Low-Voltage Electrical Service Standard E.21-10

Page 165

Tables

Table 2

Service voltage limits – Allowable range At supply point (in volts)

Type of line

Nominal voltage (volts)

Extreme operating conditions Normal operating conditions

Single-phase 120/240

106/212

110/220

125/250

127/254

Three-phase 4 conductors 120/208Y 347/600Y

110/190 306/530

112/194 318/550

125/216 360/625

127/220 367/635

Three-phase 3 conductors 600

530

550

625

635

At point of use (at load point) (in volts)

Type of line

Nominal voltage (volts)

Extreme operating conditions Normal operating conditions

Single-phase 120/240

104/208

108/216

125/250

127/254

Three-phase 4 conductors 120/208Y 347/600Y

108/187 300/520

110/190 312/540

125/216 360/625

127/220 367/635

Three-phase 3 conductors 600

520

540

625

635

Notes: Normal operating conditions – No improvements or corrective measures are required. Extreme operating conditions – Improvements or corrective measures must be planned based on an established program, but immediate action is not necessarily required. Ref.: Section 2.6.2 and CAN3-C235-83 (C2000)