17.1π = 70 π π‘π’ππ π₯ 2,
(140) π π‘π’ππ 36 ππ‘
>
(3)π π‘π’ππ 1 ππ‘
NOT OK
Upsize to W30x90 Composite 839π
Ξ£π'π = 839π, π = 17.1π = 50 π π‘π’ππ π₯ 2,
(100) π π‘π’ππ 36 ππ‘
<
(3)π π‘π’ππ 1 ππ‘
Use W33x152 Composite w/ (100) studs
Special Case (Adjacent to Artium) 2
π΄π = 6. 5ππ‘ Γ 36ππ‘ = 234ππ‘
Pre-Composite Loads & Deflections (DL & Construction LL) π·πΏ = π€ = π€π πππ + π€ππππ + π€ππππ = 53. 7ππ π π
πΏπΏ πΆπππ π‘ππ’ππ‘πππ = 20. 0 ππ π Pre-Composite Strength (Laterally Supported) π€ = (1. 2π·πΏ + 1. 6πΏπΏ) Γ 6. 5ππ‘ = 0. 6268 πππ 2
ππππ₯ =
π€π 8
2
=
0.686πππ Γ 36ππ‘ 8
= 101. 55 πππ Β· ππ‘
AISC Table 3-4 Select: W10x49 Οπππ = 106 πππ Β· ππ‘ β₯ ππππ₯ = 101. 55 πππ Β· ππ‘ 4
5π€π
βπππ₯ = 384πΈπΌ =
4
5 Γ 0.6268 πππΓ (36ππ‘Γ12) 4
384(29000 ππ π)272ππ
= 0. 5 ππ
Specify Camber NO CAMBER Post-Composite Loads & Deflections π·πΏ = 72. 7 ππ π (Table 1.1)
31
OK
πΏπΏ = 125 Post-Composite Strength π€ = (1. 2π·πΏ + 1. 6πΏπΏ) Γ 6. 5ππ‘ = 1. 867 πππ 2
π€π 8
ππππ₯ =
2
1.867 πππ *(36ππ‘) 8
=
= 302. 46 πππ Β· ππ‘
AISC Table 3-2 Select: W14x398 Determine Ξ£ππ (Assuming 1 stud per foot) Ξ£ππ = 36 Γ 17. 1π = 615. 6π πΏ
π
72
13
Determine ππππ = πππ( 8 , 20 ) = πππ( 8 , 2 ) = 7. 5ππ‘ = 90ππ Ξ£π
615.6π
π = 0.85π'ππ
π πππ
= 0.85 Γ 3ππ π Γ 90 = 2. 684ππ π
Determine π2 = π‘ β 2 = 6. 25" β
2.684" 2
= 5. 9ππ β π2 = 6. 0"
AISC Table 3-19 Select: W12x26 Composite Ξ£ππ = 321π Οπππ β 319 πππ Β· ππ‘ > ππππ₯ = 302. 46 πππ Β· ππ‘ OK Post-Composite Deflection 4
πΌπΏπ΅ β 715ππ
Add Studs as Required Ξ£ππ = 321π 4
4
5π€π
5(1.867πππ)(36Γ12)
βπΏπΏ = 384πΈπΌ =
πΏ
= 3. 40 β₯ 720 = 0. 6" Not OK
4
384(29000 ππ π) 715ππ
AISC Table 3-19 Select: W16x31 Composite 4
4
5π€π
πΌπππ = 384πΈβ
=
πΏπΏ
5(1.867πππ)*(36Γ12) 384(29000 ππ π)0.6 164π
= 337. 914 ππ
Ξ£π'π = 164, π = 17.1π = 10 π π‘π’ππ ,
(20) π π‘π’ππ 36 ππ‘
=
4 (1) π π‘π’π 8.30 ππ.
<
(2)π π‘π’ππ 1 ππ‘
Use W16 x 31 w/ (20) Studs 4.4.9. Floor 2 Girder Calculations Girder Interior 2
π΄π = 24ππ‘ * 36 ππ‘ = 864 ππ‘
Pre-Composite Loading ππ π€ = ππ πππ + πππππ + πππππππ = 49. 7 πππΉ + 8 πππΉ = 57. 7 πππΉ
32
OK
ππΏπΏ, πΆπππ π‘ππ’ππ‘πππ = 20 πππΉ Post-Composite Loading π·πΏ = ππ π€ + πππΌπ·πΏ = 57. 7 πππΉ + 19 πππΉ = 76. 7 πππΉ πΏπΏ = 125 Γ (0. 25 +
15
) = 125 Γ (0. 25 +
πΎπΏπΏπ΄π
15 2*864
) = 76. 36ππ π < 0. 8 Γ 150
πΏπΏ = 125 Γ 0. 8 = 100 πππΉ Pre-composite strength ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ ππ’ = (1. 2(57. 7 πππΉ * 12 ππ‘) + 1. 6(20 πππΉ * 12 ππ‘)) * 36 ππ‘ ππ’ = 43736 πππ = 43. 7 πΎπππ ππππ₯ =
ππΏ 4
43.7 πΎπππ * 24 ππ‘ 4
=
= 262. 41 πΎππ Β· ππ‘
πΏπ = 12ππ‘ πΆπ = 1. 67 AISC Table 3-2 Select W16x40 Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 67)[274 πΎπππ β 10(12 ππ‘ β 5. 55 ππ‘)] β€ 274 πΎπππ 349. 86 β₯ 274 πΎπππ Οππππ₯ = 274 πΎπππ Οππππ₯ β₯ ππππ₯ π = (57. 7 πππΉ * 12 ππ‘) * 36 ππ‘ = 24. 92 πΎπππ 3
βππ =
3
ππΏ 48πΈπΌ
=
24.92 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(518 ππ )
= 0. 83"
0. 8(0. 83") = 0. 66" NO CAMBER Post Composite Strength ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ ππ’ = (1. 2(76. 7 πππΉ * 12 ππ‘) + 1. 6(100 πππΉ * 12 ππ‘)) * 36 ππ‘ ππ’ = 108. 88 πΎπππ ππππ₯ =
ππΏ 4
=
108.88 πΎπππ * 24 ππ‘ 4
= 653. 28 πΎππ Β· ππ‘
1 stud/ft Ξ£ππ = 24/2 * (17. 1 πΎπππ ) = 205. 2 πΎπππ πΏ
π
ππππ = πππ( 8 , 20 ) = πππ(
24 ππ‘ , 8
36 ππ‘ ) 2
= 36 ππ
33
π=
Ξ£ππ
=
0.85ππ'ππππ
205.2 πΎπππ 0.85(3πΎππΌ)(36ππ)
π
π2 = π‘ β 2 = 6. 25" β
= 2. 235 ππ
2.235 ππ 2
= 5. 13 ππ β π2 = 5"
AISC Table 3-18 Use Ξ£ππ = 192 πΎπππ , π2 = 5" Οπππ = 416 πΎππ Β· ππ‘ Οπππ β€ ππππ₯ Upsize Beam to W21x44 and Increase to 2 studs/ft Ξ£ππ = 24 * (17. 1 πΎπππ ) = 410. 4 πΎπππ π=
Ξ£ππ
=
0.85ππ'ππππ
410.4 πΎπππ 0.85(3πΎππΌ)(36ππ)
π
π2 = π‘ β 2 = 6. 25" β
= 4. 47 ππ
4.47 ππ 2
= 4 ππ
AISC Table 3-18; Use Ξ£ππ = 358 πΎπππ , π2 = 4" Οπππ = 607 πΎππ Β· ππ‘ Οπππ β€ ππππ₯ Upsize Beam to W21x48 and Increase to 3 studs/ft Ξ£ππ = π=
3(24) 2
* (17. 1 πΎπππ ) = 615. 6 πΎπππ
Ξ£ππ
=
0.85ππ'ππππ π
615.6 πΎπππ 0.85(3πΎππΌ)(36ππ)
= 6. 7 ππ
6.7 ππ 2
= 2. 9 ππ
π2 = π‘ β 2 = 6. 25" β
AISC Table 3-18; Use Ξ£ππ = 530, π2 = 2. 5", π2 = 3" π2 = 2. 5": 643 πΎ Β· ππ‘ , π2 = 3": 662 πΎ Β· ππ‘ 662β643 (2. 9 β 2. 5) + 643 = 658. 2 πΎ Β· ππ‘ 3β2.5
π2 = 2. 9":
Οπππ = 658. 2 πΎππ Β· ππ‘ β₯ ππππ₯ = 653. 28 πΎππ Β· ππ‘ Camber 3
βππ =
3
ππΏ 48πΈπΌ
=
24.92 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(959 ππ )
= 0. 45"
0. 8(0. 45") = 0. 36" NO CAMBER AISC Table 3-19; Use Ξ£ππ = 530, π2 = 2. 5" 4
πΌπΏπ΅ = 1950 ππ
Deflection LL only: π = 100 πππΉ * 24 ππ‘ * 36 ππ‘ = 86. 4 πΎπππ 3
βπΏπΏ =
ππΏ 48πΈπΌ
3
=
86.4 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(1950 ππ )
= 0. 76" β€ 34
24*12 ππ 720
= 0. 4"
3
πΌπΏπ΅,πππ =
ππΏ 48πΈπΌ
3
=
4
86.4 πΎπππ *(24*12 ππ) 48(29000 πΎππΌ)(0.4")
= 3706. 74 ππ
Upsize Beam to W24x84 and 2 studs/ft AISC Table 3-19; Use Ξ£ππ = 308, Ξ£ππ = 425, π2 = 4" πΌπΏπ΅ =
4 4 4000β3640 (410. 4 β 308) + 3640 = 3955 ππ β₯ 3706. 74 ππ 425β308 3
βπΏπΏ =
3
ππΏ 48πΈπΌ
=
86.4 πΎπππ *(24*12 ππ)
= 0. 375" β€
4
48(29000 πΎππΌ)(3955 ππ )
24*12 ππ 720
= 0. 4"
12*24 ππ 240
= 1. 2"
DL Post-Composite: π = 19 πππΉ * 24ππ‘ * 36 ππ‘ = 16. 42 πΎπππ 3
ππΏ
βπ·πΏ, ππΆ = 48πΈπΌ =
3
16.42 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(3955 ππ )
= 0. 07"
βπππ‘ππ = 0. 45" + 0. 07" + 0. 375" = 0. 895" β€ W24x84 w/ (48) studs Exterior Girder
π΄π = 12ππ‘ * 36/2 ππ‘ = 216 ππ‘
2
Pre-composite ππ π€ = ππ πππ + πππππ + πππππ = 49. 7 πππΉ + 8 πππΉ = 57. 7 πππΉ ππΏπΏ, πΆπππ π‘ππ’ππ‘πππ = 20 πππΉ Post Composite ππ·πΏ = ππ π€ + πππΌπ·πΏ = 57. 7 πππΉ + 19 πππΉ = 76. 7 πππΉ ππΏπΏ = 125 πππΉ
35
ππ€ = 1. 2(15 πππΉ * 13 ππ‘) = 234 ππΏπΉ ππ‘ππ‘ππ = 234 ππΏπΉ + 1. 2(76. 7 πππΉ * 1 ππ‘) + 1. 6(125 πππΉ * 1 ππ‘) = 526. 04 ππΏπΉ Pre-composite strength ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) *
πΏππππ 2
ππ’ = (1. 2(57. 7 πππΉ * 12 ππ‘) + 1. 6(20 πππΉ * 12 ππ‘)) * 18 ππ‘ ππ’ = 21865 πππ = 21. 87 πΎπππ ππππ₯ =
ππΏ 4
2
+
π€πΏ 8
=
21.87 πΎπππ * 24 ππ‘ 4
2
+
526.04 ππΏπΉ*(24ππ‘) 8000
= 131. 19 + 37. 87πΎππ Β· ππ‘
ππππ₯ = 169. 06 πΎππ Β· ππ‘ πΏπ = 12ππ‘ πΆπ = 1. 67 AISC Table 3-2 Select W21x44 Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 67)[358 πΎπππ β 16. 8(12 ππ‘ β 4. 45 ππ‘)] β€ 358 πΎπππ 386. 03 πΎπππ β₯ 358 πΎπππ Οππππ₯ = 358 πΎπππ Οππππ₯ β₯ ππππ₯ π = 57. 7 πππΉ * 12 ππ‘ * 18 ππ‘ = 12. 46 πΎπππ 3
βππ =
ππΏ 48πΈπΌ
3
=
12.46 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(843 ππ )
= 0. 25"
NO CAMBER Post Composite Strength ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ/2 ππ’ = (1. 2(76. 7 πππΉ * 12 ππ‘) + 1. 6(125 πππΉ * 12 ππ‘)) * 18 ππ‘ ππ’ = 63. 08 πΎπππ ππππ₯ =
ππΏ 4
2
+
π€πΏ 8
=
63.08 πΎπππ * 24 ππ‘ 4
2
+
526.04 ππΏπΉ*(24ππ‘) 8000
πΎππ Β· ππ‘
ππππ₯ = 416. 35 πΎππ Β· ππ‘ 1 stud/ft Ξ£ππ = 24/2 * (17. 1 πΎπππ ) = 205. 2 πΎπππ πΏ
π
ππππ = 12" + πππ( 8 , 20 ) = 12" + πππ( π=
Ξ£ππ 0.85ππ'ππππ π
=
205.2 πΎπππ 0.85(3πΎππΌ)(48ππ)
π2 = π‘ β 2 = 6. 25" β
1.67 ππ 2
24 ππ‘ , 8
36 ππ‘ ) 2
= 1. 67 ππ = 5. 41 ππ β π2 = 5" 36
= 48 ππ
AISC Table 3-18 Use Ξ£ππ = 163 πΎπππ , π2 = 5" Οπππ = 518 πΎππ Β· ππ‘ AISC Table 3-19 πΌπΏπ΅ = 1460 ππ
4
Check Deflection LL only: π = 125 πππΉ * 12 ππ‘ * 18 ππ‘ = 27 πΎπππ 1 πΎππ
π€πΏ = 125 ππΏπΉ * 12000 ππ = 0. 010 πΎππ/ππ 4
5π€πΏπΏ
3
ππΏ 48πΈπΌ
βπΏπΏ =
3
+ 384πΈπΌ =
4
27 πΎπππ *(24*12 ππ)
+
4
48(29000 πΎππΌ)(1460ππ )
5*0.010 πΎππ/ππ(24*12 ππ)
4
384(29000 πΎππΌ)(1460 ππ )
= 0. 32" β€ 3/8"
DL Post-Composite: π = 19 πππΉ * 12ππ‘ * 18 ππ‘ = 8. 21 πΎπππ 1 πΎππ
π€π· = (15 πππΉ * 13 ππ‘ + 76. 7ππΏπΉ) * 12000 ππ = 0. 023 πΎππ/ππ 4
5π€π·πΏ
3
βπ·πΏ, ππΆ =
ππΏ 48πΈπΌ
+
3
= 384πΈπΌ
8.21 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(1460 ππ )
4
+
Total Deflection βπ·πΏ, ππΆ + βπΏπΏ + βππ = 0. 36" + 0. 32" + 0. 25" βπππ‘ππ = 0. 93" β€
12*24 ππ 240
OK
= 1. 2"
W21x44 w/ (24) studs Special Exterior Girder π΄π = 0 ππ‘
2
Loading Exterior Wall = 15 πππΉ * 19 πΉπ = 285 ππΏπΉ Deflection (there is no live loading) 4
5π€πΏ 384πΈπΌ
βπππ₯ =
πΏ
β€ 240 = 4
285
πΌπππ =
24*12 240
5( 12*1000 )(24*12) 384(29000)(1.2)
= 1. 2" 4
= 61. 14 ππ
4
AISC Table 3-3 Select W12x14;πΌπ₯ = 88. 6 ππ Οππππ₯ = 65. 3 πΎππ Β· ππ‘; Strength 2
ππππ₯ =
π€πΏ 8
2
=
285 ππΏπΉ *( 24 ππ‘) 8(1000)
= 20. 52 πΎππ Β· ππ‘
37
5*0.023 πΎππ/ππ(24*12 ππ)
4
384(29000 πΎππΌ)(1460 ππ )
= 0. 36"
πΏπ = 12ππ‘ πΆπ = 1. 67 Οπππ = 18. 6 πΎππ Β· ππ‘ Γ 1. 67 = 31. 06 πΎππ Β· ππ‘ β€ Οππππ₯ = 65. 3 πΎππ Β· ππ‘ Οπππ = 31. 06 πΎππ Β· ππ‘ β₯ 20. 52 πΎππ Β· ππ‘ W12x14 Lvl 2, Special Case: Girder
π΄π = 12ππ‘ * 36/2 ππ‘ = 216 ππ‘
2
Pre-composite ππ π€ = ππ πππ + πππππ + πππππ = 49. 7 πππΉ + 8 πππΉ = 57. 7 πππΉ ππΏπΏ, πΆπππ π‘ππ’ππ‘πππ = 20 πππΉ Post Composite ππ·πΏ = ππ π€ + πππΌπ·πΏ = 57. 7 πππΉ + 19 πππΉ = 76. 7 πππΉ ππΏπΏ = 125 πππΉ ππ‘ππ‘ππ = 1. 2(76. 7 πππΉ * 1 ππ‘) + 1. 6(125 πππΉ * 1 ππ‘) = 292. 04 ππΏπΉ Pre-composite strength ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) *
πΏππππ 2
38
ππ’ = (1. 2(57. 7 πππΉ * 12 ππ‘) + 1. 6(20 πππΉ * 12 ππ‘)) * 18 ππ‘ ππ’ = 21865 πππ = 21. 87 πΎπππ ππππ₯ =
ππΏ 4
2
+
π€πΏ 8
=
21.87 πΎπππ * 24 ππ‘ 4
2
+
292.04 ππΏπΉ*(24ππ‘) 8000
= 131. 19 + 21. 03 πΎππ Β· ππ‘
ππππ₯ = 152. 22 πΎππ Β· ππ‘ πΏπ = 12ππ‘ πΆπ = 1. 67 AISC Table 3-2 Select W21x44 Οπππ = πΆπ[Οππππ₯ β Οππ΅πΉ(πΏπ β πΏπ)] β€ Οππππ₯ (1. 67)[358 πΎπππ β 16. 8(12 ππ‘ β 4. 45 ππ‘)] β€ 358 πΎπππ 386. 03 πΎπππ β₯ 358 πΎπππ Οππππ₯ = 358 πΎπππ Οππππ₯ β₯ ππππ₯ π = 57. 7 πππΉ * 12 ππ‘ * 18 ππ‘ = 12. 46 πΎπππ 3
βππ =
ππΏ 48πΈπΌ
3
=
12.46 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(843 ππ )
= 0. 25"
NO CAMBER Post Composite Strength ππ’ = (1. 2π·πΏ + 1. 6πΏπΏ) * πΏππππ/2 ππ’ = (1. 2(76. 7 πππΉ * 12 ππ‘) + 1. 6(125 πππΉ * 12 ππ‘)) * 18 ππ‘ ππ’ = 63. 08 πΎπππ ππππ₯ =
ππΏ 4
2
+
π€πΏ 8
=
63.08 πΎπππ * 24 ππ‘ 4
2
+
292.04 ππΏπΉ*(24ππ‘) 8000
πΎππ Β· ππ‘
ππππ₯ = 399. 51 πΎππ Β· ππ‘ 1 stud/ft Ξ£ππ = 24/2 * (17. 1 πΎπππ ) = 205. 2 πΎπππ πΏ
π
ππππ = 12" + πππ( 8 , 20 ) = 12" + πππ( π=
Ξ£ππ 0.85ππ'ππππ
=
205.2 πΎπππ 0.85(3πΎππΌ)(48ππ)
π
π2 = π‘ β 2 = 6. 25" β
1.67 ππ 2
24 ππ‘ , 8
36 ππ‘ ) 2
= 1. 67 ππ = 5. 41 ππ β π2 = 5"
AISC Table 3-18 Use Ξ£ππ = 163 πΎπππ , π2 = 5" Οπππ = 518 πΎππ Β· ππ‘ AISC Table 3-19
39
= 48 ππ
πΌπΏπ΅ = 1460 ππ
4
Check Deflection LL only: π = 125 πππΉ * 12 ππ‘ * 18 ππ‘ = 27 πΎπππ 1 πΎππ
π€πΏ = 125 ππΏπΉ * 12000 ππ = 0. 010 πΎππ/ππ 4
5π€ πΏ
3
βπΏπΏ =
ππΏ 48πΈπΌ
πΏ + 384πΈπΌ =
3
4
27 πΎπππ *(24*12 ππ)
+
4
48(29000 πΎππΌ)(1460ππ )
5*0.010 πΎππ/ππ(24*12 ππ)
4
384(29000 πΎππΌ)(1460 ππ )
= 0. 32" β€ 3/8"
DL Post-Composite: π = 19 πππΉ * 12ππ‘ * 18 ππ‘ = 8. 21 πΎπππ 1 πΎππ
π€π· = 76. 7ππΏπΉ * 12000 ππ = 0. 0064 πΎππ/ππ 4
3
βπ·πΏ, ππΆ =
ππΏ 48πΈπΌ
+
5π€π·πΏ
= 384πΈπΌ
3
8.21 πΎπππ *(24*12 ππ)
4
48(29000 πΎππΌ)(1460 ππ )
4
+
5*0.0064 πΎππ/ππ(24*12 ππ)
Total Deflection βπ·πΏ, ππΆ + βπΏπΏ + βππ = 0. 33" + 0. 32" + 0. 25" βπππ‘ππ = 0. 91" β€
12*24 ππ 240
= 1. 2"
OK
W21x44 w/ (24) studs
5. Connection Design 5.1. Typical Beam to Girder Connection at Roof level
πΏ = 15. 9" β 2(2") = 11. 9" β 11. 5" AISC Table 10-10a π = 11. 5" , π = 4 ππ’ = 11. 46 πΎπππ (πππ. 2) USE ΒΌβ Plate w/ ΒΎβ bolts & 3/16β weld
40
4
384(29000 πΎππΌ)(1460 ππ )
= 0. 33"
Check beam web for block shear
ππβ = 1. 5" 2
π΄ππ‘ = (ππβ β Γ/2)π‘π€ = (1. 5" β (3/4" + 1/16")/2)(0. 275") = 0. 30 ππ 2
π΄ππ£ = ππ‘π€ = 11. 25" * 0. 275" = 3. 09 ππ π΄ππ£ = (π β (π β 0. 5)(Γ/2))π‘π€
π΄ππ£ = (11. 25" β (3. 5")( (3/4" + 1/16")/2)))(0. 275")) = 2. 70 ππ
2
2
0. 6πΉπ¦π΄ππ£ = 0. 6(50 πΎππΌ)(3. 09 ππ ) = 92. 7 ππππ 2
0. 6πΉπ’π΄ππ£ = 0. 6(65 πΎππΌ)(2. 70 ππ ) = 105. 3 ππππ Οπ π = 0. 75(0. 6πΉπ¦π΄ππ£ + πππ πΉπ’π΄ππ‘) = 0. 75(92. 7 ππππ + (1)19. 5 πΎπππ )) Οπ π = 84. 15 ππππ Οπ π β₯ ππ’
OK
5.2. Typical Girder to Column Connection at Office Level
3" 1
12"
41
Single Plate Connection using: β β Diameter A325-N BOLTS πΉπ¦ = 36 ππ π 7
Girder: W18x35 ; π‘π = 16 " Shear Demand: ππ’ = 35. 62 ππππ (Typical Girder Calcs) 3
7
1
πΏ = 17 4 " β 2( 16 ") = 16. 875" β 14 2 " AISC Table 10-10a 1
πΏ = 16. 875" β 14 2 " N=5 1
Plate Thickness = 4 " USE ΒΌβ Plate w/ ΒΎβ bolts & 3/16β weld
6. Secondary Steel β Wind Girt Design 6.2. Loading Load Type
Loading (PLF)
Exterior Wall
71.3
Out of Plane Wind (Ultimate)
570
6.3. Final HSS Design HSS Size Wind Girt
HSS16x4x3/16
42
6.4. D-3 Column Check 6.4.1. Loading Load Type
Loading
Live Axial Load
79.3 Kips
Dead Axial Load
193.7 Kips
Out of plane Wind Load
13.68 Kips
6.4.2. Final D-3 Column Design D-3 Column Initial Column
W12x53
Final Column
W12x65
7. Steel Member Take-Off 7.1. Columns Column
Top Section
Length (ft)
Weight (lbs)
Middle Section
Length Weight (ft) (lbs)
Bottom Section
Length (ft)
Weight (lbs)
A-1
W8x31
39
1209
W8x48
33
1584
W10x49
23
1127
A-2
W8x31
39
1209
W12x53
33
1749
W12x65
23
1495
A-3
W8x31
39
1209
W12x53
33
1749
W12x65
23
1495
A-4
W8x31
39
1209
W12x53
33
1749
W12x65
23
1495
A-5
W8x31
39
1209
W8x48
33
1584
W10x49
23
1127
B-1
W8x31
39
1209
W10x54
33
1782
W12x65
23
1495
B-2
W8x31
39
1209
W12x65
33
2145
W14x132
23
3036
B-3
W8x31
39
1209
W12x65
33
2145
W14x132
23
3036
43
Column
Top Section
Length (ft)
Weight (lbs)
Middle Section
Length Weight (ft) (lbs)
Bottom Section
Length (ft)
Weight (lbs)
B-4
W8x31
39
1209
W12x65
33
2145
W14x132
23
3036
B-5
W8x31
39
1209
W10x54
33
1782
W12x65
23
1495
C-1
W8x31
39
1209
W10x54
33
1782
W12x65
23
1495
C-2
W8x31
39
1209
W10x49
33
1617
W10x54
23
1242
C-3
W8x31
39
1209
W10x49
33
1617
W10x49
23
1127
C-4
W8x31
39
1209
W10x49
33
1617
W10x54
23
1242
C-5
W8x31
39
1209
W10x54
33
1782
W12x65
23
1495
D-1
W8x31
39
1209
W8x48
33
1584
W10x49
23
1127
D-2
W8x31
39
1209
W12x53
33
1749
W12x58
23
1334
D-3
W8x31
39
1209
W12x65
33
2145
W12x65
23
1495
D-4
W8x31
39
1209
W12x53
33
1749
W12x58
23
1334
D-5
W8x31
39
1209
W8x48
33
1584
W10x49
23
1127
Total Weight (lbs)
Weight (Tons)
Cost/Ton
Cost of Steel
Number of Splices
Cost/Splice
Cost of Splices
Total Cost
90548
45.274
$6000
$271644
60
$2000
$120000
$391644
Length (ft)
Weight (lbs)
7.2. Beams
Beam Size
Location
Quantity
Total Weight (lbs)
39
43524
Roof W16x31
Interior/Exterior
36
1116
Typical Floor
44
W16x31
Interior
36
1116
21
23436
W18x40
Exterior
36
1440
6
8640
Floor 2 W16x31
Atruim
36
1116
2
2232
W21x73
Interior
36
2628
16
42048
W33x152
Exterior
36
5472
6
32832
Total Weight (lbs)
Weight (Tons)
Cost/Ton
Cost of Steel
152712
76.36
$6000
$458160
45
7.3. Girders
Beam Size
Location
Length (ft)
Weight (lbs)
Quantity
Total Weight (lbs)
16
13440
Roof W18x35
Interior/Exterior
24
840
Typical Floor W16x31
Exterior
24
744
8
5952
W16x40
Interior
24
960
8
7680
Floor 2 W12x14
Atrium Exterior
24
336
2
672
W21x44
Exterior/Interior Atrium
24
1056
8
8448
W24x84
Interior
24
2016
6
12096
Total Weight (lbs)
Weight (Tons)
Cost/Ton
Cost of Steel
48288
24.14
$6000
$144864
Member
Member Size
Nominal Weight (lb/ft)
Cost
Wind Girt
HSS16x4x3/16
24.73
$3,561.12
7.4. Wind Girt
7.5. Total Cost Colum cost
Beam Cost
Girder Cost
Wind Grit Cost
Total Cost
$391,644
$458,160
$144,864
$3,561.12
$998,229.12
46