Low voltage cables

Page 1

XHHW-2 Cables

Cross (X) Linked Polyethylene Insulation, High Heat resistant (90째C), 2: Suitable for Dry and Wet Locations

Description Soft copper conductor, XLPE insulated.

Construction Conductor Compressed Stranded Soft copper. Insulation Cross Linked Polyethylene (XLPE 90째C). Options Aluminum Conductor, XLPE SR (Sunlight resistant) insulation. For sizes greater than 1/0 AWG, Type Tray Cable (TC).

Characteristics Operating temperature Dry Locations: 90째C Wet Locations: 90째C Operating Voltage 600 V.

Uses and Applications Overhead distribution of electric energy in low voltage systems. Connection to boards, motors, and building wiring. Installation ducts and raceways. Abrasion and moisture resistant insulation, its dimensions permits optimal filled in tubes and ducts. Pass VW-1 Vertical flame Test.

7


Standards and Specifications CENTELSA XHHW-2 cables are manufacturing according to the following standards: ASTM B3, NTC-ICONTEC 359. Soft copper wire. ASTM B8, NTC-ICONTEC 307. Concentric Lay Stranded copper conductors. ASTM B787. 19 Wire Combination Unilay Stranded Copper conductors for subsequent insulation UL 1581, NTC-3203. Reference Standard for Electrical Wires, Cables and Flexible Cords. UL 44, NTC-3277. Thermo set-Insulated Wires and Cables.

Certifications CENTELSA XHHW-2 Cables type, are certified by: UL 44 File E137698.

Note: Other configurations and sizes not specified herein are available upon request.

8


Cables Type XHHW-2 600V (International Unit System) Cross (X) Linked Polyethylene Insulation, High Heat resistant (90°C), 2: Suitable for Dry and Wet Locations Manufacturing Standards: UL 44, NTC-3277. Thermo set-Insulated Wires and Cables. SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 Notes:

STRANDS STRANDING No. CLASS

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

CROSS SECTION (mm2)

2.08 3.31 5.26 8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4 304.0 354.7 380.0 405.4 456.0 506.7

CONDUCTOR INSULATION DIAMETER THICKNESS (mm) (mm)

1.79 2.25 2.85 3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04 22.00 23.75 24.59 25.39 26.94 28.38

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 2.03 2.03 2.03 2.03 2.03 2.03

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

3.39 3.85 4.45 5.97 6.90 8.09 9.58 11.10 12.10 13.23 14.50 15.92 17.62 18.96 20.22 21.38 23.48 26.18 27.93 28.77 29.57 31.12 32.56

26 39 58 96 146 223 344 435 541 674 841 1051 1248 1487 1725 1963 2437 2939 3412 3649 3886 4358 4830

DC RESISTANT AMPACITY² (A)3 AT 20°C¹ (ohm/km)

8.45 5.31 3.34 2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694 0.0578 0.0496 0.0463 0.0434 0.0386 0.0347

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

AMPACITY² (A)4

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. 90°C conductor temperature, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

9


Cables Type XHHW-2 600V Cross (X) Linked Polyethylene Insulation, High Heat resistant (90°C), 2: Suitable for Dry and Wet Locations Manufacturing Standards: UL 44, NTC-3277. Thermo set-Insulated Wires and Cables. SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

STRANDS STRANDING No. (mils)

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B Notes:

10

CROSS SECTION (sq inches)

0.00323 0.00513 0.00815 0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393 0.471 0.550 0.589 0.628 0.707 0.785

CONDUCTOR INSULATION DIAMETER THICKNESS (mils) (mils)

70 89 112 141 178 225 283 322 361 406 456 512 558 611 661 706 789 866 935 968 1000 1061 1117

30 30 30 45 45 45 45 55 55 55 55 55 65 65 65 65 65 80 80 80 80 80 80

DIAMETER APPROX. OVER TOTAL INSULATION WEIGHT (mils) (pound/1000ft)

133 152 175 235 272 318 377 437 476 521 571 627 694 747 796 842 924 1031 1100 1133 1164 1225 1282

18 26 39 65 98 150 231 292 364 453 565 707 838 999 1159 1319 1638 1975 2293 2452 2611 2929 3246

DC RESISTANT AMPACITY² (A)3 AT 20°C¹ (ohm/1000ft)

2.58 1.62 1.02 0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212 0.0176 0.0151 0.0141 0.0132 0.0118 0.0106

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. 90°C conductor temperature, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

AMPACITY² (A)4

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615


RHH/RHW2/USE-2 Cables Rubber or Thermoset Insulation, High Heat Resistant (90°C) for Dry Locations Rubber or Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations Underground Service Entrance Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations

Description Soft copper conductor, XLPE insulated.

Construction Conductor Compressed Stranded Soft copper. Insulation Cross Linked Polyethylene (XLPE 90°C). Options Aluminum Conductor, XLPE SR (Sunlight resistant) insulation. For sizes greater than 1/0 AWG, Type Tray Cable (TC).

Characteristics Operating temperature Dry locations, RHH, RHW-2 and USE-2 90°•'3fC. Wet locations, RHW-2 and USE-2 90°•'3fC. Wet locations, RHH 75°C. Operating Voltage 600 V, RHH, RHW-2 and USE-2. 2000 V, RHH y RHW-2. 11


Uses and Applications General purpose for power and control circuits, industrial and building wiring. When used as USE-2 conductor, can be installed in underground service entrance and in directed buried. Abrasion and moisture resistant insulation, its dimensions permits optimal filled in tubes and ducts. Pass VW-1 Vertical flame Test.

Standards and Specifications ASTM B3, NTC-ICONTEC 359. Soft copper wire. ASTM B8, NTC-ICONTEC 307. Concentric Lay Stranded copper conductors. ASTM B787. 19 Wire Combination Unilay Stranded Copper conductors for subsequent insulation UL 1581, NTC-3203. Reference Standard for Electrical Wires, Cables and Flexible Cords. UL 44, NTC-3277. Thermo set-Insulated Wires and Cables.

Certifications CENTELSA RHH / RHW-2 / USE-2 Cables type, are certified by: UL 44 File E137698, for RHH y RHW-2. UL 854 File E207803, for USE-2. Note: Other configurations and sizes not specified herein are available upon request.

12


Cables Type RHH / RHW-2 / USE-2 600V (Internacional Unit System) Rubber or Thermoset Insulation, High Heat Resistant (90°C) for Dry Locations Rubber or Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations Underground Service Entrance Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations Manufacturing Standard: UL 44, NTC-3277. Thermo set-Insulated Wires and Cables. UL 854, NTC-4564 Service entrance Cables (For USE-2) SIZE AWG / kcmil

STRANDS No.

STRANDING CLASS

CROSS SECTION (mm²)

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

2.08 3.31 5.26 8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4 304.0 354.7 380.0 405.4 456.0 506.7

Notes:

CONDUCTOR INSULATION DIAMETER THICKNESS (mm) (mm)

1.79 2.25 2.85 3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04 22.00 23.75 24.59 25.39 26.94 28.38

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41 2.79 2.79 2.79 2.79 2.79 2.79

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

4.17 4.63 5.23 6.75 7.68 8.87 10.36 12.36 13.36 14.49 15.76 17.18 19.14 20.48 21.74 22.90 25.00 27.74 29.49 30.33 31.13 32.68 34.12

31 44 65 105 155 234 357 460 568 704 873 1086 1295 1537 1779 2019 2499 3009 3488 3727 3965 4442 4917

DC RESISTANCE AMPACITY² (A)3 AT 20°C 1 (ohm/km)

8.45 5.31 3.34 2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694 0.0578 0.0496 0.0463 0.0434 0.0386 0.0347

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

AMPACITY² (A)4

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. 90°C conductor temperature, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

13


Cables Type RHH / RHW-2 / USE-2 600V Rubber or Thermoset Insulation, High Heat Resistant (90°C) for Dry Locations Rubber or Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations Underground Service Entrance Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations Manufacturing Standard: UL 44, NTC-3277. Thermo set-Insulated Wires and Cables. UL 854, NTC-4564 Service entrance Cables (For USE-2).

SIZE AWG / kcmil

STRANDS No.

STRANDING CLASS (mils)

CROSS SECTION (sq inches)

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

0.00323 0.00513 0.00815 0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393 0.471 0.550 0.589 0.628 0.707 0.785

Notes:

14

CONDUCTOR INSULATION DIAMETER THICKNESS (mils) (mils)

70 89 112 141 178 225 283 322 361 406 456 512 558 611 661 706 789 866 935 968 1000 1061 1117

45 45 45 60 60 60 60 80 80 80 80 80 95 95 95 95 95 110 110 110 110 110 110

DIAMETER APPROX. DC RESISTANCE AMPACITY² OVER TOTAL (A)3 AT 20°C 1 INSULATION WEIGHT (ohm/1000ft) (mils) (pounds/1000ft)

164 182 206 266 303 349 408 487 526 571 620 676 753 806 856 901 984 1092 1161 1194 1226 1287 1343

21 30 44 70 104 157 240 309 382 473 587 730 870 1033 1195 1357 1680 2022 2344 2504 2665 2985 3305

2.58 1.62 1.02 0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212 0.0176 0.0151 0.0141 0.0132 0.0118 0.0106

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. 90°C conductor temperature, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

AMPACITY² (A)4

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615


Cables Type RHH / RHW-2 / USE-2 2000V (Internacional Unit System) Rubber or Thermoset Insulation, High Heat Resistant (90°C) for Dry Locations. Rubber or Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations. Manufacturing Standard: UL 44, NTC-3277. Thermo set-Insulated Wires and Cables. SIZE AWG / kcmil

STRANDS No.

STRANDING CLASS

CROSS SECTION (mm²)

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

2.08 3.31 5.26 8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4 304.0 354.7 380.0 405.4 456.0 506.7

CONDUCTOR INSULATION DIAMETER THICKNESS (mm) (mm)

1.79 2.25 2.85 3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04 22.00 23.75 24.59 25.39 26.94 28.38

1.52 1.52 1.52 1.78 1.78 1.78 1.78 2.29 2.29 2.29 2.29 2.29 2.67 2.67 2.67 2.67 2.67 3.05 3.05 3.05 3.05 3.05 3.05

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

4.95 5.41 6.01 7.29 8.22 9.41 10.90 12.90 13.90 15.03 16.30 17.72 19.68 21.02 22.28 23.44 25.54 28.28 30.03 30.87 31.67 33.22 34.66

37 51 72 111 163 242 367 471 580 717 888 1102 1312 1556 1799 2040 2522 3035 3515 3754 3994 4472 4948

DC RESISTANCE AMPACITY² (A)3 AT 20°C 1 (ohm/km)

8.45 5.31 3.34 2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694 0.0578 0.0496 0.0463 0.0434 0.0386 0.0347

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

AMPACITY² (A)4

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. T90°C conductor temperature, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

15


Cables Type RHH / RHW-2 / USE-2 2000V Rubber or Thermoset Insulation, High Heat Resistant (90°C) for Dry Locations. Rubber or Thermoset Insulation, Heat Resistant (90°C), 2: Suitable for Dry and Wet Locations.

Manufacturing Standard: UL 44, NTC-3277. Thermo set-Insulated Wires and Cables. SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

STRANDS No.

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

STRANDING CLASS

CROSS SECTION (mils)

B B B B B B B B B B B B B B B B B B B B B B B

0.00323 0.00513 0.00815 0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393 0.471 0.550 0.589 0.628 0.707 0.785

CONDUCTOR INSULATION DIAMETER THICKNESS (mils) (mils)

70 89 112 141 178 225 283 322 361 406 456 512 558 611 661 706 789 866 935 968 1000 1061 1117

60 60 60 70 70 70 70 90 90 90 90 90 105 105 105 105 105 120 120 120 120 120 120

DIAMETER APPROX. DC RESISTANCE AMPACITY² OVER TOTAL (A)3 AT 20°C 1 INSULATION WEIGHT (ohm/1000ft) (mils) (pound/1000ft)

195 213 236 287 324 370 429 508 547 592 642 698 775 828 877 923 1006 1113 1182 1215 1247 1308 1365

25 34 48 75 109 163 247 317 390 482 597 741 882 1046 1209 1371 1695 2039 2362 2523 2684 3005 3326

2.58 1.62 1.02 0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212 0.0176 0.0151 0.0141 0.0132 0.0118 0.0106

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

Notes: 1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. T90°C conductor temperature, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

16

AMPACITY² (A)4

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615


TTU Cables Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground

Description Soft copper conductor, XLPE or PE insulated and an PVC external jacket.

Construction Conductor Compressed Stranded Soft copper. Insulation Thermoplastic Polyethylene (PE 75°•'3fC), for PE-PVC. Cross Linked Polyethylene (XLPE 90°•'3fC), for XLPE-PVC. Options Aluminum Conductor, PVC-LS (Low smoke emissions) jacket and PVC SR (Sunlight resistant) jacket For sizes greater than 1/0 AWG, Type Tray Cable (TC).

Characteristics Operating temperature Dry and wet locations. 75°C for TTU PE-PVC. 90°C for TTU XLPE-PVC. Operating Voltage 600 V and 2000 V

Uses and Applications Industrial installations, distribution and lighting systems. Dry or wet locations installations, in Tray Cable, ducts or raceways. Sizes 8 AWG and greater are useful for directed burial. 17


TTU design join excellent PE electrical properties, electrical and mechanical XLPE properties as insulation with mechanical and flame retardancy PVC properties as external jacket.

Standards and Specifications CENTELSA TTU Cables are manufactured under the following standards: ASTM B3, NTC-ICONTEC 359. Soft copper wire. ASTM B8, NTC-ICONTEC 307. Concentric Lay Stranded copper conductors. ASTM B787. 19 Wire Combination Unilay Stranded Copper conductors for subsequent insulation. UL 1581, NTC-3203. Reference Standard for Electrical Wires, Cables and Flexible Cords. ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy.

Certifications CENTELSA TTU cables are certified by CIDET (Colombia). Cert. No. 408. Note: Other configurations and sizes not specified herein are available upon request.

18


Cables Type TTU 600V (International Unit System) Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy.

SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

JACKET DIAMETER APPROX. DC STRANDSSTRANDING CROSS CONDUCTOR INSULATION DIAMETER AMPACITY 2 AMPACITY 2 CLASS SECTION DIAMETER THICKNESS OVER THICKNESS OVER TOTAL RESISTANCE No. (A)3 (A)4 (mm2) (mm) (mm) INSULATION (mm) JACKET WEIGHT AT 20°C1 (mm) (mm) (kg/km) (ohm/km) PE INSULATION

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

2.08 3.31 5.26 8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4 304.0 354.7 380.0 405.4 456.0 506.7

1.79 2.25 2.85 3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04 22.00 23.75 24.59 25.39 26.94 28.38

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 2.03 2.03 2.03 2.03 2.03 2.03

3.38 3.85 4.44 5.96 6.89 8.08 9.57 11.09 12.09 13.22 14.49 15.91 17.61 18.95 20.21 21.37 23.47 26.18 27.93 28.77 29.57 31.12 32.56

0.38 0.38 0.38 0.38 0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65

4.22 4.69 5.28 6.80 8.49 9.67 11.17 13.46 14.46 15.59 16.86 18.28 19.98 22.39 23.64 24.80 26.90 29.61 31.36 32.20 33.00 34.56 36.00

32 46 66 106 170 251 376 494 605 743 916 1132 1335 1632 1879 2125 2614 3130 3616 3858 4100 4583 5064

8.45 5.31 3.34 2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694 0.0578 0.0496 0.0463 0.0434 0.0386 0.0347

30 35 50 70 95 125 170 195 230 265 310 360 405 455 505 545 620 690 755 785 815 870 935

20 25 35 50 65 85 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. 75°C for PE insulation, 90°C conductor temperature nfor XLPE insulation, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

19

AMPACITY 2 (A)3

AMPACITY 2 (A)4

XLPE INSULATION

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615


Cables Type TTU 600V Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy.

SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

JACKET DIAMETER APPROX. DC STRANDSSTRANDING CROSS CONDUCTOR INSULATION DIAMETER AMPACITY 2 AMPACITY 2 TOTAL RESISTANCE CLASS SECTION DIAMETER THICKNESS OVER THICKNESS OVER No. (A)3 (A)4 WEIGHT (sq inches) (mils) (mils) INSULATION (mils) JACKET AT 20°C1 (pounds/ (mils) (mils) 1000ft) (ohm/1000ft) PE INSULATION

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

0.00323 0.00513 0.00815 0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393 0.471 0.550 0.589 0.628 0.707 0.785

70 89 112 141 178 225 283 322 361 406 456 512 558 611 661 706 789 866 935 968 1000 1061 1117

30 30 30 45 45 45 45 55 55 55 55 55 65 65 65 65 65 80 80 80 80 80 80

133 152 175 235 271 318 377 437 476 521 571 626 693 746 796 841 924 1031 1100 1133 1164 1225 1282

15 15 15 15 30 30 30 45 45 45 45 45 45 65 65 65 65 65 65 65 65 65 65

166 185 208 268 334 381 440 530 569 614 664 720 787 881 931 976 1059 1166 1235 1268 1299 1360 1417

22 31 44 71 114 168 253 332 406 499 615 761 897 1097 1263 1428 1756 2104 2430 2593 2755 3080 3403

2.58 1.62 1.02 0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212 0.0176 0.0151 0.0141 0.0132 0.0118 0.0106

30 35 50 70 95 125 170 195 230 265 310 360 405 455 505 545 620 690 755 785 815 870 935

20 25 35 50 65 85 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545

AMPACITY 2 (A)3

AMPACITY 2 (A)4

XLPE INSULATION

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615

Notes: 1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. 75°C for PE insulation, 90°C conductor temperature nfor XLPE insulation, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

20


Cables Type TTU 600V (International Unit System) Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy.

SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

JACKET DIAMETER APPROX. DC STRANDSSTRANDING CROSS CONDUCTOR INSULATION DIAMETER AMPACITY 2 AMPACITY 2 CLASS SECTION DIAMETER THICKNESS OVER THICKNESS OVER TOTAL RESISTANCE No. (A)3 (A)4 (mm2) (mm) (mm) INSULATION (mm) JACKET WEIGHT AT 20°C1 (mm) (mm) (kg/km) (ohm/km) PE INSULATION

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

2.08 3.31 5.26 8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4 304.0 354.7 380.0 405.4 456.0 506.7

1.79 2.25 2.85 3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04 22.00 23.75 24.59 25.39 26.94 28.38

1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 1.90 1.90 1.90 1.90 2.29 2.29 2.29 2.29 2.29 2.29 2.29

4.16 4.63 5.22 6.50 7.44 8.62 10.11 11.61 12.61 13.74 15.01 16.43 18.13 19.47 20.73 21.89 24.76 26.71 28.47 29.31 30.11 31.66 33.10

0.38 0.38 0.38 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65

5.00 5.46 6.05 8.10 9.03 10.21 11.71 13.98 14.98 16.11 17.38 18.80 21.56 22.91 24.16 25.32 28.19 30.15 31.90 32.74 33.54 35.09 36.53

38 52 73 125 178 259 386 505 617 756 930 1147 1401 1651 1899 2145 2668 3155 3642 3885 4127 4611 5093

8.45 5.31 3.34 2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694 0.0578 0.0496 0.0463 0.0434 0.0386 0.0347

30 35 50 70 95 125 170 195 230 265 310 360 405 455 505 545 620 690 755 785 815 870 935

20 25 35 50 65 85 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. 75°C for PE insulation, 90°C conductor temperature nfor XLPE insulation, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

21

AMPACITY 2 (A)3

AMPACITY 2 (A)4

XLPE INSULATION

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615


Cables Type TTU 600V Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy. SIZE AWG / kcmil

14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000

DIAMETER APPROX. DC STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER JACKET AMPACITY 2 AMPACITY 2 TOTAL RESISTANCE (mils) SECTION DIAMETER THICKNESS OVER THICKNESS OVER No. (A)3 (A)4 WEIGHT (sq inches) (mils) (mils) INSULATION (mils) JACKET AT 20°C1 (pounds/ (mils) (mils) 1000ft) (ohm/1000ft) PE INSULATION

7 7 7 7 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 61 61

B B B B B B B B B B B B B B B B B B B B B B B

0.00323 0.00513 0.00815 0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393 0.471 0.550 0.589 0.628 0.707 0.785

70 89 112 141 178 225 283 322 361 406 456 512 558 611 661 706 789 866 935 968 1000 1061 1117

45 45 45 55 55 55 55 65 65 65 65 65 75 75 75 75 90 90 90 90 90 90 90

164 182 205 256 293 339 398 457 496 541 591 647 714 767 816 862 975 1052 1121 1154 1185 1246 1303

15 15 15 30 30 30 30 45 45 45 45 45 65 65 65 65 65 65 65 65 65 65 65

197 215 238 319 356 402 461 551 590 634 684 740 849 902 951 997 1110 1187 1256 1289 1320 1382 1438

26 35 49 84 119 174 259 340 414 508 625 771 942 1109 1276 1442 1793 2120 2447 2611 2774 3099 3423

2.58 1.62 1.02 0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212 0.0176 0.0151 0.0141 0.0132 0.0118 0.0106

30 35 50 70 95 125 170 195 230 265 310 360 405 455 505 545 620 690 755 785 815 870 935

AMPACITY 2 (A)3

20 25 35 50 65 85 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545

Notes: 1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. 75°C for PE insulation, 90°C conductor temperature nfor XLPE insulation, 30°C ambient temperature, According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. One single conductor at free air at 30°C ambient temperature. 4. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature. 5. According to NEC NTC 2050 the minimun size for use in Tray Cables must be 1/0 AWG for phase conductors, and 4 AWG for grounding conductors. 6. Data herein indicated are approximated and are subject to normal manufacturing tolerances.

22

AMPACITY 2 (A)4

XLPE INSULATION

35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 855 885 920 985 1055

25 30 40 55 75 95 130 150 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615


Three Conductor Power Cables

Cross (X) Linked Polyethylene Insulation, High Heat resistant (90°C), 2: Suitable for Dry Insulation, and Wet Cross (X) Linked Polyethilene HighLocations Heat resistant (90°C), 2: Suitable for Dry and Wet Locations

Description Three soft copper conductors PVC or XLPE insulated twisted and with overall PVC jacket.

Design Conductor Soft stranded compressed copper. Insulation Polyvinyl Chloride (PVC 75°C) flame retardant, for PVC-PVC insulation and jacket. Cross linked Polyethylene (XLPE 90°C), for XLPE-PVC insulation and jacket. Filler Flame retardant Polyvinyl Chloride. Jacket Flame retardant Polyvinyl Chloride. Options EPR insulation. Metallic shield in copper tape or copper wires. Grounding conductor- Armor in galvanized steel wires or galvanized steel tape or interlocked armor tape aluminum or steel. Moisture barrier, PVC SR (Sunlight Resistant) jacket.

Characteristics Operating temperature Dry and wet locations. 75°C, for PVC-PVC insulation-jacket. 90°C, for XLPE-PVC insulation-jacket. 23


Operating Voltage 600 V. Optional 2000 V.

Uses and Applications General purpose in industrial installations for Low Voltage indoor distribution of electrical energy in low tension. Installation in dry or wet locations, in ducts, raceway or buried direct. The design of Power Cable 3 - conductor combines the excellent electrical properties of PE, and electrical and mechanical of XLPE like insulation materials, and the mechanical properties and PVC flame in the outer jacket. In special applications the cable can be used under water. XLPE insulated conductors have minor total diameters for the same voltage of operation, that PVC isolated ones.

Standards and Specifications CENTELSA Power Cables are manufactured under the following standards: ASTM B3, NTC-ICONTEC 359. Soft copper wire. ASTM B8, NTC-ICONTEC 307. Concentric Lay Stranded copper conductors. ASTM B787. 19 Wire Combination Unilay Stranded Copper conductors for subsequent insulation. UL 1581, NTC-3203. Reference Standard for Electrical Wires, Cables and Flexible Cords. ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy. IEC 228. Conductors for insulated cables (mm2 sizes). IEC 60502-1. Cables for 1kV Voltages (mm2 sizes).

Certifications CENTELSA Power Cables are certified by CIDET (Colombia). Cert. No. 1668. 24


Phases identification PVC-PVC Cables are identified by colored phases black, white and red. Black jacket. XLPE-PVC Cables are identified by numbered black phases. Black jacket. Note: Other configurations and sizes not specified herein are available upon request.

Three Conductors Cables PVC-PVC 600V (International Unit System) Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy. SIZE AWG / kcmil

8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 Notes:

STRANDS STRANDING CLASS No.

7 7 7 7 19 19 19 19 19 37 37 37 37 37

B B B B B B B B B B B B B B

CROSS CONDUCTOR INSULATION DIAMETER ASSEMBLY FILLER JACKET DIAMETER SECTION DIAMETER THICKNESS DIAMETER THICKNESS THICKNESS OVER OVER (mm2) (mm) (mm) (mm) (mm) JACKET INSULATION (mm) (mm) (mm)

8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4

3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04

1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41

6.75 7.68 8.87 10.36 12.36 13.36 14.49 15.76 17.18 19.14 20.48 21.74 22.90 25.00

14.55 16.56 19.11 22.32 26.64 28.79 31.23 33.96 37.02 41.24 44.14 46.85 49.34 53.88

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00

1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79

17.71 19.72 23.29 26.50 30.82 32.97 37.41 40.14 44.76 48.98 51.88 54.59 57.08 61.62

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C1 (ohm/km)

541 737 1089 1554 2007 2408 3071 3702 4639 5500 6392 7278 8154 9886

2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. In race way, or direct burial, 75째C conductor temperature, 30째C ambient temperature. 3. Data herein indicated are approximated and are subject to normal manufacturing tolerances.

25

AMPACITY 2 (A)

50 65 85 115 130 150 175 200 230 255 285 310 335 380


Three Conductors Cables PVC-PVC 600V Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy. SIZE AWG / kcmil

8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500

STRANDS STRANDING (mils) No.

7 7 7 7 19 19 19 19 19 37 37 37 37 37

B B B B B B B B B B B B B B

CROSS CONDUCTOR INSULATION DIAMETER ASSEMBLY FILLER JACKET DIAMETER APPROX. DC SECTION DIAMETER THICKNESS OVER DIAMETER THICKNESS THICKNESS OVER TOTAL RESISTANCE (sq inches) (mils) (mils) INSULATION (mils) (mils) (mils) JACKET WEIGHT AT 20°C1 (mils) (mils) (pound/1000ft) (ohm/1000ft)

0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393 Notes:

141 178 225 283 322 361 406 456 512 558 611 661 706 789

60 60 60 60 80 80 80 80 80 95 95 95 95 95

266 303 349 408 487 526 571 620 676 753 806 856 901 984

573 652 752 879 1049 1133 1229 1337 1457 1624 1738 1845 1943 2121

39 39 39 39 39 39 39 39

60 60 80 80 80 80 80 80 110 110 110 110 110 110

697 776 917 1043 1213 1298 1473 1580 1762 1928 2042 2149 2247 2426

363 496 732 1044 1349 1619 2064 2488 3118 3696 4296 4891 5480 6644

0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212

AMPACITY 2 (A)

50 65 85 115 130 150 175 200 230 255 285 310 335 380

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. In race way, or direct burial, 75°C conductor temperature, 30°C ambient temperature. 3. Data herein indicated are approximated and are subject to normal manufacturing tolerances.

Three Conductors Cables XLPE-PVC 600V (International Unit System) Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy. SIZE AWG / kcmil

8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500

JACKET DIAMETER STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER ASSEMBLY FILLER CLASS SECTION DIAMETER THICKNESS OVER DIAMETER THICKNESS THICKNESS OVER No. 2 (mm ) (mm) (mm) INSULATION (mm) (mm) (mm) JACKET (mm) (mm)

7 7 7 7 19 19 19 19 19 37 37 37 37 37

B B B B B B B B B B B B B B

8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 126.7 152.0 177.3 202.7 253.4 Notes:

26

3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 14.18 15.52 16.78 17.94 20.04

1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65

5.97 6.90 8.09 9.58 11.10 12.10 13.23 14.50 15.92 17.62 18.96 20.22 21.38 23.48

12.87 14.88 17.43 20.64 23.92 26.07 28.51 31.25 34.30 37.96 40.86 43.58 46.07 50.60

1.00 1.00 1.00 1.00 1.00 1.00 1.00

1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C1 (ohm/km)

AMPACITY 2 (A)

460 646 930 1424 1787 2171 2649 3409 4165 5073 5936 6795 7646 9333

2.10 1.32 0.831 0.523 0.415 0.329 0.261 0.207 0.164 0.139 0.116 0.0992 0.0868 0.0694

55 75 95 130 150 170 195 225 260 290 320 350 380 430

16.03 18.04 20.59 24.82 28.10 30.25 32.69 37.43 40.48 45.70 48.60 51.32 53.81 58.34

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. In race way, or direct burial, 90°C conductor temperature, 30°C ambient temperature. 3. Data herein indicated are approximated and are subject to normal manufacturing tolerances.


Three Conductors Cables XLPE-PVC 600V Manufacturing Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy. SIZE AWG / kcmil

8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 Notes:

JACKET DIAMETER APPROX. DC STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER ASSEMBLY FILLER (mils) SECTION DIAMETER THICKNESS OVER DIAMETER THICKNESS THICKNESS OVER TOTAL RESISTANCE No. (sq inches) (mils) (mils) INSULATION (mils) (mils) (mils) JACKET WEIGHT AT 20°C1 (mils) (mils) (pound/1000ft) (ohm/1000ft)

7 7 7 7 19 19 19 19 19 37 37 37 37 37

B B B B B B B B B B B B B B

0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.196 0.236 0.275 0.314 0.393

141 178 225 283 322 361 406 456 512 558 611 661 706 789

45 45 45 45 55 55 55 55 55 65 65 65 65 65

235 272 318 377 437 476 521 571 627 694 747 796 842 924

507 586 686 813 942 1026 1123 1230 1350 1495 1609 1716 1814 1992

39 39 39 39 39 39 39

60 60 60 80 80 80 80 80 80 110 110 110 110 110

631 710 810 977 1106 1191 1287 1474 1594 1799 1914 2020 2118 2297

AMPACITY 2 (A)

0.641 0.403 0.253 0.159 0.126 0.100 0.0795 0.0630 0.0500 0.0423 0.0353 0.0302 0.0264 0.0212

55 75 95 130 150 170 195 225 260 290 320 350 380 430

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C1 (ohm/km)

AMPACITY 2 (A)

530 752 1115 1468 2018 2724 3722 4600 5707 7014 8996

1.76 1.10 0.703 0.502 0.352 0.251 0.185 0.147 0.117 0.0951 0.0733

50 70 90 110 140 170 205 240 275 310 365

309 434 625 957 1201 1459 1780 2291 2799 3409 3989 4567 5139 6272

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. In race way, or direct burial, 90°C conductor temperature, 30°C ambient temperature. 3. Data herein indicated are approximated and are subject to normal manufacturing tolerances.

Three Conductor Power Cable Type PVC-PVC 0.6/1 kV ( mm2 Sizes) Manufacturing Standard: IEC 60502-1 Cables for 1 kV Voltages. SIZE AWG / kcmil

10 16 25 35 50 70 95 120 150 185 240 Notes:

JACKET DIAMETER STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER ASSEMBLY FILLER CLASS SECTION DIAMETER THICKNESS OVER DIAMETER THICKNESS THICKNESS OVER No. 2 (mm ) (mm) (mm) INSULATION (mm) (mm) (mm) JACKET (mm) (mm)

7 7 7 7 19 19 19 37 37 37 37

2 2 2 2 2 2 2 2 2 2 2

10.0 16.0 25.0 35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0

3.72 4.70 5.88 6.96 8.26 9.77 11.39 12.88 14.40 15.99 18.29

1.00 1.00 1.20 1.20 1.40 1.40 1.60 1.60 1.80 2.00 2.20

5.82 6.80 8.38 9.46 11.18 12.69 14.71 16.20 18.14 20.15 22.83

12.54 14.65 18.06 20.39 24.09 27.35 31.70 34.91 39.09 43.42 49.20

0.50 0.50 0.50 0.50 0.50

1.80 1.80 1.80 1.80 1.80 2.00 2.10 2.30 2.40 2.60 2.80

16.28 18.39 21.80 24.13 27.83 31.51 37.02 40.65 45.03 49.78 55.96

1. Designated Voltage Uo/U means Uo rated voltage phase-neutral, U rated voltage phase-phase. 2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 3. In race way, or direct burial, 75°C conductor temperature, 30°C ambient temperature. 4. Data herein indicated are approximated and are subject to normal manufacturing tolerances.

27


Three Conductor Power Cable Type XLPE-PVC 0.6/1 kV ( mm2 Sizes) Manufacturing Standard: IEC 60502-1 Cables for 1 kV Voltages. SIZE AWG / kcmil

10 16 25 35 50 70 95 120 150 185 240

JACKET DIAMETER STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER ASSEMBLY FILLER CLASS SECTION DIAMETER THICKNESS OVER DIAMETER THICKNESS THICKNESS OVER No. (mm2) (mm) (mm) INSULATION (mm) (mm) (mm) JACKET (mm) (mm)

7 7 7 7 19 19 19 37 37 37 37

2 2 2 2 2 2 2 2 2 2 2

10.0 16.0 25.0 35.0 50.0 70.0 95.0 120.0 150.0 185.0 240.0 Notes:

28

3.72 4.70 5.88 6.96 8.26 9.77 11.39 12.88 14.40 15.99 18.29

0.70 0.70 0.90 0.90 1.00 1.10 1.10 1.20 1.40 1.60 1.70

5.20 6.18 7.78 8.86 10.36 12.05 13.67 15.38 17.32 19.31 21.83

11.21 13.32 16.77 19.09 22.33 25.97 29.46 33.14 37.32 41.61 47.04

0.50 0.50 0.50 0.50

1.80 1.80 1.80 1.80 1.80 1.90 2.00 2.20 2.30 2.50 2.70

14.95 17.06 20.51 22.83 26.07 29.93 33.62 38.68 43.06 47.77 53.60

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C1 (ohm/km)

AMPACITY 2 (A)

473 686 1033 1375 1883 2578 3411 4373 5445 6707 8602

1.76 1.10 0.703 0.502 0.352 0.251 0.185 0.147 0.117 0.0951 0.0733

60 80 105 130 160 195 235 270 310 350 410

1. Designated Voltage Uo/U means Uo rated voltage phase-neutral, U rated voltage phase-phase. 2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 3. In race way, or direct burial, 90째C conductor temperature, 30째C ambient temperature. 4. Data herein indicated are approximated and are subject to normal manufacturing tolerances.


Service Entrance Type SEU & SER Service Entrance Cable Unarmored or U-shaped Service Entrance Cable Round

Description Service Entrance SEU: one or two XHHW-2 insulated conductors, paralleled, with concentric neutral, reinforced tape and PVC jacket. Service Entrance SER: two or three XHHW-2 insulated conductors, twisted together with or without bare grounding conductor, reinforced tape and PVC jacket.

Construction Conductor Soft copper stranded and compressed. Insulation Cross Linked Polyethylene (XLPE 90째C).

Design Service Entrance Type U, SEU: Round configuration for one phase conductor and neutral, flan configuration for two phase conductors and neutral. Neutral Service Entrance SEU : soft copper wires applied concentrically around phases with SZ technology (UL 854 Section 15.4) Service Entrance SER: soft copper stranded, twisted together with phases Binder Tape Service Entrance SEU: polyester tape over neutral conductor Service Entrance SER: polyester tape over assembly. 29


Jacket Flame Retardant and Sunlight resistant PVC. Options THWN-2 Conductors. Jacket with PVC LS (LOW Smoke emission). Aluminum conductors.

Characteristics Operating Temperature Dry and wet locations 90째C. Operating Voltage 600 V.

Uses and Applications Service Entrance or Drop Cable up to Service Entrance Equipment and to general breaker. May be used for branch circuits according to NEC and NTC 2050.

Standards and Specifications CENTELSA Service Entrance Cables are manufactured under the following standards: ASTM B3, NTC-359. Soft copper wires. ASTM B8, NTC-307. Concentric Lay Stranded copper conductors. ASTM B787. 19 Wire Combination Unilay Stranded Copper conductors for subsequent insulation UL 1581, NTC-3203. Reference Standard for Electrical Wires, Cables and Flexible Cords. UL 854, NTC-ICONTEC 4564. Service Entrance Cables.

Certifications CENTELSA Service Entrance Cables are certified by: UL 854 File E207803. CIDET (Colombia). Cert. No. 00416. Note: Other configurations and sizes not specified herein are available upon request.

30


Service Entrance Type SEU 600V (International System Unit) Service Entrance Cable Unarmored or U-shaped

1 x 10 + 10 1x8+8 1x6+6 1x4+4 1x2+2 2 x 10 + 10 2x8+8 2x6+6 2x4+4 2x2+2 2 x 8 + 10 2x6+8 2x4+6 2x2+4 Notes:

SIZE AWG

STRANDING CLASS

CODE

STRANDS No.

Manufacturing Standard: UL 854, NTC 4564. Service Entrance Cables CROSS CONDUCTOR INSULATION DIAMETER SECTION DIAMETER THICKNESS OVER (mm2) (mm) (mm) INSULATION (mm)

10 8 6 4 2 10 8 6 4 2 8 6 4 2

1 7 7 7 7 1 7 7 7 7 7 7 7 7

SOLID B B B B SOLID B B B B B B B B

5.26 8.37 13.30 21.15 33.63 5.26 8.37 13.30 21.15 33.63 8.37 13.30 21.15 33.63

2.59 3.59 4.52 5.71 7.20 2.59 3.59 4.52 5.71 7.20 3.59 4.52 5.71 7.20

0.76 1.14 1.14 1.14 1.14 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14

4.18 5.96 6.89 8.08 9.57 4.18 5.96 6.89 8.08 9.57 5.96 6.89 8.08 9.57

NEUTRAL SIZE AWG

10 8 6 4 2 10 8 6 4 2 10 8 6 4

NEUTRAL CONDUCTOR STRANDS STRAND No. DIAMETER (mm)

26 41 41 41 41 26 41 41 41 41 26 41 41 41

0.51 0.51 0.64 0.81 1.02 0.51 0.51 0.64 0.81 1.02 0.51 0.51 0.64 0.81

POLYESTERIC JACKET TAPE THICKNESS THICKNESS (mm) (mm)

0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032

0.76 1.14 1.14 1.14 1.14 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14

DIMENSIONS OVER JACKET (mm)

DC APPROX. AMPACITY 2 TOTAL RESISTANCE (A) AT 20°C1 WEIGHT (ohm/km) (kg/km)

126 216 316 475 721 195 338 492 733 1107 309 445 657 989

6.82 9.36 10.56 12.08 13.99 6.90 x 11.08 9.45 x 15.42 10.65 x 17.54 12.17 x 20.25 14.09 x 23.66 9.45 x 15.42 10.38 x 17.28 11.83 x 19.91 13.66 x 23.23

3.28 2.10 1.32 0.831 0.523 3.28 2.10 1.32 0.831 0.523 2.10 1.32 0.831 0.523

40 55 75 95 130 40 55 75 95 130 55 75 95 130

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. LData herein indicated are approximated and are subject to normal manufacturing tolerances.

Service Entrance Type SEU 600V Service Entrance Cable Unarmored or U-shaped

1 x 10 + 10 1x8+8 1x6+6 1x4+4 1x2+2 2 x 10 + 10 2x8+8 2x6+6 2x4+4 2x2+2 2 x 8 + 10 2x6+8 2x4+6 2x2+4 Notes:

SIZE AWG

STRANDING (mils)

CODE

STRANDS No.

Manufacturing Standard: UL 854, NTC 4564. Service Entrance Cables

10 8 6 4 2 10 8 6 4 2 8 6 4 2

1 7 7 7 7 1 7 7 7 7 7 7 7 7

SOLID 0.00815 0.0130 B 0.0206 B 0.0328 B 0.0521 B SOLID 0.00815 0.0130 B 0.0206 B 0.0328 B 0.0521 B 0.0130 B 0.0206 B 0.0328 B 0.0521 B

CROSS CONDUCTOR INSULATION DIAMETER SECTION DIAMETER THICKNESS OVER (mils) (sq inches) (mils) INSULATION (mils)

102 141 178 225 283 102 141 178 225 283 141 178 225 283

30 45 45 45 45 30 45 45 45 45 45 45 45 45

165 235 271 318 377 165 235 271 318 377 235 271 318 377

NEUTRAL NEUTRAL CONDUCTOR POLYESTERIC JACKET DIMENSIONS APPROX. DC TAPE THICKNESS SIZE OVER TOTAL RESISTANCE STRANDS STRAND THICKNESS (mils) AWG JACKET WEIGHT AT 20°C1 No. DIAMETER (mils) (mils) (pound/1000ft) (ohm/1000ft) (mils)

10 8 6 4 2 10 8 6 4 2 10 8 6 4

26 41 41 41 41 26 41 41 41 41 26 41 41 41

20.1 20.1 25.3 32.0 40.3 20.1 20.1 25.3 32.0 40.3 20.1 20.1 25.3 32.0

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

30 45 45 45 45 30 45 45 45 45 45 45 45 45

269 369 416 476 551 272 x 436 372 x 607 419 x 691 479 x 797 555 x 931 372 x 607 409 x 680 466 x 784 538 x 915

85 145 213 319 484 131 227 331 493 744 208 299 441 664

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2.No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. LData herein indicated are approximated and are subject to normal manufacturing tolerances.

31

0.999 0.641 0.403 0.253 0.159 0.999 0.641 0.403 0.253 0.159 0.641 0.403 0.253 0.159

AMPACITY 2 (A)

40 55 75 95 130 40 55 75 95 130 55 75 95 130


Service Entrance Type SER 600V (International System Unit) Service Entrance Cable Round

3x8 3x6 3x4 3x2 3x1 3 x 1/0 3 x 2/0 3 x 3/0 3 x 4/0 3x8+8 3x6+6 3x4+6 3x2+4 3 x 1/0 + 2 3 x 2/0 + 1 3 x 3/0 + 1/0 3 x 4/0 + 2/0

SIZE AWG

STRANDING CLASS

CODE

STRANDS No.

Manufacturing Standard: UL 854, NTC 4564. Service Entrance Cables

8 6 4 2 1 1/0 2/0 3/0 4/0 8 6 4 2 1/0 2/0 3/0 4/0

7 7 7 7 19 19 19 19 19 7 7 7 7 19 19 19 19

B B B B B B B B B B B B B B B B B

CROSS CONDUCTOR INSULATION DIAMETER SECTION DIAMETER THICKNESS OVER (mm2) (mm) (mm) INSULATION (mm)

8.37 13.30 21.15 33.63 42.41 53.48 67.43 85.03 107.2 8.37 13.30 21.15 33.63 53.48 67.43 85.03 107.2

3.59 4.52 5.71 7.20 8.18 9.18 10.31 11.58 13.00 3.59 4.52 5.71 7.20 9.18 10.31 11.58 13.00 Notes:

1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40

5.96 6.89 8.08 9.57 11.09 12.09 13.22 14.49 15.91 5.96 6.89 8.08 9.57 12.09 13.22 14.49 15.91

NEUTRAL NEUTRAL NEUTRAL ASSEMBLY SIZE CONDUCTOR CONDUCTOR DIAMETER AWG STRANDS DIAMETER (mm) No. No.

8 6 6 4 2 1 1/0 2/0

7 7 7 7 7 19 19 19

3.59 4.52 4.52 5.71 7.20 8.18 9.18 10.31

12.85 14.86 17.41 20.62 23.90 26.05 28.50 31.23 34.28 13.72 15.86 18.58 22.01 27.81 30.41 33.33 36.59

REINFORCED TAPE THICKNESS (mm)

DC JACKET DIMENSIONS APPROX. AMPACITY 2 THICKNESS OVER TOTAL RESISTANCE (A) 1 (mm) JACKET WEIGHT AT 20°C (ohm/Km) (mm) (Kg/Km)

0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100 0.100

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

14.75 16.75 19.30 22.52 25.80 27.95 30.39 33.13 36.18 15.61 17.75 20.47 23.91 29.70 32.31 35.23 38.49

344 501 744 1124 1411 1740 2153 2669 3317 424 626 870 1323 2055 2548 3167 3943

2.12 1.34 0.840 0.528 0.419 0.332 0.263 0.209 0.166 2.12 1.34 0.840 0.528 0.332 0.263 0.209 0.166

55 75 95 130 150 170 195 225 260 55 75 95 130 170 195 225 260

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

Service Entrance Type SER 600V Service Entrance Cable Round

3x8 3x6 3x4 3x2 3x1 3 x 1/0 3 x 2/0 3 x 3/0 3 x 4/0 3x8+8 3x6+6 3x4+6 3x2+4 3 x 1/0 + 2 3 x 2/0 + 1 3 x 3/0 + 1/0 3 x 4/0 + 2/0

SIZE AWG

STRANDING (mils)

CODE

STRANDS No.

Manufacturing Standard: UL 854, NTC 4564. Service Entrance Cables

8 6 4 2 1 1/0 2/0 3/0 4/0 8 6 4 2 1/0 2/0 3/0 4/0

7 7 7 7 19 19 19 19 19 7 7 7 7 19 19 19 19

B B B B B B B B B B B B B B B B B

CROSS CONDUCTOR INSULATION DIAMETER NEUTRAL NEUTRAL NEUTRAL ASSEMBLY SECTION DIAMETER THICKNESS OVER SIZE CONDUCTOR CONDUCTOR DIAMETER (sq inches) (mils) (mils) INSULATION AWG STRANDS DIAMETER (mils) (mils) No. No.

0.0130 0.0206 0.0328 0.0521 0.0657 0.0829 0.105 0.132 0.166 0.0130 0.0206 0.0328 0.0521 0.0829 0.105 0.132 0.166

141 178 225 283 322 361 406 456 512 141 178 225 283 361 406 456 512 Notes:

32

45 45 45 45 55 55 55 55 55 45 45 45 45 55 55 55 55

235 271 318 377 437 476 521 571 626 235 271 318 377 476 521 571 626

8 6 6 4 2 1 1/0 2/0

7 7 7 7 7 19 19 19

141 178 178 225 283 322 361 406

506 585 685 812 941 1026 1122 1230 1350 540 624 731 867 1095 1197 1312 1441

REINFORCED TAPE THICKNESS (mils)

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

DC JACKET DIMENSIONS APPROX. AMPACITY 2 TOTAL RESISTANCE THICKNESS OVER (A) AT 20°C1 WEIGHT (mils) JACKET (pound/1000ft) (ohm/1000ft) (mils)

30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30

581 660 760 887 1016 1100 1197 1304 1424 615 699 806 941 1169 1272 1387 1515

231 336 500 755 948 1170 1447 1794 2229 285 421 585 889 1381 1713 2128 2650

0.647 0.407 0.256 0.161 0.128 0.101 0.0803 0.0637 0.0505 0.647 0.407 0.256 0.161 0.101 0.0803 0.0637 0.0505

55 75 95 130 150 170 195 225 260 55 75 95 130 170 195 225 260

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. Data herein indicated are approximated and are subject to normal manuracturing tolerances.


Service Entrance Type ARE & APE A: Service Entrance R: Round Configuration E: Concentric Neutral Conductor A: Service Entrance P: Flat Configuration E: Concentric Neutral Conductor

Description ARE: one or two XLPE insulated conductors, twisted together, with concentric neutral, PVC filler and PE jacket. APE: two XLPE insulated conductors, paralleled, with polyester tape, concentric neutral, and PE jacket. Service Entrance SER: two or three XHHW-2 insulated conductors, twisted together with or without bare grounding conductor, reinforced tape and PVC jacket.

Construction Conductor Soft copper stranded and compressed. Insulation Cross Linked Polyethylene (XLPE 90째C). Configuration ARE: Round. APE: Flat. Binder Tape APE: Polyester Tape over paralleled conductors. Neutral Soft copper wires applied concentrically around phases with SZ technology with high coverage over phase conductors. Jacket Polyethylene (PE). Rip cord for easy installation. Options Aluminum conductor. PVC Insulation. Sunlight Resistant PVC Jacket. 33


Low Smoke Emission PVC Jacket.

Characteristics Operation Temperature Dry and wet locations 90째C. Operating Voltage 600 V.

Uses and Applications Service Entrance or Drop Cable up to Service Entrance Equipment and to general breaker.

Standards CENTELSA ARE and APE Service Entrance Cables are manufactured under the following standards: ASTM B3, NTC-359. Soft copper wires. ASTM B8, NTC-307. Concentric Lay Stranded copper conductors.

Certifications CENTELSA ARE and APE Service Entrance Cables are certified by: CIDET (Colombia). Cert. No. 00416. Note: Other configurations and sizes not specified herein are available upon request.

34


Service Entrance Type ARE 600V (International System Unit) A: Service Entrance R: Round Configuration E: Concentric Neutral Conductor

CODE

SIZE AWG

STRANDS No.

STRANDING CLASS

Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy CROSS CONDUCTOR INSULATION DIAMETER FILLER DIAMETER NEUTRAL SECTION DIAMETER THICKNESS OVER THICKNESS OVER SIZE (mm2) (mm) (mm) INSULATION (mm) FILLER AWG (mm) (mm)

1 x 12 + 12 1 x 10 + 10 1x8+8 1x6+8 1x4+6 1x2+4 2 x 12 + 12 2 x 10 + 10 2x8+8 2x6+8 2x4+6 2x2+4

12 10 8 6 4 2 12 10 8 6 4 2

1 1 7 7 7 7 1 1 7 7 7 7

SOLID SOLID B B B B SOLID SOLID B B B B

3.31 5.26 8.37 13.30 21.15 33.63 3.31 5.26 8.37 13.30 21.15 33.63

Notes:

2.05 2.59 3.59 4.52 5.71 7.20 2.05 2.59 3.59 4.52 5.71 7.20

0.76 0.76 1.14 1.14 1.14 1.14 0.76 0.76 1.14 1.14 1.14 1.14

3.65 4.18 5.96 6.89 8.08 9.57 3.65 4.18 5.96 6.89 8.08 9.57

0.50 0.50 0.50 0.50 0.50 0.50

3.65 4.18 5.96 6.89 8.08 9.57 8.30 9.37 12.93 14.79 17.15 20.14

12 10 8 8 6 4 12 10 8 8 6 4

JACKET DIMENSIONS THICKNESS OVER STRANDS STRAND JACKET (mm) No. DIAMETER (mm) (mm)

NEUTRAL CONDUCTOR

17 26 41 41 41 41 26 26 41 41 41 41

0.51 0.51 0.51 0.51 0.64 0.81 0.51 0.51 0.51 0.51 0.64 0.81

1.14 1.14 1.14 1.14 1.14 1.52 1.14 1.14 1.14 1.14 1.14 1.52

APPROX. TOTAL WEIGHT (kg/km)

DC AMPACITY 2 RESISTANCE (A) AT 20°C1 (ohm/km)

88 126 202 254 382 598 173 243 408 543 794 1200

7.04 7.58 9.36 10.29 11.73 14.36 7.04 7.58 9.36 10.29 11.73 14.36

5.21 3.28 2.10 1.32 0.83 0.52 5.21 3.28 2.10 1.32 0.831 0.523

30 40 55 75 95 130 30 40 55 75 95 130

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

Service Entrance Type ARE 600V A: Service Entrance R: Round Configuration E: Concentric Neutral Conductor

CODE

SIZE AWG

STRANDS No.

STRANDING (mils)

Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy

1 x 12 + 12 1 x 10 + 10 1x8+8 1x6+8 1x4+6 1x2+4 2 x 12 + 12 2 x 10 + 10 2x8+8 2x6+8 2x4+6 2x2+4

12 10 8 6 4 2 12 10 8 6 4 2

1 1 7 7 7 7 1 1 7 7 7 7

SOLID SOLID B B B B SOLID SOLID B B B B

Notes:

CROSS CONDUCTOR INSULATION DIAMETER FILLER DIAMETER NEUTRAL NEUTRAL CONDUCTOR JACKET DIMENSIONS APPROX. DC RESISTANCE AMPACITY 2 SECTION DIAMETER THICKNESS OVER THICKNESS OVER SIZE THICKNESS OVER TOTAL AT 20°C1 (A) STRANDS STRAND JACKET (sq inches2) (mils) (mils) INSULATION (mils) FILLER AWG (mils) WEIGHT (ohm/1000ft) No. DIAMETER (mils) (mils) (mils) (pound/1000ft) (mils)

0.00513 0.00815 0.0130 0.0206 0.0328 0.0521 0.00513 0.00815 0.0130 0.0206 0.0328 0.0521

81 102 141 178 225 283 81 102 141 178 225 283

30 30 45 45 45 45 30 30 45 45 45 45

144 165 235 271 318 377 144 165 235 271 318 377

20 20 20 20 20 20

144 165 235 271 318 377 327 369 509 582 675 793

12 10 8 8 6 4 12 10 8 8 6 4

17 26 41 41 41 41 26 26 41 41 41 41

20.1 20.1 20.1 20.1 25.3 32.0 20.1 20.1 20.1 20.1 25.3 32.0

45 45 45 45 45 60 45 45 45 45 45 60

59 85 136 171 257 402 117 163 274 365 534 807

277 298 368 405 462 565 277 298 368 405 462 565

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

35

1.59 0.999 0.641 0.403 0.253 0.159 1.59 0.999 0.641 0.403 0.253 0.159

30 40 55 75 95 130 30 40 55 75 95 130


Service Entrance Type APE 600V (International System Unit) A: Service Entrance P: Flat Configuration E: Concentric Neutral Conductor

CODE

SIZE AWG

STRANDS No.

STRANDING CLASS

Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy

2 x 10 + 10 2x8+8 2x6+6 2x4+4 2x2+2 2 x 8 + 10 2x6+8 2x4+6 2x2+4

10 8 6 4 2 8 6 4 2

1 7 7 7 7 7 7 7 7

SOLID B B B B B B B B

CROSS CONDUCTOR INSULATION DIAMETER NEUTRAL NEUTRAL POLYESTERIC JACKET SECTION DIAMETER THICKNESS OVER SIZE CONDUCTOR TAPE THICKNESS (mm2) (mm) (mm) INSULATION AWG STRANDS THICKNESS (mm) (mm) No. (mm)

5.26 8.37 13.30 21.15 33.63 8.37 13.30 21.15 33.63

2.59 3.59 4.52 5.71 7.20 3.59 4.52 5.71 7.20

Notes:

0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14

4.18 5.96 6.89 8.08 9.57 5.96 6.89 8.08 9.57

10 8 6 4 2 10 8 6 4

26 41 41 41 41 26 41 41 41

0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032 0.032

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14

DIMENSIONS OVER JACKET (mm)

7.67 x 11.86 9.45 x 15.42 10.65 x 17.54 12.17 x 20.25 14.09 x 23.66 9.45 x 15.42 10.38 x 17.28 11.83 x 19.91 13.66 x 23.23

APPROX. DC AMPACITY 2 TOTAL RESISTANCE (A) WEIGHT AT 20°C1 (kg/km) (ohm/km)

196 316 467 704 1072 288 420 628 955

40 55 75 95 130 55 75 95 130

3.28 2.10 1.32 0.831 0.523 2.10 1.32 0.831 0.523

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper. 2.No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

Service Entrance Type APE 600V A: Service Entrance P: Flat Configuration E: Concentric Neutral Conductor

CONSTRUCTION

SIZE AWG

STRANDS No.

STRANDING CLASS

Standard: ICEA S-95-658, NTC-ICONTEC 1099-1. Power Cables rated 2000 volts or less for the Distribution of Electrical Energy

2 x 10 + 10 2x8+8 2x6+6 2x4+4 2x2+2 2 x 8 + 10 2x6+8 2x4+6 2x2+4

10 8 6 4 2 8 6 4 2

1 7 7 7 7 7 7 7 7

SOLID 0.00815 0.0130 B 0.0206 B 0.0328 B 0.0521 B 0.0130 B 0.0206 B 0.0328 B 0.0521 B

CROSS CONDUCTOR INSULATION DIAMETER SECTION DIAMETER THICKNESS OVER (sq inches2) (mils) (mils) INSULATION (mils)

102 141 178 225 283 141 178 225 283

Notes:

36

30 45 45 45 45 45 45 45 45

165 235 271 318 377 235 271 318 377

NEUTRAL NEUTRAL POLYESTERIC JACKET SIZE CONDUCTOR TAPE THICKNESS AWG STRANDS THICKNESS (mils) No. (mils)

10 8 6 4 2 10 8 6 4

26 41 41 41 41 26 41 41 41

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

45 45 45 45 45 45 45 45 45

DIMENSIONS APPROX. OVER TOTAL JACKET WEIGHT (mils) (pound/1000ft)

302 x 467 372 x 607 419 x 691 479 x 797 555 x 931 372 x 607 409 x 680 466 x 784 538 x 915

132 212 314 473 721 193 282 422 642

DC RESISTANCE AT 20°C1 (ohm/1000ft)

AMPACITY 2 (A)

0.999 0.641 0.403 0.253 0.159 0.641 0.403 0.253 0.159

40 55 75 95 130 55 75 95 130

1. DC resistance calculated based on a 10,371 ohm-cmil/1000ft resistivity for cooper. 2. No more than three current carrying conductors in a duct or in direct burial, 30°C ambient temperature, 90°C conductor temperature. According to NEC and NTC 2050, for sizes 14 12 and 10 AWG overload protection must be 15, 20 and 30 A. 3. Data herein indicated are approximated and are subject to normal manuracturing tolerances.


Neutral Supported Multiplex Cable

Description Aluminum conductors PE or XLPE insulated twisted together with a neutral supporting Messenger in AAC, AAAC or ACSR.

Construction Conductor Concentrically stranded, compressed 1350-H19 Aluminum. Duplex one phase conductor, Triplex two phase conductor, Quadruplex three phase conductors. Insulation Cross Linked Polyethylene (XLPE 90째C) or thermoplastic polyethylene (PE 75째C). Neutral supporting messenger AAC All Aluminum Conductor, AAAC All Aluminum Alloy Conductor or ACSR Aluminum conductor steel reinforced. Options Phase conductor in AAAC. Neutral covered. Additional conductor for Public lighting system. Overall Jacket.

Characteristics Operating Temperature 990째C, for XLPE insulation. 75째C, for PE insulation. Operating Voltage 600 V. 37


Applications Duplex: Overhead Secondary Distribution, street lighting, outdoor lighting or temporally installations. Triplex: Overhead Secondary Distribution, from pole to service entrance derivation. Quadruplex: Overhead Secondary Distribution Three-phase system, from pole to service entrance derivation.

Standards CENTELSA MULTIPLEX Cables are manufactured under the following standards: ASTM B231, NTC-308. Concentric-Lay-Stranded Aluminum 1350 Conductors ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts.

Certifications CENTELSA MULTIPLEX Cables are certified by: CIDET (Colombia). Certificate No. 01336 ICEA S-76-474. Note: Other configurations and sizes not specified herein are available upon request.

38


Neutral Supported Duplex 600V (International System Unit) Manufacturing Standard: ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts. CODE

SIZE STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER CLASS SECTION DIAMETER THICKNESS OVER AWG / No. (mm2) (mm) (mm) INSULATION kcmil (mm)

PEKINGESE 6 COLLIE 6 DACHSHUND 4 SPANIEL 4 DOBERMAN 2 MALEMUTE 1/0 SETTER 6 SHEPHERD 6 ESKIMO 4 TERRIER 4 CHOW 2 BULL 1/0 CHIHUAHUA 6 VIZSLA 6 HARRIER 4 WHIPPET 4 SCHNAUZER 2 HEELER 1/0 Notes:

1 7 1 7 7 19 1 7 1 7 7 19 1 7 1 7 7 19

SOLID B SOLID B B B SOLID B SOLID B B B SOLID B SOLID B B B

13.30 13.30 21.15 21.15 33.63 53.48 13.30 13.30 21.15 21.15 33.63 53.48 13.30 13.30 21.15 21.15 33.63 53.48

4.12 4.52 5.19 5.71 7.20 9.18 4.12 4.52 5.19 5.71 7.20 9.18 4.12 4.52 5.19 5.71 7.20 9.18

1.14 1.14 1.14 1.14 1.14 1.52 1.14 1.14 1.14 1.14 1.14 1.52 1.14 1.14 1.14 1.14 1.14 1.52

6.50 6.90 7.57 8.09 9.58 12.34 6.50 6.90 7.57 8.09 9.58 12.34 6.50 6.90 7.57 8.09 9.58 12.34

SELF SUPPORTING NEUTRAL TYPE

SIZE STRANDS TENSILE No. STRENGTH AWG / kcmil (kg)

6 6 4 AAC 4 2 1/0 6 6 4 ACSR 4 2 1/0 30.58 30.58 48.69 AAAC 48.69 77.47 123.3

7 7 7 7 7 7 6/1 6/1 6/1 6/1 6/1 6/1 7 7 7 7 7 7

256 256 400 400 613 903 540 540 845 845 1294 1986 502 502 799 799 1272 1939

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C1 (ohm/km)

AMPACITY 2 (A)3

AMPACITY 2 (A)4

95 100 142 149 227 360 112 117 170 177 271 429 101 105 152 159 242 384

2.12 2.16 1.33 1.36 0.854 0.537 2.12 2.16 1.33 1.36 0.854 0.537 2.12 2.16 1.33 1.36 0.854 0.537

70 70 90 90 120 160 70 70 90 90 120 160 70 70 90 90 120 160

85 85 115 115 150 205 85 85 115 115 150 205 85 85 115 115 150 205

1. DC resistance calculated based on a 28,172 ohm-mm2/km resistivity for aluminum. 2. 40째C Ambient temperature, 610 mm/seg wind speed, at sea level at 60 Hz. 3. 75째C conductor temperature. 4. 90째C conductor temperature. 5. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

39


Neutral Supported Duplex 600V Manufacturing Standard: ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts. CODE

APPROX. SELF SUPPORTING NEUTRAL DC SIZE STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER TOTAL (mils) SECTION DIAMETER THICKNESS OVER RESISTANCE AWG / No. TYPE SIZE STRANDS TENSILE WEIGHT (sq inches) (mils) (mils) INSULATION AT 20°C1 kcmil No. AWG / STRENGTH (pound/1000ft) (mils) (ohm/1000ft) kcmil (pound)

PEKINGESE 6 COLLIE 6 DACHSHUND 4 SPANIEL 4 DOBERMAN 2 MALEMUTE 1/0 SETTER 6 SHEPHERD 6 ESKIMO 4 TERRIER 4 CHOW 2 BULL 1/0 CHIHUAHUA 6 VIZSLA 6 HARRIER 4 WHIPPET 4 SCHNAUZER 2 HEELER 1/0

1 7 1 7 7 19 1 7 1 7 7 19 1 7 1 7 7 19

SOLID B SOLID B B B SOLID B SOLID B B B SOLID B SOLID B B B

0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 Notes:

162 178 204 225 283 361 162 178 204 225 283 361 162 178 204 225 283 361

45 45 45 45 45 60 45 45 45 45 45 60 45 45 45 45 45 60

256 272 298 318 377 486 256 272 298 318 377 486 256 272 298 318 377 486

7 7 7 7 7 7 6/1 6/1 6/1 6/1 6/1 6/1 7 7 7 7 7 7

6 6 4 AAC 4 2 1/0 6 6 4 ACSR 4 2 1/0 30.58 30.58 48.69 AAAC 48.69 77.47 123.3

564 564 882 882 1351 1991 1190 1190 1863 1863 2853 4378 1107 1107 1761 1761 2804 4275

64 67 96 100 153 242 75 78 114 119 182 289 68 71 102 107 163 258

0.646 0.658 0.406 0.414 0.260 0.164 0.646 0.658 0.406 0.414 0.260 0.164 0.646 0.658 0.406 0.414 0.260 0.164

AMPACITY 2 (A)3

AMPACITY 2 (A)4

70 70 90 90 120 160 70 70 90 90 120 160 70 70 90 90 120 160

85 85 115 115 150 205 85 85 115 115 150 205 85 85 115 115 150 205

1. DC resistance calculated based on a 16,946 ohm-mm2/km resistivity for aluminum. 2. 40°C Ambient temperature, 610 mm/seg wind speed, at sea level at 60 Hz. 3. 75°C conductor temperature. 4. 90°C conductor temperature. 5. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

Neutral Supported Triplex 600V (International System Unit) Manufacturing Standard: ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts. CODE

HAIOTIS PATELLA FUSUS OYSTER CLAM MUREX

SIZE STRANDS STRANDING CLASS AWG / No. kcmil

6 6 4 4 2 1/0

1 7 1 7 7 7

SOLID B SOLID B B B

CROSS CONDUCTOR INSULATION DIAMETER SECTION DIAMETER THICKNESS OVER (mm²) (mm) (mm) INSULATION (mm)

13.30 13.30 21.15 21.15 33.63 53.48

4.12 4.52 5.19 5.71 7.20 9.18

1.14 1.14 1.14 1.14 1.14 1.52

6.50 6.90 7.57 8.09 9.58 12.34

SELF SUPPORTING NEUTRAL TYPE

AAC

SIZE AWG / kcmil

STRANDS No.

6 6 4 4 2 1/0

7 7 7 7 7 7

TENSILE STRENGTH (Kg)

256 256 400 400 613 903

APPROX. TOTAL WEIGHT (Kg/Km)

153 162 226 240 361 582

DC RESISTANCE AT 20°C1 (ohm/Km)

AMPACITY 2 (A)3

AMPACITY 2 (A)4

2.12 2.16 1.33 1.36 0.854 0.537

70 70 90 90 120 160

85 85 115 115 150 205

Continued on page 41

40


Continued from page 40

Neutral Supported Triplex 600V (International System Unit)

CODE

SIZE STRANDS STRANDING CLASS AWG / No. kcmil

PURPURA 1/0 NASSA 2/0 TROPHON 2/0 MELITA 3/0 PORTUNUS 4/0 NANNYNOSE 336.4 PALUDINA 6 VOLUTA 6 WHELK 4 PERIWINKLE 4 CONCH 2 NERITINA 1/0 CENIA 1/0 RUNCINA 2/0 TRITON 2/0 MURSIA 3/0 ZUZARA 4/0 LIMPET 336.4 SCALLOP 4 STROMBUS 4 COCKLE 2 JANTHINA 1/0 RANELLA 1/0 CAVOLINIA 2/0 CLIO 2/0 AEGA 3/0 CERAPUS 4/0 COWRY 336.4 MINEX 6 HIPPA 6 PRAWN 4 BARNACLES 4 SHRIMP 2 GAMMARUS 1/0 LEDA 1/0 DUNGENESE 2/0 CYCLOPS 2/0 FLUSTRA 3/0 LEPAS 4/0 ARTEMIA 4 CRAB 4 SOLASTER 2 SANDCRAB 1/0 ECHINUS 1/0 CRAYFISH 2/0 SIPHO 2/0 FULGAR 3/0 ARCA 4/0 Notes:

19 7 19 19 19 19 1 7 1 7 7 7 19 7 19 19 19 19 1 7 7 7 19 7 19 19 19 19 1 7 1 7 7 7 19 7 19 19 19 1 7 7 7 19 7 19 19 19

B B B B B B SOLID B SOLID B B B B B B B B B SOLID B B B B B B B B B SOLID B SOLID B B B B B B B B SOLID B B B B B B B B

CROSS CONDUCTOR INSULATION DIAMETER SECTION DIAMETER THICKNESS OVER (mm²) (mm) (mm) INSULATION (mm)

53.48 67.43 67.43 85.03 107.2 170.5 13.30 13.30 21.15 21.15 33.63 53.48 53.48 67.43 67.43 85.03 107.2 170.5 21.15 21.15 33.63 53.48 53.48 67.43 67.43 85.03 107.2 170.5 13.30 13.30 21.15 21.15 33.63 53.48 53.48 67.43 67.43 85.03 107.2 21.15 21.15 33.63 53.48 53.48 67.43 67.43 85.03 107.2

9.18 10.31 10.31 11.58 13.00 16.39 4.12 4.52 5.19 5.71 7.20 9.18 9.18 10.31 10.31 11.58 13.00 16.39 5.19 5.71 7.20 9.18 9.18 10.31 10.31 11.58 13.00 16.39 4.12 4.52 5.19 5.71 7.20 9.18 9.18 10.31 10.31 11.58 13.00 5.19 5.71 7.20 9.18 9.18 10.31 10.31 11.58 13.00

1.52 1.52 1.52 1.52 1.52 2.03 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 2.03 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 1.52

12.34 13.47 13.47 14.74 16.16 20.57 6.50 6.90 7.57 8.09 9.58 12.34 12.34 13.47 13.47 14.74 16.16 20.57 7.57 8.09 9.58 12.34 12.34 13.47 13.47 14.74 16.16 20.57 6.50 6.90 7.57 8.09 9.58 12.34 12.34 13.47 13.47 14.74 16.16 7.57 8.09 9.58 12.34 12.34 13.47 13.47 14.74 16.16

SELF SUPPORTING NEUTRAL TYPE

SIZE AWG / kcmil

STRANDS No.

7 1/0 7 2/0 7 2/0 AAC 3/0 19 4/0 19 336.4 19 6 6/1 6 6/1 4 6/1 4 6/1 2 6/1 1/0 6/1 ACSR 1/0 6/1 2/0 6/1 2/0 6/1 3/0 6/1 4/0 6/1 336.4 18/1 6 6/1 6 6/1 4 6/1 2 6/1 ACSR 2 6/1 REDUCED 1 6/1 SIZE 1 6/1 1/0 6/1 2/0 6/1 4/0 6/1 7 30.58 7 30.58 7 48.69 7 48.69 7 77.47 AAAC 7 123.3 7 123.3 7 155.4 7 155.4 7 195.7 7 246.9 7 30.6 7 30.6 7 48.7 AAAC 7 77.5 REDUCED 77.5 7 SIZE 7 97.6 7 97.6 7 123.3 7 155.4

TENSILE STRENGTH (Kg)

903 1138 1138 1501 1823 2786 540 540 845 845 1294 1986 1986 2403 2403 3000 3784 3937 540 540 845 1294 1294 1616 1616 1986 2403 3784 502 502 799 799 1272 1939 1939 2444 2444 3077 3882 502 502 799 1272 1272 1603 1603 1939 2444

APPROX. TOTAL WEIGHT (Kg/Km)

571 715 702 865 1069 1713 170 179 254 267 404 651 640 803 789 975 1208 1788 221 235 353 570 559 701 687 847 1046 1676 158 168 235 249 376 606 595 746 732 903 1117 210 224 335 541 530 664 651 801 989

DC RESISTANCE AT 20°C1 (ohm/Km)

AMPACITY 2 (A)3

AMPACITY 2 (A)4

0.537 0.426 0.426 0.338 0.268 0.169 2.12 2.16 1.33 1.36 0.854 0.537 0.537 0.426 0.426 0.338 0.268 0.169 1.33 1.36 0.854 0.537 0.537 0.426 0.426 0.338 0.268 0.169 2.12 2.16 1.33 1.36 0.854 0.537 0.537 0.426 0.426 0.338 0.268 1.33 1.36 0.854 0.537 0.537 0.426 0.426 0.338 0.268

160 185 185 215 245 325 70 70 90 90 120 160 160 185 185 215 245 325 90 90 120 160 160 185 185 215 245 325 70 70 90 90 120 160 160 185 185 215 245 90 90 120 160 160 185 185 215 245

205 235 235 275 315 420 85 85 115 115 150 205 205 235 235 275 315 420 115 115 150 205 205 235 235 275 315 420 85 85 115 115 150 205 205 235 235 275 315 115 115 150 205 205 235 235 275 315

1. DC resistance calculated based on a 28,172 ohm-mm2/km resistivity for aluminum. 2. 40°C Ambient temperature, 610 mm/seg wind speed, at sea level at 60 Hz. 3. 75°C conductor temperature. 4. 90°C conductor temperature. 5. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

41


Neutral Supported Triplex 600V Manufacturing Standard: ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts.

CODE

SIZE STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER (mils) SECTION DIAMETER THICKNESS OVER AWG / No. (sq inches) (mils) (mils) INSULATION kcmil (mils)

HAIOTIS 6 PATELLA 6 FUSUS 4 OYSTER 4 CLAM 2 MUREX 1/0 PURPURA 1/0 NASSA 2/0 TROPHON 2/0 MELITA 3/0 PORTUNUS 4/0 NANNYNOSE 336.4 PALUDINA 6 VOLUTA 6 WHELK 4 PERIWINKLE 4 CONCH 2 NERITINA 1/0 CENIA 1/0 RUNCINA 2/0 TRITON 2/0 MURSIA 3/0 ZUZARA 4/0 LIMPET 336.4 SCALLOP 4 STROMBUS 4 COCKLE 2 JANTHINA 1/0 RANELLA 1/0 CAVOLINIA 2/0 CLIO 2/0 AEGA 3/0 CERAPUS 4/0 COWRY 336.4 MINEX 6 HIPPA 6 PRAWN 4 BARNACLES 4 SHRIMP 2 GAMMARUS 1/0 LEDA 1/0 DUNGENESE 2/0 CYCLOPS 2/0 FLUSTRA 3/0 LEPAS 4/0 ARTEMIA 4 CRAB 4 SOLASTER 2 SANDCRAB 1/0

1 7 1 7 7 7 19 7 19 19 19 19 1 7 1 7 7 7 19 7 19 19 19 19 1 7 7 7 19 7 19 19 19 19 1 7 1 7 7 7 19 7 19 19 19 1 7 7 7

SOLID B SOLID B B B B B B B B B SOLID B SOLID B B B B B B B B B SOLID B B B B B B B B B SOLID B SOLID B B B B B B B B SOLID B B B

0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.0829 0.1045 0.1045 0.1318 0.1662 0.2642 0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.0829 0.1045 0.1045 0.1318 0.1662 0.2642 0.0328 0.0328 0.0521 0.0829 0.0829 0.1045 0.1045 0.1318 0.1662 0.2642 0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.0829 0.1045 0.1045 0.1318 0.1662 0.0328 0.0328 0.0521 0.0829

162 178 204 225 283 361 361 406 406 456 512 645 162 178 204 225 283 361 361 406 406 456 512 645 204 225 283 361 361 406 406 456 512 645 162 178 204 225 283 361 361 406 406 456 512 204 225 283 361

45 45 45 45 45 60 60 60 60 60 60 80 45 45 45 45 45 60 60 60 60 60 60 80 45 45 45 60 60 60 60 60 60 80 45 45 45 45 45 60 60 60 60 60 60 45 45 45 60

256 272 298 318 377 486 486 530 530 580 636 810 256 272 298 318 377 486 486 530 530 580 636 810 298 318 377 486 486 530 530 580 636 810 256 272 298 318 377 486 486 530 530 580 636 298 318 377 486

APPROX. DC TOTAL RESISTANCE SIZE STRANDS TENSILE WEIGHT AT 20째C1 AWG / No. STRENGTH (pound/1000ft) (ohm/1000ft)

SELF SUPPORTING NEUTRAL TYPE

kcmil

7 6 7 6 7 4 7 4 7 2 7 1/0 AAC 7 1/0 7 2/0 7 2/0 3/0 19 4/0 19 336.4 19 6 6/1 6 6/1 4 6/1 4 6/1 2 6/1 1/0 6/1 ACSR 1/0 6/1 2/0 6/1 2/0 6/1 3/0 6/1 4/0 6/1 336.4 18/1 6 6/1 6 6/1 4 6/1 2 6/1 ACSR 2 6/1 REDUCED 1 6/1 SIZE 1 6/1 1/0 6/1 2/0 6/1 4/0 6/1 7 30.58 7 30.58 7 48.69 7 48.69 7 77.47 AAAC 7 123.3 7 123.3 7 155.4 7 155.4 7 195.7 7 246.9 7 30.6 AAAC 7 30.6 REDUCED 48.7 7 SIZE 7 77.5

AMPACITY 2 (A)3

AMPACITY 2 (A)4

70 70 90 90 120 160 160 185 185 215 245 325 70 70 90 90 120 160 160 185 185 215 245 325 90 90 120 160 160 185 185 215 245 325 70 70 90 90 120 160 160 185 185 215 245 90 90 120 160

85 85 115 115 150 205 205 235 235 275 315 420 85 85 115 115 150 205 205 235 235 275 315 420 115 115 150 205 205 235 235 275 315 420 85 85 115 115 150 205 205 235 235 275 315 115 115 150 205

(pound)

564 564 882 882 1351 1991 1991 2509 2509 3309 4019 6142 1190 1190 1863 1863 2853 4378 4378 5298 5298 6614 8342 8679 1190 1190 1863 2853 2853 3563 3563 4378 5298 8342 1107 1107 1761 1761 2804 4275 4275 5388 5388 6784 8558 1107 1107 1761 2804

103 109 152 161 242 391 384 481 472 581 718 1151 114 120 170 180 272 438 430 540 530 655 812 1202 149 158 237 383 376 471 462 569 703 1126 107 113 158 168 252 407 400 501 492 607 751 141 150 225 364

0.646 0.658 0.406 0.414 0.260 0.164 0.164 0.130 0.130 0.103 0.0817 0.0514 0.646 0.658 0.406 0.414 0.260 0.164 0.164 0.130 0.130 0.103 0.0817 0.0514 0.406 0.414 0.260 0.164 0.164 0.130 0.130 0.103 0.0817 0.0514 0.646 0.658 0.406 0.414 0.260 0.164 0.164 0.130 0.130 0.103 0.0817 0.406 0.414 0.260 0.164

Continued on page 43

42


Continued from page 42

Neutral Supported Triplex 600V

CODE

ECHINUS CRAYFISH SIPHO FULGAR ARCA Notes:

SIZE STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER (mils) SECTION DIAMETER THICKNESS OVER AWG / No. (sq inches) (mils) (mils) INSULATION kcmil (mils)

1/0 2/0 2/0 3/0 4/0

19 7 19 19 19

B B B B B

0.0829 0.1045 0.1045 0.1318 0.1662

361 406 406 456 512

60 60 60 60 60

486 530 530 580 636

APPROX. DC TOTAL RESISTANCE TENSILE WEIGHT AT 20°C1 STRENGTH (pound/1000ft) (ohm/1000ft)

SELF SUPPORTING NEUTRAL TYPE

SIZE AWG / kcmil

77.5 97.6 AAAC REDUCED 97.6 123.3 SIZE 155.4

STRANDS No.

AMPACITY 2 (A)3

AMPACITY 2 (A)4

160 185 185 215 245

205 235 235 275 315

(pound)

7 7 7 7 7

2804 3534 3534 4275 5388

356 447 437 538 664

0.164 0.130 0.130 0.103 0.0817

1. DC resistance calculated based on a 16,946 ohm-mm2/km resistivity for aluminum. 2. 40°C Ambient temperature, 610 mm/seg wind speed, at sea level at 60 Hz. 3. 75°C conductor temperature. 4. 90°C conductor temperature. 5. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

Neutral Supported Quadruplex 600V (International System Unit) Manufacturing Standard: ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts. CODE

SELF SUPPORTING NEUTRAL SIZE STRANDS STRANDING CROSS CONDUCTOR INSULATION DIAMETER CLASS SECTION DIAMETER THICKNESS OVER AWG / No. TYPE SIZE STRANDS TENSILE (mm²) (mm) (mm) INSULATION kcmil No. AWG / STRENGTH (mm) kcmil (Kg)

CLYDESDALE 4 PINTO 4 MUSTANG 2 CRIOLLO 1/0 PERCHERON 2/0 HANOVERIAN 3/0 OLDENBURG 4/0 LIPPIZANER 336.4 MOROCHUCA 6 CHOLA 6 MORGAN 4 HACKNEY 4 PALOMINO 2 COSTENA 1/0 GRULLO 2/0 SUFFOLK 3/0 APPALOOSA 4/0 BRONCO 336.4 BAY 6 FRENCH-COACH 6 GERMAN-COACH 4 ARABIAN 4 BELGIAN 2 SHETLAND 1/0 THOROUGHBRED 2/0 TROTTER 3/0 WALKING 4/0 Notes:

1 7 7 19 19 19 19 19 1 7 1 7 7 19 19 19 19 19 1 7 1 7 7 19 19 19 19

SOLID B B B B B B B SOLID B SOLID B B B B B B B SOLID B SOLID B B B B B B

21.15 21.15 33.63 53.48 67.43 85.03 107.2 170.5 13.30 13.30 21.15 21.15 33.63 53.48 67.43 85.03 107.2 170.5 13.30 13.30 21.15 21.15 33.63 53.48 67.43 85.03 107.2

5.19 5.71 7.20 9.18 10.31 11.58 13.00 16.39 4.12 4.52 5.19 5.71 7.20 9.18 10.31 11.58 13.00 16.39 4.12 4.52 5.19 5.71 7.20 9.18 10.31 11.58 13.00

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52

7.57 8.09 9.58 12.34 13.47 14.74 16.16 20.57 6.50 6.90 7.57 8.09 9.58 12.34 13.47 14.74 16.16 20.57 6.50 6.90 7.57 8.09 9.58 12.34 13.47 14.74 16.16

4 4 2 AAC 1/0 2/0 3/0 4/0 336.4 6 6 4 4 2 ACSR 1/0 2/0 3/0 4/0 336.4 30.58 30.58 48.69 48.69 77.47 AAAC 123.3 155.4 195.7 246.9

7 7 7 7 7 19 19 19 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 18/1 7 7 7 7 7 7 7 7 7

400 400 613 903 1138 1501 1823 2786 540 540 845 845 1294 1986 2403 3000 3784 3937 502 502 799 799 1272 1939 2444 3077 3882

APPROX. TOTAL WEIGHT (Kg/Km)

310 330 494 781 958 1179 1454 2332 228 242 337 358 538 851 1046 1289 1593 2407 216 230 319 340 509 806 989 1217 1502

DC RESISTANCE AT 20°C1 (ohm/Km)

1.33 1.36 0.854 0.537 0.426 0.338 0.268 0.169 2.12 2.16 1.33 1.36 0.854 0.537 0.426 0.338 0.268 0.169 2.12 2.16 1.33 1.36 0.854 0.537 0.426 0.338 0.268

1. DC resistance calculated based on a 28,172 ohm-mm2/km resistivity for aluminum. 2. 40°C Ambient temperature, 610 mm/seg wind speed, at sea level at 60 Hz. 3. 75°C conductor temperature. 4. 90°C conductor temperature. 5. Data herein indicated are approximated and are subject to normal manuracturing tolerances.

43

AMPACITY 2 (A)3

80 80 105 140 160 185 210 280 60 60 80 80 105 140 160 185 210 280 60 60 80 80 105 140 160 185 210

AMPACITY 2 (A)4

100 100 135 180 205 235 275 370 75 75 100 100 135 180 205 235 275 370 75 75 100 100 135 180 205 235 275


Neutral Supported Quadruplex 600V Manufacturing Standard: ICEA S-76-474. Neutral supported power cables assemblies with weather resistant extruded insulation rated 600 volts. CODE

SIZE STRANDS STRANDING CROSS CONDUCTOR INSULATION (mils) SECTION DIAMETER THICKNESS AWG / No. (sq inches) (mils) (mils) kcmil

CLYDESDALE 4 PINTO 4 MUSTANG 2 CRIOLLO 1/0 PERCHERON 2/0 HANOVERIAN 3/0 OLDENBURG 4/0 LIPPIZANER 336.4 MOROCHUCA 6 CHOLA 6 MORGAN 4 HACKNEY 4 PALOMINO 2 COSTENA 1/0 GRULLO 2/0 SUFFOLK 3/0 APPALOOSA 4/0 BRONCO 336.4 BAY 6 FRENCH-COACH 6 GERMAN-COACH 4 ARABIAN 4 BELGIAN 2 SHETLAND 1/0 THOROUGHBRED 2/0 TROTTER 3/0 WALKING 4/0

1 7 7 19 19 19 19 19 1 7 1 7 7 19 19 19 19 19 1 7 1 7 7 19 19 19 19

SOLID B B B B B B B SOLID B SOLID B B B B B B B SOLID B SOLID B B B B B B

0.0328 0.0328 0.0521 0.0829 0.105 0.132 0.166 0.264 0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.105 0.132 0.166 0.264 0.0206 0.0206 0.0328 0.0328 0.0521 0.0829 0.105 0.132 0.166 Notes:

44

204 225 283 361 406 456 512 645 162 178 204 225 283 361 406 456 512 645 162 178 204 225 283 361 406 456 512

45 45 45 60 60 60 60 80 45 45 45 45 45 60 60 60 60 80 45 45 45 45 45 60 60 60 60

APPROX. DIAMETER SELF SUPPORTING NEUTRAL TOTAL OVER TYPE SIZE STRANDS TENSILE WEIGHT INSULATION No. AWG / STRENGTH (pound/1000ft) (mils) kcmil (pound)

298 318 377 486 530 580 636 810 256 272 298 318 377 486 530 580 636 810 256 272 298 318 377 486 530 580 636

4 4 2 AAC 1/0 2/0 3/0 4/0 336.4 6 6 4 4 2 ACSR 1/0 2/0 3/0 4/0 336.4 30.58 30.58 48.69 48.69 AAAC 77.47 123.3 155.4 195.7 246.9

7 7 7 7 7 19 19 19 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 18/1 7 7 7 7 7 7 7 7 7

882 882 1351 1991 2509 3309 4019 6142 1190 1190 1863 1863 2853 4378 5298 6614 8342 8679 1107 1107 1761 1761 2804 4275 5388 6784 8558

208 222 332 525 644 792 977 1568 153 162 227 240 361 572 703 866 1071 1618 145 155 214 228 342 541 665 818 1010

DC RESISTANCE AT 20째C1 (ohm/1000ft)

AMPACITY 2 (A)3

AMPACITY 2 (A)4

0.406 0.414 0.260 0.164 0.130 0.103 0.0817 0.0514 0.646 0.658 0.406 0.414 0.260 0.164 0.130 0.103 0.0817 0.0514 0.646 0.658 0.406 0.414 0.260 0.164 0.130 0.103 0.0817

80 80 105 140 160 185 210 280 60 60 80 80 105 140 160 185 210 280 60 60 80 80 105 140 160 185 210

100 100 135 180 205 235 275 370 75 75 100 100 135 180 205 235 275 370 75 75 100 100 135 180 205 235 275

1. DC resistance calculated based on a 16,946 ohm-mm2/km resistivity for aluminum. 2. 40째C Ambient temperature, 610 mm/seg wind speed, at sea level at 60 Hz. 3. 75째C conductor temperature. 4. 90째C conductor temperature. 5. Data herein indicated are approximated and are subject to normal manuracturing tolerances.