choices can be made. It was clear that as Tokyo’s temperature is warmer than Amsterdam’s, focus needs to be given to cooling rather than heating. The challenge: space is limited in Tokyo hence the proposal of making SC as a plug & play unitized system.

Earth, Wind, and Fire (EWF) is a natural ventilation system developed by Dr Ben Bronsema for office buildings in the Western European climate. Powered by nature: ground temperature & gravity for cooling, wind for energy generation & ventilation, and sun for the heat and natural draft, this system claims not only to use little energy but also naturally purifies while humidify/dehumidify the air. No study has been done to see the performance of the system in a warmer climate, such as Tokyo. This thesis intends to answer that with the following research question: “Is the Dutch EWF, in place of the existing air-conditioning system, an efficient energy-retrofitting method to achieve energy-neutrality in an office building in Tokyo without compromising thermal comfort of users?”

Armed with a case study integrating EWF into a relatively new 10-story medium-sized office building in Tokyo, the study explored and compared 4 different systems: the existing energy-conscious VRF system, conventional VAV system, EWF with chilled ceiling, and EWF through chilled beams, as shown below. As a conclusion, EWF can contribute to energy reduction (40%) without compromising thermal comfort in comparison to the conventional VAV. Regarding VRF, further research needs to be done to properly simulate EWF with HR in the dynamic simulation software used. Moreover, EWF contributed to ventilation energy reduction in all cases evaluated, as well as improving thermal comfort.

The 2 dynamic duo of EWF: air supply system called Climate Cascade (CC) and air exhaust system called Solar Chimney (SC) are sized and calculated using 2 separate Excel models, from which the key parameters are identified and design

SUMMER Climate Cascade

1. VAV

2. VRF

3. EWF with chilled ceiling

4. EWF through chilled beams

Solar Chimney

Pre-cooled air to CC 27 °C

Air at the top of SC 25°C

12.5 °C

21 °C

Outside air 31°C efficiency 70% air medium

Space Cooling to 28 °C 28 °C

Heat Pump

Chiller

15 °C

Chilled ceiling

28 °C

15 °C

15 °C

28 °C

Cold Storage

Ground temperature 15 °C

11 °C

Heat Storage 19 °C

WINTER Climate Cascade

Pre-heated air to CC 18 °C

12.5 °C

!

The variety of systems explored

Solar Chimney Air at the top of SC 22°C

14 °C

Outside air 9 °C efficiency 70% air medium

Twin Coil

Air Heating to 16.5 °C

(when necessary)

35 °C

Heat Pump

Chiller 17 °C

11 °C

Cold Storage

Space Heating to 20 °C

20 °C 25 °C

Floor heating

19 °C

Ground temperature 15 °C

11 °C

19 °C

Summer & Winter scenarios

Schematic section of EWF in NK Building, Tokyo

Name Graduation year Tutors 12

Heat Storage

Corresponding temperature distribution

Solar chimney as unitized system: opaque block, transparent block, and frames

Puji Nata Djaja 2021 Regina Bokel & Alejandro Prieto