LCP100 Local Control Panel

August 2010

LCP100 LOOP

SWITCH TO LOOP POSITION AUX )

LOGIC SOLVER OUTPUT

1 LOOP )

CASE GROUND

8-20 mA )

LOOP *

* (USER SUPPLIED)

DVC6000 SIS TERMINAL BOX THE DVC6000 SIS MUST BE IN POINT-TO-POINT MODE

NOTE: 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT LEAST 8 mA. THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA.

SHIELD NOT CONNECTED TO LCP100

GE26881-B, Sheet 2 E1084-1

POINT-TO-POINT MODE

LOOP

LCP100 SWITCH TO LOOP POSITION AUX )

LOGIC SOLVER OUTPUT

1 LOOP )

24VDC

)

CASE GROUND

LOOP *

* (USER SUPPLIED)

SYS − /)

DVC6000 SIS TERMINAL BOX

LC340 LINE CONDITIONER

THE DVC6000 SIS MUST BE IN MULTI-DROP MODE

FLD − /)

SHIELD NOT CONNECTED TO LCP100

NOTE: 1 THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA. E1375-1

MULTI-DROP MODE

Figure 4. Wiring for Loop-Powered Configuration; Logic Solver Wired to the Fisher LCP100 then the FIELDVUE DVC6000 SIS