ATC White Paper - Transitioning to Low-GWP Refrigerants in Process Cooling

Page 1


APPLIED THERMAL CONT

TRANSITIONING TO LOW-GW

PROCESS COOLING

The transition to low Global Warming Potential (GWP) refrigerants is reshaping the process cooling landscape.

Driven by tightening environmental regulations and sustainability targets, engineers and manufacturers are increasingly required to move away from traditional high-GWP refrigerants toward more environmentally responsible alternatives.

Among the most widely adopted options in process cooling are R290 (propane) and R454C, each offering distinct advantages and trade-offs. In practice, the selection of these refrigerants is often driven by system capacity and application requirements, rather than a direct like-for-like choice between the two

This white paper explores:

The characteristics of R290 and R454C and how they are applied in different system sizes

Key regulatory drivers across major regions (UK, EU, US, UAE) Application considerations when selecting low-GWP refrigerants

It is intended to support engineers, OEMs, and technical decision makers navigating this transition

The Challenge

Transitioning to low-GWP refrigerants is not simply a case of replacing one refrigerant with another. Each alternative introduces new considerations around safety, system design, performance, and compliance. In many cases, there is no single “like-for-like” replacement, meaning engineers must balance environmental impact with practical system requirements Understanding these trade-offs is essential to making informed decisions.

APPLIED THERMAL CONT TRANSITIONING TO LOW-GW

R290 and R454C i

R290 and R454C are both low-GWP application suitability Rather than chiller capacities and system desig considerations

R290

R454C

R290 is a natural refrigerant with extremely low environmental impact Key characteristics include:

Ultra-low GWP ( 3)

Excellent thermodynamic performance

High energy efficiency

Advantages of R290

Superior heat transfer performance

Environmentally sustainable

High system efficiency

Future-proof against regulatory changes

Limitations of R290

Classified as A3 (highly flammable)

Charge size and limitations in many applications

Requires strict safety design and risk assessment

May require additional safety components and certifications

R454C is a synthetic, mildly flammable refrigerant blend designed as a lower-GWP alternative to traditional HFCs. Key characteristics include:

Low-GWP (~148)

Lower flammability compared to R290

Advantages of R454C

Easier transition from legacy refrigerants

Lower flammability risk compared to A3 refrigerants

Suitable for a wide range of applications

Limitations of R454C

Higher GWP than natural refrigerants

Lower efficiency compared to R290 in some applications

Still subject to long-term regulatory pressure

Performance Com

When comparing R290 (propane) a distinct advantages depending on t

R290 provides excellent thermodyn strong cooling capacity, high energ support compact system designs and lower power consumption.

R454C, meanwhile, offers a balanced combination of performance, lower GWP, and reduced flammability classification (A2L), making it well suited to larger systems and applications where refrigerant charge, installation environment, or regulatory compliance are key considerations

While R454C can experience a greater reduction in cooling performance at more demanding lowtemperature conditions compared with R290, it remains an effective and widely adopted solution for medium and large-capacity chiller systems Conversely, although R290 can deliver very strong performance and efficiency benefits, its A3 flammability classification requires additional design considerations around ventilation, leak detection, electrical protection, and overall system compliance.

As such, we utilise R290 within our smaller chiller platforms, where refrigerant charge limits can be more easily managed, and R454C within our larger chillers, where system capacity and application requirements make it a highly practical and effective solution

Selection Considerations

In general:

R290 is typically applied in smaller-capacity systems where maximum efficiency and ultra-low GWP can be achieved within charge size limitations

R454C is typically applied in larger-capacity systems where lower flammability classification and practical system design considerations are key.

Regulatory Driver

UK & European Union

The UK and EU are implementing phased reductions in high-GWP refrigerants under F-Gas regulations. Key drivers include:

Gradual reduction in allowable HFC quotas

Restrictions on placing high-GWP systems on the market

Increasing compliance requirements for manufacturers

Direction of travel:

Continued tightening of GWP thresholds

Increased focus on natural refrigerants

Greater emphasis on lifecycle emissions

United States

United Arab Emirates

Regulation in the US is evolving, with increasing adoption of low-GWP refrigerants driven by federal and state-level initiatives

Key influences include:

The AIM Act (American Innovation and Manufacturing Act)

State-level regulations (e g California)

Industry-led sustainability commitments

Greater emphasis on lifecycle emissions

The UAE is also aligning with global environmental goals, with increasing focus on reducing emissions and improving energy efficiency

Key drivers include:

Adoption of international standards

Sustainability initiatives and green building regulations

Gradual transition away from high-GWP refrigerants

Regional Differences

Global refrigerant regulations all aim to reduce highGWP refrigerants but differ in pace and structure

The EU is the most stringent, using a quota-based phasedown with explicit bans that rapidly push adoption of very low-GWP refrigerants

The US follows the AIM Act with a federally driven phasedown but varied state-level rules that create regional differences, and Asia applies a more mixed approach, with Japan and China implementing staged reductions under the Kigali framework but generally with more gradual timelines and greater flexibility in refrigerant choice.

Impact on System Design

Regulations influence refrigerant selection, system architecture, safety requirements, and future upgrade pathways,

Application Consi

Selecting the right refrigerant depends heavily on the application and operating environment

Safety Requirements

System Design Implications

Flammability classification plays a critical role R290 is classified as an A3 refrigerant, meaning that it requires strict safety measures including leak detection, ventilation, and explosion protection in certain environments R454C poses a lower flammability risk as an A2L refrigerant but still requires compliance with safety standards

Different refrigerants require different system designs, including:

Component selection

Refrigerant charge management

System layout and enclosure design

Charge Size Limitations

Performance Requirements

Environmental Conditions

R290 systems are often limited by maximum allowable charge sizes This can influence system capacity and application suitability and may require distributed or modulated designs

Applications with high cooling demand or efficiency requirements may favour refrigerants with better thermodynamic performance, such as R290

Ambient temperature, installation environment, and application type all influence refrigerant selection

Common Challen

Safety Concerns

Flammability introduces additional requirements.

Lack of Familiarity

Engineers and end users may be les refrigerants

System Redesign Requirements

Existing systems may not be directly combatible with new refrigerants

Regulatory Uncertainty

Future regulatory changes can make long-term planning challenging

Balancing Sustainability & Practicality

The lowest GWP option is not always the most practical Trade-offs between efficiency, safety, and cost must be managed

Best Practice Approach to Transitioning

Understand Regulatory Requirements

Ensure compliance with current and future legislation in target markets

Define Application Needs

Consider cooliing capacity, environment, and safety constraints.

Evaluate Refrigerant Options

Assess refrigerants such as R290 and R454C based on GWP, performance, safety, and suitability for the intended system capacity and application

Assess System Design Implications

Ensure system design aligns with refrigerant properties.

Plan for the Future

Chiller selection is increasingly shaped by lower-GWP regulations, with R454C and R290 used according to application size,safety requirements, and long-term compliance needs.

Practical Recomm

Prioritise low-GWP refrigerants

Carefully assess safety implicat refrigerants

Avoid assuming direct replacem

Engage with technical specialis

Consider long-term regulatory and environmental impacts.

The transition to low-GWP refrigerants is a necessary and ongoing shift in the process cooling industry

By understanding the characteristics of refrigerants such as R290 and R454C, and how they are applied across different system sizes and applications, recognising the impact of global regulations, and carefully considering application requirements, engineers can make informed decisions that balance performance, safety, and sustainability

A proactive approach to refrigerant selection ensures compliance while supporting efficient and reliable system operation