Instruction Manual
LCP100 Local Control Panel
August 2010
LCP100 LOOP
SWITCH TO LOOP POSITION AUX )
LOGIC SOLVER OUTPUT
1 LOOP )
CASE GROUND
8-20 mA )
LOOP *
* (USER SUPPLIED)
DVC6000 SIS TERMINAL BOX THE DVC6000 SIS MUST BE IN POINT-TO-POINT MODE
NOTE: 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT LEAST 8 mA. THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA.
SHIELD NOT CONNECTED TO LCP100
GE26881-B, Sheet 2 E1084-1
POINT-TO-POINT MODE
LOOP
LCP100 SWITCH TO LOOP POSITION AUX )
LOGIC SOLVER OUTPUT
1 LOOP )
24VDC
)
CASE GROUND
LOOP *
* (USER SUPPLIED)
SYS − /)
DVC6000 SIS TERMINAL BOX
LC340 LINE CONDITIONER
THE DVC6000 SIS MUST BE IN MULTI-DROP MODE
FLD − /)
SHIELD NOT CONNECTED TO LCP100
NOTE: 1 THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA. E1375-1
MULTI-DROP MODE
Figure 4. Wiring for Loop-Powered Configuration; Logic Solver Wired to the Fisher LCP100 then the FIELDVUE DVC6000 SIS
6