INSPECTION REPORT

For the Property at:

777 MOCKINGBIRD LANE SANTA ROSA BEACH, FL 32555

Prepared for: JANE DOE Inspection Date: Thursday, November 12, 2015 Prepared by: Randall Rands

Inspections by Randall LLC 102 Heron turn Panama City Beach, FL 32407 850 714 1955 inspectionsbyrandall.com randall@inspectionsbyrandall.com

Detailed property inspection reports - for information and your safety


January 19, 2016 Dear Jane Doe, RE: Report No. 1030, v.3 777 Mockingbird Lane Santa Rosa Beach, FL 32555 Thanks very much for choosing Inspections by Randall LLC to perform your home inspection. The inspection itself and the attached report comply with the requirements of the Standards of Practice of our national Association. This document defines the scope of a home inspection. Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report. The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein . The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectors cannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. If conditions change, we are available to revisit the property and update our report. The report itself is copyrighted, and may not be used in whole or in part without our express written permission. Again, thanks very much for choosing us to perform your home inspection. Sincerely, Randall Rands on behalf of Inspections by Randall LLC

Inspections by Randall LLC 102 Heron turn Panama City Beach, FL 32407 850 714 1955 inspectionsbyrandall.com randall@inspectionsbyrandall.com


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as a courtesy and cannot be considered a substitute for reading the entire report. Please read the complete document. Priority Maintenance Items

Exterior ROOF DRAINAGE \ Downspouts Condition: Downspouts end too close to building discharge right at building edge is causing erosion suggest further evaluation. to eliminate erosions Implication(s): Chance of water damage to contents, finishes and/or structure Location: Exterior

Providing great property inspections for every client every time

Page 1 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

1. Downspouts end too close to building EXTERIOR GLASS \ Glass (glazing) Condition: Cracked interior panel cracked Implication(s): Cosmetic defects Location: First Floor Kitchen

2. Cracked Providing great property inspections for every client every time

Page 2 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

PORCHES, DECKS, STEPS, PATIOS AND BALCONIES \ Columns Condition: Damage Damaged column base at screened area. Implication(s): Weakened structure | Chance of movement

3. Damage LANDSCAPING \ General Condition: Shrubs at rear of screened pool area are up against the screen. Recommend further evaluation by licensed landscaper

4.

5.

Providing great property inspections for every client every time

Page 3 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Condition: Trees or shrubs too close to building Implication(s): Chance of water damage to contents, finishes and/or structure | Chance of pests entering building | Material deterioration

6. Trees or shrubs too close to building

7. Trees or shrubs too close to building

Providing great property inspections for every client every time

Page 4 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

GARAGE \ Walls and ceilings Condition: Vehicle damage to wall at auto stall closest to street

8. GARAGE \ Vehicle door operators Condition: Inoperative garage door closest to the street failed to operate with electric door opener recommend further evaluation by a licensed garage door installer Implication(s): System inoperative

9. Inoperative

Providing great property inspections for every client every time

Page 5 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Electrical OPTIONAL \ Electrical Condition: Other First floor auxiliary panel in utility/weight room has several connections with wire nuts, but wire nuts mix different size wires and different colors of wires. Recommend further evaluation by licensed electrician Location: First Floor Utility Room

10. mixed wires

11. mixed wires

Condition: Other Bonus room has three outlets that have a neutral and hot reversed. These are the three outlets located on the walls to the left of the mirrored slider door

Providing great property inspections for every client every time

Page 6 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

12. Reversed lines

13. Reversed lines

Condition: Other No GFCI outlet located next to sinks in the two upstairs bathrooms. The master bath has this feature. Standard practice is to have GFCI installed for safety reasons.

14. Other

Providing great property inspections for every client every time

Page 7 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

DISTRIBUTION SYSTEM \ Lights Condition: Inoperative Lights over vanity and half bath off of pool area do not operate suggest further evaluation by licensed electrician Implication(s): Inadequate lighting DISTRIBUTION SYSTEM \ Outlets (receptacles) Condition: Inoperative Half bath off of pool area the GFCI outlet does not have any power. Recommend further evaluation by a licensed electrician Implication(s): Equipment inoperative Location: First Floor Bathroom Condition: No GFCI (Ground Fault Circuit Interrupter) Non GFCI outlets at the exterior. Standard practice for safety reasons is that all exterior outlets be GFCI protected to prevent shock hazards to people using outdoor electrical equipment. Recommend further evaluation by licensed electrician Implication(s): Electric shock

Providing great property inspections for every client every time

Page 8 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

15. No GFI (Ground Fault Interrupter)

16. No GFI (Ground Fault Interrupter) DISTRIBUTION SYSTEM \ Cover plates Condition: Missing Convenience outlets in cabinet for stereo and TV system do not have covers. Recommend further evaluation by licensed electrician Implication(s): Electric shock Location: First Floor Family Room

17. Missing

Providing great property inspections for every client every time

Page 9 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Plumbing FIXTURES AND FAUCETS \ Basin, sink and laundry tub Condition: cold water faucet not working Location: First Floor Utility Room

18. Condition: Leak Leak in plumbing under sink when disposer is run. Bottom of cabinet has water damage. Recommend further evaluation by licensed plumber Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the building Location: First Floor Kitchen

Providing great property inspections for every client every time

Page 10 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

19. Leak

20. Water damage

Interior OPTIONAL \ Interior Condition: Other exhaust fan has spots of mold at ceiling surrounding the fan at ceiling recommend further evaluation why this may be occurring Location: Second Floor Master Bathroom

Providing great property inspections for every client every time

Page 11 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

21. Other CARPENTRY \ Cabinets Condition: Mother in law apartment vinyl laminate on door is delaminating at the edges of this one door Location: First Floor Bathroom

22.

23.

Providing great property inspections for every client every time

Page 12 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

EXHAUST FANS \ Kitchen range exhaust system Condition: Inoperative The fan of the range exhaust unit that will rise from the counter to exhaust fumes from the range the exterior. To operate fan - push button - will not operate. recommend further evaluation and by licensed electrician and also the exhaust to the exterior needs to be maintained by removal of leaf debris over the screen. Implication(s): Equipment inoperative

24. Inoperative APPLIANCES \ Waste disposal Condition: Inoperative Vegetable washing sink disposer not operating Implication(s): Equipment inoperative Location: First Floor Kitchen

Providing great property inspections for every client every time

Page 13 of 88


Report No. 1030, v.3

SUMMARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

25. Inoperative This concludes the Summary section. The remainder of the report describes each of the home's systems and also details any recommendations we have for improvements. Limitations that restricted our inspection are included as well. The suggested time frames for completing recommendations are based on the limited information available during a pre-purchase home inspection. These may have to be adjusted based on the findings of specialists. Home Improvement - ballpark costs

Providing great property inspections for every client every time

Page 14 of 88


Report No. 1030, v.3

ROOFING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General:

powered roof vents

26. General:

27. gas vent at roof measures 26 inches above roof surface

28. Providing great property inspections for every client every time

Page 15 of 88


Report No. 1030, v.3

ROOFING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

General:

flashing at curved entry pediment

30.

29. General: there is roof granule build up in the gutters, not excessive typical for a roof of this age, this granule deterioration suggest that this is the original roof would be 13 years old. Architectural grade roofing is warranted for 30 years

Providing great property inspections for every client every time

Page 16 of 88


Report No. 1030, v.3

ROOFING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

31. General:

two and a half inch roofing nails at 6 inches on center

32.

Providing great property inspections for every client every time

Page 17 of 88


Report No. 1030, v.3

ROOFING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Sloped roofing material: Asphalt shingles

33. Asphalt shingles Sloped roof flashing material: Flat roofing material:

Aluminum

elastomeric single-ply

34. Probability of leakage:

Low

Providing great property inspections for every client every time

Page 18 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General: Pool enclosures and pools are not part of recommended minimum standards for inspection. Visual inspection shows the screening and the structure along with the pool and it's equipment appears to be in excellent condition

36.

35.

37. General:

Location of 3 electric sprinkler controllers

Providing great property inspections for every client every time

Page 19 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

38. General:

Wood fireplace chimney and spark arrestor

39. General:

40. Screened pool area as seen from roof

Providing great property inspections for every client every time

Page 20 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

41. General:

Weep holes in brick have insect screening.

42. General:

Gas meter and shut off

Providing great property inspections for every client every time

Page 21 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

43. General: This duct is the exhaust from the non-working kitchen exhaust. Maintenance needed to keep the screen from being covered with leaves and other debris.

44. General:

45. bait stations located in various areas around exterior wall, these are for rats and mice

Providing great property inspections for every client every time

Page 22 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

46. General:

Drain piping at exterior wall, not clear what it is connected to in the house.

47. General: Exhaust duct damper missing, needs to be replaced to prevent rodents and insects from entering the home and loss of Interior conditioned air.

Providing great property inspections for every client every time

Page 23 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

48. General: Downspout leader has been crushed, recommend replacement to allow for rainwater to flow without backing up in downspout.

49. General: Recommend calling one hour air conditioning and heating / label to see if there may be a transferable 10 year warranty that could be transferred to new homeowner.

Providing great property inspections for every client every time

Page 24 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

50. General:

Front elevation

51. General: Decorative lintel band notched to allow for refrigerant lines for heat pump number 4 to access the second floor. Closely inspected and appears to not have any water damage or deterioration recommend further investigation to seal the gaps between the conduit and that decorative lintel piece

Providing great property inspections for every client every time

Page 25 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

52. General:

Rear elevation

53. Gutter & downspout material: Gutter & downspout type:

Aluminum

Eave mounted

Gutter & downspout discharge:

Above grade

Downspout discharge: Some downspouts (these two are on the back of the house) go underground but inspection did not reveal what they connect to underground or where the ends may light.

Providing great property inspections for every client every time

Page 26 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

54.

55.

Downspout discharge: Above grade Some downspouts have extensions to direct water away from foundation, others do not.

56. Above grade Lot slope:

Away from building

Wall surfaces - masonry:

Stucco

Providing great property inspections for every client every time

Page 27 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

57. Wall surfaces - masonry:

Painted Brick

58. Soffit and fascia: Vinyl Vented vinyl soffit

Providing great property inspections for every client every time

Page 28 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

59. Vinyl Driveway: Concrete

60. Concrete

61. Concrete

Providing great property inspections for every client every time

Page 29 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

62. Concrete Walkway:

63. Concrete

Tile

64. Patio: screen door pool access doors latches are located 55 inches above grade. Locks and closers are in working condition.

Providing great property inspections for every client every time

Page 30 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

65.

66.

Patio: Concrete Pool patio is textured concrete

67. Concrete

Providing great property inspections for every client every time

Page 31 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Garage: General 3 garage doors rated with a designed wind pressure of + 25 pounds per square foot and -25 pounds per square foot

68. General

69. General

Recommendations ROOF DRAINAGE \ Downspouts 1. Condition: Downspouts end too close to building discharge right at building edge is causing erosion suggest further evaluation. to eliminate erosions Implication(s): Chance of water damage to contents, finishes and/or structure Location: Exterior

Providing great property inspections for every client every time

Page 32 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

70. Downspouts end too close to building EXTERIOR GLASS \ Glass (glazing) 2. Condition: white powdery stains on glass are dirt and just need cleaning to be removed Location: Second Floor Master Bedroom

Providing great property inspections for every client every time

Page 33 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

71. 3. Condition: Cracked interior panel cracked Implication(s): Cosmetic defects Location: First Floor Kitchen

72. Cracked DOORS \ General 4. Condition: two of the French doors will not operate the hardware for locking them is in need of repair recommend further evaluation by door professional Location: First Floor Living Room

Providing great property inspections for every client every time

Page 34 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

73. PORCHES, DECKS, STEPS, PATIOS AND BALCONIES \ Columns 5. Condition: Damage Damaged column base at screened area. Implication(s): Weakened structure | Chance of movement

74. Damage LANDSCAPING \ General 6. Condition: Shrubs at rear of screened pool area are up against the screen. Recommend further evaluation by licensed landscaper

Providing great property inspections for every client every time

Page 35 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

75. 7. Condition:

76. elephant ear plants are poisonous verify with landscaper if this is one of those poisonous plants

77. 8. Condition: Trees or shrubs too close to building Implication(s): Chance of water damage to contents, finishes and/or structure | Chance of pests entering building | Material deterioration

Providing great property inspections for every client every time

Page 36 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

78. Trees or shrubs too close to building

79. Trees or shrubs too close to building

GARAGE \ Walls and ceilings 9. Condition: Vehicle damage to wall at auto stall closest to street

Providing great property inspections for every client every time

Page 37 of 88


Report No. 1030, v.3

EXTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

80. GARAGE \ Vehicle door operators 10. Condition: Inoperative garage door closest to the street failed to operate with electric door opener recommend further evaluation by a licensed garage door installer Implication(s): System inoperative

81. Inoperative

Providing great property inspections for every client every time

Page 38 of 88


Report No. 1030, v.3

STRUCTURE 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Configuration:

Slab-on-grade

Foundation material: Floor construction:

Poured concrete Concrete

Exterior wall construction: Wood frame, brick veneer Combination of brick veneer and stucco

82. Wood frame, brick veneer

83. Wood frame, brick veneer

Roof and ceiling framing: Trusses Engineered trusses at 24" o.c.

Providing great property inspections for every client every time

Page 39 of 88


Report No. 1030, v.3

STRUCTURE 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

84. Trusses

Providing great property inspections for every client every time

Page 40 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General: assume these wires are for Electrical sprinkler controllers one is in conduit the other is not recommend for the evaluation by licensed electrician or Landscaping professional

85. General:

Electrical shutoff for exterior compressor

Providing great property inspections for every client every time

Page 41 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

86. General:

attic exhaust fan with electronic controller

87. General:

Electric generator option: secondary auxiliary panel in the utility room / weight room

Providing great property inspections for every client every time

Page 42 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

88. General:

89. surge protector system

90. General: third auxiliary panel this one located next to the main distribution panel on the exterior wall. identification of circuit breakers is faded and can't be read read very easily recommend rewriting those with a indelible marker

Providing great property inspections for every client every time

Page 43 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

91.

92.

Service entrance cable and location: Service size:

Underground - not visible

400 Amps (240 Volts)

Main disconnect/service box rating: 400 Amps Copper and aluminum main distribution wiring

Providing great property inspections for every client every time

Page 44 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

93. 400 Amps

94. 400 Amps

Main disconnect/service box type and location:

Breakers -exterior wall

System grounding material and type: Copper - other Copper ground wire goes into the ground but could not find the end of it where would be attached to ground rod

95. Copper - other Distribution panel rating:

400 Amps

Distribution panel type and location:

Breakers

Providing great property inspections for every client every time

Page 45 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Auxiliary panel (subpanel) rating:

200 Amps

Auxiliary panel (subpanel) type and location: Breakers - utility room Downstairs auxiliary panel

96. Breakers - utility room Distribution wire material and type:

97. Breakers - utility room Copper - non-metallic sheathed

Type and number of outlets (receptacles):

Grounded - typical

Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI):

GFCI in master bathroom

Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI):

GFCI - garage

Smoke detectors:

GFCI - kitchen

Present

Limitations System ground: stains on ceiling adjacent to this fixture Moisture Meter shows elevated moisture levels where stain is occurring recommend further evaluation

Providing great property inspections for every client every time

Page 46 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

98.

99.

Recommendations OPTIONAL \ Electrical 11. Condition: Other First floor auxiliary panel in utility/weight room has several connections with wire nuts, but wire nuts mix different size wires and different colors of wires. Recommend further evaluation by licensed electrician Location: First Floor Utility Room

Providing great property inspections for every client every time

Page 47 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

100. mixed wires

101. mixed wires

12. Condition: Other Bonus room has three outlets that have a neutral and hot reversed. These are the three outlets located on the walls to the left of the mirrored slider door

102. Reversed lines

103. Reversed lines

Providing great property inspections for every client every time

Page 48 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

13. Condition: Other No GFCI outlet located next to sinks in the two upstairs bathrooms. The master bath has this feature. Standard practice is to have GFCI installed for safety reasons.

104. Other 14. Condition: Other Outlets in garage are connected to the GFCI which is correct but having a refrigerator plugged into a GFCI is not standard practice when GFCI is tripped your refrigerator will be turned off. dedicated circuit is recommended for all refrigerators that are in garages

105. Ref on GFCI DISTRIBUTION SYSTEM \ Lights 15. Condition: Inoperative

Providing great property inspections for every client every time

Page 49 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Lights over vanity and half bath off of pool area do not operate suggest further evaluation by licensed electrician Implication(s): Inadequate lighting DISTRIBUTION SYSTEM \ Outlets (receptacles) 16. Condition: Inoperative Half bath off of pool area the GFCI outlet does not have any power. Recommend further evaluation by a licensed electrician Implication(s): Equipment inoperative Location: First Floor Bathroom 17. Condition: No GFCI (Ground Fault Circuit Interrupter) Non GFCI outlets at the exterior. Standard practice for safety reasons is that all exterior outlets be GFCI protected to prevent shock hazards to people using outdoor electrical equipment. Recommend further evaluation by licensed electrician Implication(s): Electric shock

Providing great property inspections for every client every time

Page 50 of 88


Report No. 1030, v.3

ELECTRICAL 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

106. No GFI (Ground Fault Interrupter)

107. No GFI (Ground Fault Interrupter) DISTRIBUTION SYSTEM \ Cover plates 18. Condition: Missing Convenience outlets in cabinet for stereo and TV system do not have covers. Recommend further evaluation by licensed electrician Implication(s): Electric shock Location: First Floor Family Room

108. Missing

Providing great property inspections for every client every time

Page 51 of 88


Report No. 1030, v.3

HEATING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Fuel/energy source: System type:

Electricity

Heat pump

Heat distribution: Ducts and registers

109. Ducts and registers

110. Ducts and registers

Ducts and registers Efficiency: High-efficiency Three of the units are 14 seer in the older unit is a 13 seer heat pump

Limitations Warm weather: Prevented testing in heating mode Heating may only be tested when the exterior temperature is 65 degrees or lower.

Providing great property inspections for every client every time

Page 52 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General:

Heat pump label on number 2

111. General:

heat pumps label on number 3

112. General:

insulation seems to be intact

Providing great property inspections for every client every time

Page 53 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

113. General:

Pipe insulation should be repaired as there are some places that are missing insulation.

114. General:

heat pump number 4 on the back side of the garage. this unit is a 13 seer Goodman umit

Providing great property inspections for every client every time

Page 54 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

115. General:

116. heat pump label on unit number 4

117.

118.

Providing great property inspections for every client every time

Page 55 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

General:

Refrigerant lines and condensation pipe as they enter and exit the exterior of the bonus room.

119. General:

Heat pump label on unit 1 - this is the main house unit with the air handler upstairs.

120.

Providing great property inspections for every client every time

Page 56 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

General:

Heat pump at lower floor 57째 supply air 72 degree return air

General:

Heat pump in mother-in-law apartment has a supply temperature of 60 degrees and a return of 73 degrees

General: Ceiling filter appears to be reusable unit. Installed by one hour air. Recommend contacting one hour for further information regarding maintenance and operation.

121. General: degrees

122.

heat pump located in the bonus room has a supply temperature of 63 degrees and a return temperature of 74

123.

Providing great property inspections for every client every time

Page 57 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

General:

Labels on air handler in bonus room

124. Air conditioning type:

125. Air cooled

Heat pump type: Air source

Providing great property inspections for every client every time

Page 58 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

126. Air source

127. Air source

Manufacturer: Amana There are four compressor units located on the exterior one on the west side and three on the east side. All manufactured by the same manufacturer which is Goodman and under the Amana label. Three are 14 seer and newer units, the fourth is a 13 seer unit and installed when the home was built in 2002. All units use r410a refrigerant

Providing great property inspections for every client every time

Page 59 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

128. Amana/Goodman

129. Amana/Goodman

Goodman Largest HVAC unit is 14 seer with r410a refrigerant

130. Goodman

131. Goodman

Providing great property inspections for every client every time

Page 60 of 88


Report No. 1030, v.3

COOLING & HEAT PUMP 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Compressor type:

Gas

Failure probability: The HVAC unit that is the oldest, which is the one serving the bonus room is 12 years old. It is getting close to end of it's useful life - it may not have been used as much as the other heat pumps and that may be why it has not been replaced. The other 3 HVAC units are 6, 3, & 3 years old. It is recommended that when a unit gets 10 years old to start budgeting to replace it as one never knows when the unit may fail. Since three of the units have been replaced, one can calculate how long the original installations lasted. One init was probably installed in 2010 - so the one before it lasted 8 years. The newest two units were installed in 2012 - so the units these replaced lasted 10 years. Temperature difference: return air temperature.

All units showed acceptable temperature differences between supply air temperature and

Providing great property inspections for every client every time

Page 61 of 88


Report No. 1030, v.3

INSULATION AND VENTILATION 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description Attic/roof insulation material: Cellulose 16 inches of cellulose and fiberglass mix insulation. 8" of fiberglass underneath 8" if cellulose.

132. Cellulose over 8" of fiberglass Attic/roof air/vapor barrier: Wall insulation material:

133. Cellulose over 8" of fiberglass

None found

Spray Foam used in bonus room

134.

Providing great property inspections for every client every time

Page 62 of 88


Report No. 1030, v.3

INSULATION AND VENTILATION 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Floor above porch/garage insulation material: Mechanical ventilation system for home:

Not determined

Kitchen exhaust fan

Bathroom exhaust fan

Providing great property inspections for every client every time

Page 63 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General: control.

These appear to be to water shut off valves, verify with owner or licensed plumber as to what these valves

135. General:

Typical plumbing roof vent

Providing great property inspections for every client every time

Page 64 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

136. Water supply source:

Public

Service piping into building: Supply piping in building:

Copper

Copper

Main water shut off valve at the:

Not located

Water heater fuel/energy source: Gas

Providing great property inspections for every client every time

Page 65 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

137. Gas

138. Gas

139. Gas Water heater type: Conventional One water heater is gas for the house and one water heater for the mother-in-law apartment is electric

Providing great property inspections for every client every time

Page 66 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Water heater exhaust venting method: Natural draft Gas water heater has natural draught through the roof Water heater manufacturer: Rheem Both water heaters are manufactured by Reem Water heater approximate age:

13 years

Hot water circulating system: Present

140. Present Waste disposal system:

Public

Waste and vent piping in building: PVC plastic

Providing great property inspections for every client every time

Page 67 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

141. PVC plastic Main fuel shut off valve at the: West Gas shutoff valve located next to gas meter in the northwest side Exterior hose bibb:

Present

Limitations Items excluded from a building inspection:

Water heater relief valves are not tested

Recommendations OPTIONAL \ Plumbing 19. Condition: no stopper in sink

Providing great property inspections for every client every time

Page 68 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

142. FIXTURES AND FAUCETS \ Basin, sink and laundry tub 20. Condition: cold water faucet not working Location: First Floor Utility Room

143. 21. Condition: Leak Leak in plumbing under sink when disposer is run. Bottom of cabinet has water damage. Recommend further evaluation by licensed plumber Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the building

Providing great property inspections for every client every time

Page 69 of 88


Report No. 1030, v.3

PLUMBING 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Location: First Floor Kitchen

144. Leak

145. Water damage

Providing great property inspections for every client every time

Page 70 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Description General: capped

Wood burning fireplace with flue damper, has been plumbed with gas pipe to the fire box - gas piping is

146. General:

147. Tag for Maytag wall oven unit shows manufacturing date of July 2002

148. General: Whole house vacuum - every vacuum outlet was not tested - however the two "baseboard" vacu um intakes operated when rocker switch was rotated.

Providing great property inspections for every client every time

Page 71 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

149. General:

150.

Ceiling stain at duct work boot shows no sign of moisture

151.

Providing great property inspections for every client every time

Page 72 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

152. Major floor finishes: Carpet

153. Carpet Hardwood

Providing great property inspections for every client every time

Page 73 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

154. Hardwood

155. Hardwood

Tile Larger tile used in main house

156. Tile

157. Tile

Tile Smaller tile used in the mother in law apartment

Providing great property inspections for every client every time

Page 74 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

158. Tile Major wall finishes:

Gypsum board

Major ceiling finishes:

Gypsum board

Windows: Single/double hung Lower unit operates, all are hard to move up and down, recommend lubricating with silicone spray

159. Single/double hung Glazing:

Double

Providing great property inspections for every client every time

Page 75 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Exterior doors - type/material: French Three French doors to pool from living room

160. French Solid wood Entry doors solid wood panel

161. Solid wood Doors:

aluminum patio door from family room to the pool

Providing great property inspections for every client every time

Page 76 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

162. Doors:

sliding glass door from mother-in-law apartment to the pool deck

Oven type: Conventional Conventional electric oven for lower unit

163. Conventional Convection Maytag - Electric convection oven on top unit - Manufactured July 2002

Providing great property inspections for every client every time

Page 77 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

164. Convection Oven fuel:

Electricity

Range fuel: Gas KitchenAid 5 burner gas range gas is turned off therefore burners could not be tested the igniters did make a snapping noise when regulators were set to lite

165. Gas Appliances: Exterior Kitchen: Jenn-air with rotisserie 5 burner gas barbecue at exterior kitchen testing appears to be in working order not rusted through could not get a burner to light since the gas has been turned off to the house.

Providing great property inspections for every client every time

Page 78 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

166.

167.

Appliances: Exterior Kitchen: Fire Magic ultimate BBQ gas burner. instructions for lighting hard to read due to dirt and debris on instruction panel

168.

169.

Providing great property inspections for every client every time

Page 79 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Appliances: Refrigerator Refrigerator at pool

170. Refrigerator

171. Refrigerator

Refrigerator Samsung French door refrigerator: Manufactured Sept of 2014

172. Refrigerator

173. Refrigerator Providing great property inspections for every client every time

Page 80 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Refrigerator Mother-in-law apartment LG French door refrigerator. Manufactured October 2007

174. Refrigerator

175. Refrigerator

Dishwasher Mother-in-law apartment KitchenAid dishwasher. Manufactured June 2008

176. Dishwasher

177. Dishwasher

Providing great property inspections for every client every time

Page 81 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

Dishwasher Bosch dishwasher silence Plus 44 DBA - Manufactured April 2015

178. Dishwasher

179. Dishwasher

Microwave oven Mother-in-law apartment microwave. GE Spacemaker XL 1800 - manufactured 2002

180. Microwave oven Laundry facilities:

mother-in-law washer and dryer facilities

Providing great property inspections for every client every time

Page 82 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

181. Laundry facilities:

Hot/cold water supply

Vented to outside

120-Volt outlet

240-Volt outlet

Kitchen ventilation: Discharges to exterior Not working Bathroom ventilation:

Exhaust fan

Laundry room ventilation: Counters and cabinets:

Clothes dryer vented to exterior

None

Counters in kitchen are granite

182. Counters and cabinets:

counters at exterior kitchen are solid

Providing great property inspections for every client every time

Page 83 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

183. Stairs and railings:

Inspected

Inventory Garbage disposal: In-sink-erator (ISE) Used at the main kitchen sink and at the vegetable washing sink in the island

Recommendations OPTIONAL \ Interior 22. Condition: Other exhaust fan has spots of mold at ceiling surrounding the fan at ceiling recommend further evaluation why this may be occurring Location: Second Floor Master Bathroom

Providing great property inspections for every client every time

Page 84 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

inspectionsbyrandall.com

HEATING

COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

184. Other CARPENTRY \ Cabinets 23. Condition: Mother in law apartment vinyl laminate on door is delaminating at the edges of this one door Location: First Floor Bathroom

185.

186.

Providing great property inspections for every client every time

Page 85 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

EXHAUST FANS \ Kitchen range exhaust system 24. Condition: Inoperative The fan of the range exhaust unit that will rise from the counter to exhaust fumes from the range the exterior. To operate fan - push button - will not operate. recommend further evaluation and by licensed electrician and also the exhaust to the exterior needs to be maintained by removal of leaf debris over the screen. Implication(s): Equipment inoperative

187. Inoperative APPLIANCES \ Refrigerator 25. Condition: mother inlaw apartment crack in plastic lower bin

Providing great property inspections for every client every time

Page 86 of 88


Report No. 1030, v.3

INTERIOR 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

188. APPLIANCES \ Waste disposal 26. Condition: Inoperative Vegetable washing sink disposer not operating Implication(s): Equipment inoperative Location: First Floor Kitchen

189. Inoperative END OF REPORT

Providing great property inspections for every client every time

Page 87 of 88


Report No. 1030, v.3

REFERENCE LIBRARY 777 Mockingbird Lane, Santa Rosa Beach, FL

November 12, 2015

SUMMARY

ELECTRICAL

ROOFING

EXTERIOR

STRUCTURE

HEATING

inspectionsbyrandall.com COOLING

INSULATION

PLUMBING

INTERIOR

REFERENCE

The links below connect you to a series of documents that will help you understand your home and how it works. These are in addition to links attached to specific items in the report. Click on any link to read about that system.

01. ROOFING, FLASHINGS AND CHIMNEYS 02. EXTERIOR 03. STRUCTURE 04. ELECTRICAL 05. HEATING 06. COOLING/HEAT PUMPS 07. INSULATION 08. PLUMBING 09. INTERIOR 10. APPLIANCES 11. LIFE CYCLES AND COSTS 12. SUPPLEMENTARY Asbestos Radon Urea Formaldehyde Foam Insulation (UFFI) Lead Carbon Monoxide Mold Household Pests Termites and Carpenter Ants

13. HOME SET-UP AND MAINTENANCE 14. MORE ABOUT HOME INSPECTIONS

Providing great property inspections for every client every time

Page 88 of 88