INSPECTION REPORT
For the Property at:
777 JAMES BOND WAY ROSEMARY BEACH, FL 32461
Prepared for: PETE HENRY Inspection Date: Monday, November 9, 2015 Prepared by: Randall Rands
Inspections by Randall LLC 102 Heron turn Panama City Beach, FL 32407 850 714 1955 inspectionsbyrandall.com randall@inspectionsbyrandall.com
Detailed property inspection reports - for information and your safety
January 27, 2016 Dear Pete Henry, RE: Report No. 1029 777 James Bond Way Rosemary Beach, FL 32461 Thanks very much for choosing Inspections by Randall LLC to perform your home inspection. The inspection itself and the attached report comply with the requirements of the Standards of Practice of our national Association. This document defines the scope of a home inspection. Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report. The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein . The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectors cannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. If conditions change, we are available to revisit the property and update our report. The report itself is copyrighted, and may not be used in whole or in part without our express written permission. Again, thanks very much for choosing us to perform your home inspection. Sincerely, Randall Rands on behalf of Inspections by Randall LLC
Inspections by Randall LLC 102 Heron turn Panama City Beach, FL 32407 850 714 1955 inspectionsbyrandall.com randall@inspectionsbyrandall.com
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as a courtesy and cannot be considered a substitute for reading the entire report. Please read the complete document. Priority Maintenance Items
Exterior DOORS \ Doors and frames Condition: Loose or poor fit Door does not fit tight against seal. Recommend further evaluation by finish carpenter. Implication(s): Chance of damage to finishes and structure Location: First Floor Dining Room
1. Loose or poor fit
2. Loose or poor fit
LANDSCAPING \ General Condition: Trees or shrubs too close to building This palm has matured and is now touching balcony, may need to be pruned, removed or moved to another area. Recommend further evaluation by qualified landscaper. Implication(s): Chance of water damage to contents, finishes and/or structure | Chance of pests entering building | Material deterioration
Providing great property inspections for every client every time
Page 1 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
3. Trees or shrubs too close to building
Electrical General Rainbird electrical sprinkler system has tapped into the 100 amp carriage house circuit breaker recommend further evaluation by licensed electrician. Implication(s): Double tapping of wires could be a fire hazard Location: Exterior wall
4.
Providing great property inspections for every client every time
Page 2 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Three of the exterior lights did not come on when the similar fixtures had come on. Recommend further evaluation by licensed electrician to find out if why the bulbs are not shining. Location: South Exterior
5.
6.
DISTRIBUTION SYSTEM \ Wiring - installation Condition: Common wires and ground wires are located on the same bus, plus the connection bridge bar has not been removed. Recommend further evaluation by a licensed electrician Location: First Floor Garage
7.
8.
Providing great property inspections for every client every time
Page 3 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
DISTRIBUTION SYSTEM \ Lights Condition: Inoperative Both lights inoperative, recommend further evaluation to see if it is just the light bulbs. Implication(s): Inadequate lighting Location: Second Floor Master Bathroom
9. Inoperative DISTRIBUTION SYSTEM \ Outlets (receptacles) Condition: Inoperative Floor outlet: No power to one of the outlets, recommend further evaluation by licensed electrician Implication(s): Equipment inoperative Location: First Floor living room
Providing great property inspections for every client every time
Page 4 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
10. Inoperative Condition: No GFCI (Ground Fault Circuit Interrupter) Appears that an outlet has been added to the balcony off the master bedroom. Common practice for exterior outlets in this location is to be GFCI protected. This outlet is not GFCI protected. Implication(s): Electric shock Location: Second Floor Balcony
Providing great property inspections for every client every time
Page 5 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
11. No GFI (Ground Fault Interrupter) Condition: Test faulty on Ground Fault Circuit Interrupter (GFCI) Ground fault circuit interrupter not operating in the cottage bathroom. Recommend further evaluation by licensed electrician Implication(s): Electric shock Location: Second Floor Bathroom
12. GFI test faulty Providing great property inspections for every client every time
Page 6 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Heating FIREPLACE \ Gas fireplace Condition: Gas fireplace could not be tested - recommend further evaluation to find out if it is functioning. Location: First Floor Dining Room Task: Further evaluation
Cooling & Heat Pump General Further evaluation needed on all heat pump units - Dirty air filters need to be replaced, all thermostats need to be located, interior air handlers for the main house need to be located and inspected. Acceptable minimum temperature differential is 14 degrees. The max temperature differential measured during the inspection was 10 degrees. Recommend routine servicing of all units - or documentation that this has recently been done. AIR CONDITIONING \ Refrigerant lines Condition: Missing insulation Implication(s): Reduced system life expectancy | Increased cooling costs | Reduced comfort Location: East Exterior
13. Missing insulation
14. Missing insulation
Providing great property inspections for every client every time
Page 7 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Insulation and Ventilation ATTIC/ROOF \ Hatch Condition: Missing No attic access present - could not inspect the attic space in either building. Implication(s): Difficult to service Location: Third Floor
Plumbing WATER HEATER \ Tank Condition: Water heater could not be found for the main building - no inspection could be made - need to verify age, condition, pressure relief valve present, overflow pan present - etc. FIXTURES AND FAUCETS \ Basin, sink and laundry tub Condition: Stopper does not seal to keep water in sink, recommend further evaluation by licensed plumber. Location: Third Floor Bathroom
15. FIXTURES AND FAUCETS \ Bathtub Condition: Drain stop ineffective Stopper needs to be installed correctly, recommend further evaluation by licensed plumber Implication(s): Reduced operability Location: Third Floor Bathroom
Providing great property inspections for every client every time
Page 8 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
16. Drain stop ineffective FIXTURES AND FAUCETS \ Shower stall Condition: Leak water leak at exterior shower recommend further evaluation by licensed plumber Implication(s): Chance of water damage to contents, finishes and/or structure Location: Exterior
17. Leak
Providing great property inspections for every client every time
Page 9 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Interior General Entire back balcony off of master bedroom surrounded with louvered shutters. It is assumed that at one time the louvers opened and closed. At this time the louvers will not adjust to open or close, they are either stuck open or stuck closed.. Shutter doors also appear to have opened and closed at one time. At this time the shutter door panels are stuck and will not open. Recommend further evaluation by finished carpenter. Location: Second Floor Porch
18.
19.
FLOORS \ Ceramic tile, stone, marble, etc Condition: Large gouges and voids in Couquina floor tile. Recommend filing and repair by contractor familiar with this type of flooring. Location: First Floor areas
Providing great property inspections for every client every time
Page 10 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
20.
21.
CEILINGS \ Wood Condition: Water stains at ceiling - next to exterior wall under the second floor balcony. Recommend further evaluation by licensed contractor Location: First Floor Dining Room
22.
23.
WINDOWS \ General Condition: Carriage Apartment: Double hung window next to the dining room table is open over an inch and not locked. Not sure if this is how window is supposed to be, recommend further evaluation by speaking with existing owner.
Providing great property inspections for every client every time
Page 11 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Location: Second Floor Living Room - Carriage
24.
25.
DOORS \ Doors and frames Condition: Inoperable Both doors to the left and right of the center door could not unlock this door to open appears to be stuck. Recommend further evaluation by finish carpenter Implication(s): Reduced operability Location: Second Floor Master Bedroom
Providing great property inspections for every client every time
Page 12 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
26. Inoperable
27. Inoperable
STAIRS \ Handrails Condition: Missing Standard practice is to have one continuous handrail from top of stairs to the bottom of the stairs. Both flights of stairs do not have this safety feature. Implication(s): Fall hazard
Providing great property inspections for every client every time
Page 13 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Providing great property inspections for every client every time
Page 14 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
28. Missing hand rail STAIRS \ Spindles or balusters Condition: Loose Newel post is loose recommend further evaluation by finish carpenter Implication(s): Fall hazard Location: Third Floor Bedroom
29. Loose Providing great property inspections for every client every time
Page 15 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Condition: Loose newel posts are loose and wiggle do not feel sturdy recommend further evaluation by finish Implication(s): Fall hazard Location: Second Floor Staircase
30. Wobbles Condition: Loose Spindles and Newel post are loose and wobbly. Recommend further evaluation by licensed contractor Implication(s): Fall hazard Location: First Floor
Providing great property inspections for every client every time
Page 16 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
31. Loose EXHAUST FANS \ Exhaust fan Condition: Inoperative Exhaust fan not operating. Implication(s): Chance of condensation damage to finishes and/or structure Location: Second Floor Master Bathroom EXHAUST FANS \ Kitchen range exhaust system Condition: Damper not working as it should. This photo was taken after exhaust fan was turned off. Recommend further evaluation to adjust damper to close Location: First Floor - exterior
32. Providing great property inspections for every client every time
Page 17 of 78
Report No. 1029
SUMMARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
This concludes the Summary section. The remainder of the report describes each of the home's systems and also details any recommendations we have for improvements. Limitations that restricted our inspection are included as well. The suggested time frames for completing recommendations are based on the limited information available during a pre-purchase home inspection. These may have to be adjusted based on the findings of specialists. Home Improvement - ballpark costs
Providing great property inspections for every client every time
Page 18 of 78
Report No. 1029
ROOFING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Sloped roofing material: Metal Copper standing seam
33. Metal Sloped roof flashing material: Copper
Providing great property inspections for every client every time
Page 19 of 78
Report No. 1029
ROOFING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
34. Copper Probability of leakage:
Low
Providing great property inspections for every client every time
Page 20 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description General:
Northerly front elevation
35. General:
Easterly side
36. Providing great property inspections for every client every time
Page 21 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
General:
Louvered window shutters surrounding balcony
37. General:
Southeast elevation
38. General:
Southerly side
Providing great property inspections for every client every time
Page 22 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
39. General:
Southwest elevation
40. General:
Gas Meter and main shut off valve location
Providing great property inspections for every client every time
Page 23 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
41.
42.
Gutter & downspout material: Gutter & downspout type:
Copper
Eave mounted
Gutter & downspout discharge: Below grade
43. Below grade Lot slope:
Away from building
Providing great property inspections for every client every time
Page 24 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Wall surfaces: Stucco Smooth finished stucco over concrete wall
44. Stucco Soffit and fascia: Wood
Providing great property inspections for every client every time
Page 25 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
45. Wood Driveway:
Pavers
Walkway: Pavers
46. Pavers Deck: Wood
Providing great property inspections for every client every time
Page 26 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
47. Wood Porch:
Front and rear raised porches at exteriors are Coquina tile
48.
49.
Providing great property inspections for every client every time
Page 27 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Exterior steps: Balcony:
Wood
Wood
No performance issues were noted.
Wood railings
No performance issues were noted.
Patio: Pavers
50. Pavers
51. Pavers
Fence: Concrete Concrete wall with a smooth skim coat of stucco
52. Concrete
Providing great property inspections for every client every time
Page 28 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Recommendations DOORS \ Doors and frames 1. Condition: Loose or poor fit Door does not fit tight against seal. Recommend further evaluation by finish carpenter. Implication(s): Chance of damage to finishes and structure Location: First Floor Dining Room
53. Loose or poor fit
54. Loose or poor fit
LANDSCAPING \ General 2. Condition: Trees or shrubs too close to building This palm has matured and is now touching balcony, may need to be pruned, removed or moved to another area. Recommend further evaluation by qualified landscaper. Implication(s): Chance of water damage to contents, finishes and/or structure | Chance of pests entering building | Material deterioration
Providing great property inspections for every client every time
Page 29 of 78
Report No. 1029
EXTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
55. Trees or shrubs too close to building
Providing great property inspections for every client every time
Page 30 of 78
Report No. 1029
STRUCTURE 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Configuration:
Slab-on-grade
Foundation material: Floor construction:
Poured concrete Concrete
Exterior wall construction: Concrete block with smooth stucco finish (Wall construction according to Walton County Property Assessor's description) Roof and ceiling framing:
Rafters/roof joists
Providing great property inspections for every client every time
Page 31 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Service entrance cable and location: Service size:
Underground - not visible
200 Amps (240 Volts)
Main disconnect/service box rating:
200 amps
Main disconnect/service box type and location: Breakers -exterior wall Main service panel 200 amp breaker for the house with a 100 amp breaker for the carriage house electrical panel.
56. Breakers -exterior wall System grounding material and type: Distribution panel rating:
57. Breakers -exterior wall Not visible
400 Amps
Distribution panel type and location:
Breakers - exterior wall
Auxiliary panel (subpanel) type and location: Breakers - first floor
Providing great property inspections for every client every time
Page 32 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
58. Breakers - first floor
59. Breakers - first floor
Auxiliary panel (subpanel) rating:
60.
100 amp
61.
Providing great property inspections for every client every time
Page 33 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Distribution wire material and type:
Copper - non-metallic sheathed
Type and number of outlets (receptacles):
Grounded - typical
Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): GFCI - kitchen AFCI - bedroom Smoke detectors:
GFCI - bathroom
GFCI - outside
GFCI - whirlpool
Present
Carbon monoxide (CO) detectors: Present
62. Present
Recommendations General 3. Rainbird electrical sprinkler system has tapped into the 100 amp carriage house circuit breaker recommend further evaluation by licensed electrician. Implication(s): Double tapping of wires could be a fire hazard Location: Exterior wall
Providing great property inspections for every client every time
Page 34 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
63. 4. Three of the exterior lights did not come on when the similar fixtures had come on. Recommend further evaluation by licensed electrician to find out if why the bulbs are not shining. Location: South Exterior
64.
65.
DISTRIBUTION SYSTEM \ Wiring - installation 5. Condition: Common wires and ground wires are located on the same bus, plus the connection bridge bar has not been removed. Recommend further evaluation by a licensed electrician Location: First Floor Garage
Providing great property inspections for every client every time
Page 35 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
66.
67.
DISTRIBUTION SYSTEM \ Lights 6. Condition: Inoperative Both lights inoperative, recommend further evaluation to see if it is just the light bulbs. Implication(s): Inadequate lighting Location: Second Floor Master Bathroom
68. Inoperative DISTRIBUTION SYSTEM \ Outlets (receptacles) 7. Condition: Inoperative Floor outlet: No power to one of the outlets, recommend further evaluation by licensed electrician
Providing great property inspections for every client every time
Page 36 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Implication(s): Equipment inoperative Location: First Floor living room
69. Inoperative 8. Condition: No GFCI (Ground Fault Circuit Interrupter) Appears that an outlet has been added to the balcony off the master bedroom. Common practice for exterior outlets in this location is to be GFCI protected. This outlet is not GFCI protected. Implication(s): Electric shock Location: Second Floor Balcony
Providing great property inspections for every client every time
Page 37 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
70. No GFI (Ground Fault Interrupter) 9. Condition: Test faulty on Ground Fault Circuit Interrupter (GFCI) Ground fault circuit interrupter not operating in the cottage bathroom. Recommend further evaluation by licensed electrician Implication(s): Electric shock Location: Second Floor Bathroom
Providing great property inspections for every client every time
Page 38 of 78
Report No. 1029
ELECTRICAL 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
71. GFI test faulty
Providing great property inspections for every client every time
Page 39 of 78
Report No. 1029
HEATING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Fuel/energy source: System type:
Heat pump
Heat distribution: Efficiency:
Electricity
High velocity ducts
one unit is from 2014 with the high efficiency the other unit from 2006 would be a lower efficiency unit
Approximate age:
One unit is the original unit from 2006 - 9 years old. The other unit is one year old from 2014
Limitations Warm weather: Prevented testing in heating mode Heating may only be tested when the exterior temperature is 65 degrees or lower.
Recommendations FIREPLACE \ Gas fireplace 10. Condition: Gas fireplace could not be tested - recommend further evaluation to find out if it is functioning. Location: First Floor Dining Room Task: Further evaluation
Providing great property inspections for every client every time
Page 40 of 78
Report No. 1029
COOLING & HEAT PUMP 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Air conditioning type: Air cooled
72. Air cooled Heat pump type: Air source
Providing great property inspections for every client every time
Page 41 of 78
Report No. 1029
COOLING & HEAT PUMP 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
73. Air source Manufacturer:
74.
Ruud, interior air handler could not be inspected due to no access to unit.
75.
Providing great property inspections for every client every time
Page 42 of 78
Report No. 1029
COOLING & HEAT PUMP 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Manufacturer:
Quietside, interior unit is located in the third floor bunkroom
76. Manufacturer:
77. Unico
78. Manufacturer: Bryant Bryant unit at exterior, interior air handler could not be inspected due to no access to unit.
Providing great property inspections for every client every time
Page 43 of 78
Report No. 1029
COOLING & HEAT PUMP 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
79. Bryant
80. Bryant
81. Bryant Supply temperature:
65째
Return temperature:
75째
Providing great property inspections for every client every time
Page 44 of 78
Report No. 1029
COOLING & HEAT PUMP 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Temperature difference: 10째 Further evaluation needed on all units - Dirty air filters need to be replaced, all thermostats need to be located, interior air handlers for the main house need to be located and inspected. Acceptable minimum temperature differential is 14 degrees. Recommend routine servicing of all units - or documentation that this has recently been done. This suggests performance issues. Service may be needed.
Limitations General: Could not inspect either of two air handlers in the main house. Found the thermostat on the first floor - turned down the AC to make the unit run - located this air handler at the top of the stairs on the second floor - but there was not any access - could hear it running. Next job was to locate the other unit - assumed there must be a second floor thermostat - but could not locate this, since the AC could not be turned to down to make the air handler operate - this meant the second air handler could not be located.
Recommendations General 11. Further evaluation needed on all heat pump units - Dirty air filters need to be replaced, all thermostats need to be located, interior air handlers for the main house need to be located and inspected. Acceptable minimum temperature differential is 14 degrees. The max temperature differential measured during the inspection was 10 degrees. Recommend routine servicing of all units - or documentation that this has recently been done. AIR CONDITIONING \ Refrigerant lines 12. Condition: Missing insulation Implication(s): Reduced system life expectancy | Increased cooling costs | Reduced comfort Location: East Exterior
82. Missing insulation
Providing great property inspections for every client every time
Page 45 of 78
Report No. 1029
COOLING & HEAT PUMP 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
83. Missing insulation
Providing great property inspections for every client every time
Page 46 of 78
Report No. 1029
INSULATION AND VENTILATION 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Wall insulation material:
Not determined
Recommendations ATTIC/ROOF \ Hatch 13. Condition: Missing No attic access present - could not inspect the attic space in either building. Implication(s): Difficult to service Location: Third Floor
Providing great property inspections for every client every time
Page 47 of 78
Report No. 1029
PLUMBING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Water supply source:
Public
Service piping into building: Supply piping in building:
Not visible
Copper
Main water shut off valve at the: Water flow and pressure:
Could not verify water meter or turn off location
Functional
Water heater fuel/energy source: Electric This is the water heater located in the garage assume that is for the cottage could not locate water heater for the main house
84. Electric
85. Electric
Water heater type: Conventional Water heater in the garage is for the carriage house, could not locate water heater for the main house. Water heater manufacturer: Tank capacity:
Rheem
30 gallons
Water heater approximate age:
9 years
Typical life expectancy:
8 to 12 years
Waste disposal system:
Public
Exterior hose bibb:
Providing great property inspections for every client every time
Page 48 of 78
Report No. 1029
PLUMBING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Present
86. Present
Limitations Fixtures not tested/not in service: Water heater Could not find a water heater in the main house. All closets were opened but could locate water heater. Found the water heater in the garage - assume it was for the carriage house.
Recommendations WATER HEATER \ Tank 14. Condition: Water heater could not be found for the main building - no inspection could be made - need to verify age, condition, pressure relief valve present, overflow pan present - etc. FIXTURES AND FAUCETS \ Basin, sink and laundry tub 15. Condition: Stopper does not seal to keep water in sink, recommend further evaluation by licensed plumber. Location: Third Floor Bathroom
Providing great property inspections for every client every time
Page 49 of 78
Report No. 1029
PLUMBING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
87. FIXTURES AND FAUCETS \ Bathtub 16. Condition: Drain stop ineffective Stopper needs to be installed correctly, recommend further evaluation by licensed plumber Implication(s): Reduced operability Location: Third Floor Bathroom
88. Drain stop ineffective FIXTURES AND FAUCETS \ Shower stall 17. Condition: Leak water leak at exterior shower recommend further evaluation by licensed plumber
Providing great property inspections for every client every time
Page 50 of 78
Report No. 1029
PLUMBING 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Implication(s): Chance of water damage to contents, finishes and/or structure Location: Exterior
89. Leak
Providing great property inspections for every client every time
Page 51 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Description Major floor finishes:
Coquina tile
90.
91.
Major floor finishes: Hardwood Solid hardwood flooring used on 2nd floor and third
Providing great property inspections for every client every time
Page 52 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
92. Hardwood
93. Hardwood
Hardwood This is the hardwood used at all floor surfaces in the Carriage house
94. Hardwood Marble Marble used for flooring at master bathroom
Providing great property inspections for every client every time
Page 53 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
95. Marble Marble Marvell in 3rd floor bathroom
96. Marble
Providing great property inspections for every client every time
Page 54 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Major wall finishes: smooth coat plaster
Tongue and groove 1 by 4 clear boards used at most walls. Balance of walls are finished with a
97.
98.
Major ceiling finishes: Wood Bead board panels used in the ceiling of the carriage house
Providing great property inspections for every client every time
Page 55 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
99. Bead board Wood Ceiling finish at first floor ceiling 1 by 4 T&G clear. Ceiling finishes at 2nd and 3rd floor are beaded paneling. Windows: Single/double hung Wood window with true divided lights.
Providing great property inspections for every client every time
Page 56 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
100. Double hung Casement Casement window used in the third floor bunk room and also in the Carriage house bathroom
101. Casement Wood
Providing great property inspections for every client every time
Page 57 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Glazing:
Double
Exterior doors - type/material: French
102. French
103. French
Doors: Inspected Solid wood panels Inspected Pocket door into the master bedroom bathroom will close by itself unless latched with this small latch.
Providing great property inspections for every client every time
Page 58 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
104. Inspected Inspected Some surface mold present at South bedroom french doors. Routine maintenance recommended to prevent mold build up.
105. Inspected
106. Inspected
Providing great property inspections for every client every time
Page 59 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Oven type:
Convection
Oven fuel: Electricity Dacor electric oven with convection
107. Electricity
108. Electricity
Range fuel: Electricity Two burner smoothtop KitchenAid used in the cottage
109. Electricity
Providing great property inspections for every client every time
Page 60 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Gas
110. Gas Appliances: Refrigerator Sub Zero
111. Refrigerator
112. Refrigerator
Providing great property inspections for every client every time
Page 61 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
113. Refrigerator Refrigerator Side by side GE Adora used in the cottage
114. Refrigerator
115. Refrigerator
Range hood Dishwasher
Providing great property inspections for every client every time
Page 62 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Braun
116. Dishwasher
117. Dishwasher
Dishwasher Fisher and Paykel dishdrawer
118. Dishwasher Waste disposal
Providing great property inspections for every client every time
Page 63 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
InSinkErator badger 1/2 horsepower
119. Waste disposal Microwave oven Dacor microwave oven manufactured June 2006
120. Microwave oven
121. Microwave oven
Microwave oven
Providing great property inspections for every client every time
Page 64 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
GE Profile microwave and convection oven used in the cottage
122. Microwave oven Central vacuum
123. Central vacuum Laundry facilities: Washer Washer Stacking Maytag Neptune washer and dryer in all closet on second floor
Providing great property inspections for every client every time
Page 65 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
124. Washer and Dryer Dryer Dryer Maytag stacking washer and dryer used in the carriage house
125. Washer and Dryer
Providing great property inspections for every client every time
Page 66 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Kitchen ventilation:
No kitchen ventilation in the cottage
Kitchen ventilation: Discharges to exterior Dacor side vent
126. Discharges to exterior Bathroom ventilation:
127. Discharges to exterior
Exhaust fan
Laundry room ventilation:
None
Counters and cabinets: Inspected Tile cabinet tops
Providing great property inspections for every client every time
Page 67 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
128. Inspected Stairs and railings:
Inspected
Inventory Garage Door Opener:
Chamberlain Liftmaster professional - one at each garage door.
129.
Providing great property inspections for every client every time
Page 68 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Recommendations General 18. Entire back balcony off of master bedroom surrounded with louvered shutters. It is assumed that at one time the louvers opened and closed. At this time the louvers will not adjust to open or close, they are either stuck open or stuck closed.. Shutter doors also appear to have opened and closed at one time. At this time the shutter door panels are stuck and will not open. Recommend further evaluation by finished carpenter. Location: Second Floor Porch
130.
131.
FLOORS \ Ceramic tile, stone, marble, etc 19. Condition: Large gouges and voids in Couquina floor tile. Recommend filing and repair by contractor familiar with this type of flooring. Location: First Floor areas
Providing great property inspections for every client every time
Page 69 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
132.
133.
CEILINGS \ Wood 20. Condition: Water stains at ceiling - next to exterior wall under the second floor balcony. Recommend further evaluation by licensed contractor Location: First Floor Dining Room
134.
135.
WINDOWS \ General 21. Condition: Carriage Apartment: Double hung window next to the dining room table is open over an inch and not locked. Not sure if this is how window is supposed to be, recommend further evaluation by speaking with existing owner.
Providing great property inspections for every client every time
Page 70 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
inspectionsbyrandall.com
November 9, 2015
STRUCTURE
ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Location: Second Floor Living Room - Carriage
136.
137.
DOORS \ Doors and frames 22. Condition: Inoperable Both doors to the left and right of the center door could not unlock this door to open appears to be stuck. Recommend further evaluation by finish carpenter Implication(s): Reduced operability Location: Second Floor Master Bedroom
Providing great property inspections for every client every time
Page 71 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
138. Inoperable
139. Inoperable
STAIRS \ Handrails 23. Condition: Missing Standard practice is to have one continuous handrail from top of stairs to the bottom of the stairs. Both flights of stairs do not have this safety feature. Implication(s): Fall hazard
Providing great property inspections for every client every time
Page 72 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
Providing great property inspections for every client every time
Page 73 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
140. Missing hand rail STAIRS \ Spindles or balusters 24. Condition: Loose Newel post is loose recommend further evaluation by finish carpenter Implication(s): Fall hazard Location: Third Floor Bedroom
141. Loose Providing great property inspections for every client every time
Page 74 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
25. Condition: Loose newel posts are loose and wiggle do not feel sturdy recommend further evaluation by finish Implication(s): Fall hazard Location: Second Floor Staircase
142. Wobbles 26. Condition: Loose Spindles and Newel post are loose and wobbly. Recommend further evaluation by licensed contractor Implication(s): Fall hazard Location: First Floor
Providing great property inspections for every client every time
Page 75 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
143. Loose EXHAUST FANS \ Exhaust fan 27. Condition: Inoperative Exhaust fan not operating. Implication(s): Chance of condensation damage to finishes and/or structure Location: Second Floor Master Bathroom EXHAUST FANS \ Kitchen range exhaust system 28. Condition: Damper not working as it should. This photo was taken after exhaust fan was turned off. Recommend further evaluation to adjust damper to close Location: First Floor - exterior
144. Providing great property inspections for every client every time
Page 76 of 78
Report No. 1029
INTERIOR 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
END OF REPORT
Providing great property inspections for every client every time
Page 77 of 78
Report No. 1029
REFERENCE LIBRARY 777 James Bond Way, Rosemary Beach, FL SUMMARY
ROOFING
EXTERIOR
STRUCTURE
inspectionsbyrandall.com
November 9, 2015 ELECTRICAL
HEATING
COOLING
INSULATION
PLUMBING
INTERIOR
REFERENCE
The links below connect you to a series of documents that will help you understand your home and how it works. These are in addition to links attached to specific items in the report. Click on any link to read about that system.
01. ROOFING, FLASHINGS AND CHIMNEYS 02. EXTERIOR 03. STRUCTURE 04. ELECTRICAL 05. HEATING 06. COOLING/HEAT PUMPS 07. INSULATION 08. PLUMBING 09. INTERIOR 10. APPLIANCES 11. LIFE CYCLES AND COSTS 12. SUPPLEMENTARY Asbestos Radon Urea Formaldehyde Foam Insulation (UFFI) Lead Carbon Monoxide Mold Household Pests Termites and Carpenter Ants
13. HOME SET-UP AND MAINTENANCE 14. MORE ABOUT HOME INSPECTIONS
Providing great property inspections for every client every time