Flexible cables

Page 1

Type ST-C Cables Extra Hard Service Thermoplastic Insulated, C: Common Use

Description Multi-conductor Cable, two, three or four flexible soft copper conductors polyolefin insulated, twisted and external PVC Rubber jacket

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Polyolefin (75째 C) Jacket Flame retardant Polyvinyl Chloride with content of rubber

Characteristics Operating Temperature 75째 C. Operating Voltage 600 V.

Applications Hard Service Cord for equipment and portable tools, special for factories, scenes and display cabinets. Open wiring installation, in portable extensions with terminals. By being of common use, it can be used like portable cord, control and power cable. Easy handling and flexibility in reduced spaces.

Specifications CENTELSA ST-C Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

CENTELSA Specifications for ST-C Cables 7


Certifications CENTELSA ST-C Flexible cords are certified by: CIDET (Colombia). Cert. No. 02005, according to RETIE (Colombian Technical Code of Electrical Installations) requirements

Colors Conductors identification: 2, black-white; 3, black-white-green; 4, blackwhite-red-green. Black colored Jacket.

Packaging Wood Reels. Reel lengths between 500 m and 2500 m.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

8


Flexible Cord Type ST-C 600V, 60oC (International System Unit) Extra Hard Service Thermoplastic Insulated, C: Common Use Standards: UL 62, NTC 2356 and CENTELSA specifications for ST-C cables

SIZE AWG

20

18

16

14

12

10

8

6

4

2

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41 2.41

50 59 70 69 82 99 86 104 127 113 139 171 152 190 255 231 288 382 380 476 630 635 790 976 902 1133 1407 1254 1600 2003

35.4 35.4 35.4 22.1 22.1 22.1 13.6 13.6 13.6 8.63 8.63 8.63 5.45 5.45 5.45 3.40 3.40 3.40 2.11 2.11 2.11 1.33 1.33 1.33 0.843 0.843 0.843 0.532 0.532 0.532

10

0.254

0.51

0.97

0.64

16

0.254

0.81

1.23

0.76

26

0.254

1.32

1.51

0.76

41

0.254

2.08

1.98

0.76

65

0.254

3.29

2.52

0.76

104

0.254

5.27

3.21

0.76

168

0.254

8.51

3.66

1.14

266

0.254

13.48

4.77

1.52

420

0.254

21.28

6.00

1.52

665

0.254

33.70

7.56

1.52

6.26 6.62 7.23 7.26 7.70 8.43 7.82 8.30 9.11 8.76 9.32 10.24 9.84 10.48 12.32 12.00 12.74 14.78 15.25 16.19 18.77 20.05 21.28 23.33 23.29 24.71 27.08 26.41 28.07 30.85

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

2

-

10

7

13

10

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 75째C conductor temperature, and Section 400 of NEC (NTC 2050) and 30째C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

9


Flexible Cord Type ST-C 600V, 60oC Extra Hard Service Thermoplastic Insulated, C: Common Use Standards: UL 62, NTC 2356 and CENTELSA specifications for ST-C cables

SIZE AWG

20

18

16

14

12

10

8

6

4

2

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils)

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

DIAMETER (mils)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils)

10

10.0

1.00

38

25

16

10.0

1.60

48

30

26

10.0

2.60

59

30

41

10.0

4.10

78

30

65

10.0

6.50

99

30

104

10.0

10.40

126

30

168

10.0

16.80

144

45

266

10.0

26.60

188

60

420

10.0

42.00

236

60

665

10.0

66.50

298

60

30 30 30 30 30 30 30 30 30 30 30 30 30 30 45 45 45 60 60 60 80 80 80 80 95 95 95 95 95 95

246 261 284 286 303 332 308 327 359 345 367 403 387 413 485 472 502 582 600 637 739 789 838 919 917 973 1066 1040 1105 1215

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20째C 1 (ohm/kft)

33 39 47 46 55 67 58 70 85 76 93 115 102 128 172 155 194 256 256 320 423 427 531 656 606 761 945 843 1075 1346

10.8 10.8 10.8 6.74 6.74 6.74 4.15 4.15 4.15 2.63 2.63 2.63 1.66 1.66 1.66 1.04 1.04 1.04 0.642 0.642 0.642 0.406 0.406 0.406 0.257 0.257 0.257 0.162 0.162 0.162

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

2

-

10

7

13

10

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notas: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 75째C conductor temperature, and Section 400 of NEC (NTC 2050) and 30째C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

10


Flexible Cords Type ST Extra Hard Service Thermoplastic Insulated

Description Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60째 C) Jacket Flame Retardant Polyvinyl chloride (PVC 60째 C)

Characteristics Operating Temperature 60째 C. Operating Voltage 600 V.

Applications Hard Service Cord for equipment and portable tools, special for factories, scenes and display cabinets. Open wiring installation, in portable extensions with terminals.

Specifications CENTELSA ST Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

Certifications CENTELSA ST Flexible cords are certified by UL, File E203934 11


Colors Conductors identification: 2, black-white; 3, black-white-green; 4, blackwhite-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

12


Flexible Cords Type ST 600V, 60oC (International System Unit) Extra Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

14

12

10

8

6

4

2

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41 2.41 2.79 2.79 3.18 3.18 3.18 3.56 3.56 3.56 3.94 3.94 3.94 4.32

210 244 290 283 331 394 357 425 512 535 644 818 692 851 1082 1088 1327 1674 1541 1899 2388

8.63 8.63 8.63 5.45 5.45 5.45 3.40 3.40 3.40 2.11 2.11 2.11 1.33 1.33 1.33 0.843 0.843 0.843 0.532 0.532 0.532

41

0.254

2.08

1.98

1.14

65

0.254

3.29

2.52

1.14

104

0.254

5.27

3.21

1.14

168

0.254

8.51

3.66

1.52

266

0.254

13.48

4.12

1.52

420

0.254

21.28

6.72

1.52

665

0.254

33.70

8.58

1.52

12.91 13.58 14.71 14.77 15.53 16.80 16.15 17.02 18.47 19.40 20.45 23.01 21.10 22.23 24.90 27.09 28.62 31.96 31.59 33.41 37.15

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60째C conductor temperature, and Section 400 of NEC (NTC 2050) and 30째C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

13


Flexible Cords Type ST 600V, 60oC Extra Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

14

12

10

8

6

4

2

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils)

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

DIAMETER (mils)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20째C 1 (ohm/kft)

80 80 80 95 95 95 95 95 95 110 110 125 125 125 140 140 140 155 155 155 170

141 164 195 190 222 265 240 286 344 359 433 550 465 572 727 731 892 1125 1036 1277 1605

2.63 2.63 2.63 1.66 1.66 1.66 1.04 1.04 1.04 0.642 0.642 0.642 0.406 0.406 0.406 0.257 0.257 0.257 0.162 0.162 0.162

41

10.0

4.10

78

45

65

10.0

6.50

99

45

104

10.0

10.40

126

45

168

10.0

16.80

144

60

266

10.0

26.60

162

60

420

10.0

42.00

265

60

665

10.0

66.50

338

60

508 535 579 582 611 661 636 670 727 764 805 906 831 875 980 1066 1127 1258 1244 1315 1463

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60째C conductor temperature, and Section 400 of NEC (NTC 2050) and 30째C ambient temperature. 3. Two current carrying conductors. 4.Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

14


Flexible Cords Type SJT Junior Hard Service Thermoplastic Insulated

Description Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60째 C) Jacket Flame Retardant Polyvinyl chloride (PVC 60째 C)

Characteristics Operating Temperature 60째 C. Operating Voltage 300 V.

Applications Junior Hard Service Cord for industrial, commercial and residential equipment. Open wiring installation, in portable extensions with terminals.

Specifications CENTELSA SJT Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

15


Certifications CENTELSA SJT Flexible cords are certified by UL, File E203934

Colors Conductors identification: 2, black-white; 3, black-white-green; 4, blackwhite-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

16


Flexible Cords Type SJT 600V, 60oC (International System Unit) Junior Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

18

16

14

12

10

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.52 1.52 1.52

69 82 99 86 104 127 113 139 171 169 208 255 298 363 445

22.1 22.1 22.1 13.6 13.6 13.6 8.63 8.63 8.63 5.45 5.45 5.45 3.40 3.40 3.40

16

0.254

0.81

1.23

0.76

26

0.254

1.32

1.51

0.76

41

0.254

2.08

1.98

0.76

65

0.254

3.29

2.52

0.76

104

0.254

5.27

3.21

1.14

7.26 7.70 8.43 7.82 8.30 9.11 8.76 9.32 10.24 10.62 11.26 12.32 14.35 15.22 16.67

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

10

7

13

10

18

15

25

20

30

25

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

10

7

13

10

18

15

25

20

30

25

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cords Type SJT 600V, 60oC Junior Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

18

16

14

12

10

Notes:

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils)

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

DIAMETER (mils)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils)

16

10.0

1.60

48

30

26

10.0

2.60

59

30

41

10.0

4.10

78

30

65

10.0

6.50

99

30

104

10.0

10.40

126

45

30 30 30 30 30 30 30 30 30 45 45 45 60 60 60

286 303 332 308 327 359 345 367 403 418 443 485 565 599 656

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20°C 1 (ohm/kft)

46 55 67 58 70 85 76 93 115 114 140 172 200 244 299

6.74 6.74 6.74 4.15 4.15 4.15 2.63 2.63 2.63 1.66 1.66 1.66 1.04 1.04 1.04

1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

17


Flexible Cords Type SVT Service Vacuum-cleaner cord, Thermoplastic Insulated

Description Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction Conductor Flexible soft copper conductor, Class M stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60째 C) Jacket Flame Retardant Polyvinyl chloride (PVC 60째 C)

Characteristics Operating Temperature 60째 C. Operating Voltage 300 V.

Applications Service Cord, vacuum cleaner cord computers and similar equipments. Open wiring installation, in portable extensions with terminals.

Specifications CENTELSA SVT Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

18


Certifications CENTELSA SVT Flexible cords are certified by UL, File E203934

Colors Conductors identification: 2, black-white; 3, black-white-green; 4, black-whitered-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

19


Flexible Cord Type SVT 300V 60°C (International System Unit) Service Vacuum-cleaner cord, Thermoplastic Insulated Standard: UL 62, NTC-ICONTEC 2356. Flexible and Fixture Wire

SIZE AWG

18

16

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

2 3 4 2 3 4

41

0.160

0.82

65

0.160

1.31

DIAMETER (mm)

1.16 6.76 6.00 1.48 6.76 6.00

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

0.76 0.76 0.76 0.76 0.76 0.76

46 56 68 62 76 94

22.1 22.1 22.1 13.6 13.6 13.6

0.38

0.38

5.60 5.91 6.43 6.24 6.60 7.20

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

10

7

13

10

Notes: 1. Fourth conductor is used as grounding conductor. 2. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 3. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 4. Two current carrying conductors. 5. Three current carrying conductors. 6. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cord Type SVT 300V 60°C Service Vacuum-cleaner cord, Thermoplastic Insulated Standard: UL 62, NTC-ICONTEC 2356. Flexible and Fixture Wire

SIZE AWG

18

16

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils)

2 3 4 2 3 4

DIAMETER (mils)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20°C 1 (ohm/kft)

30 30 30 30 30 30

31 38 46 41 51 63

6.74 6.74 6.74 4.15 4.15 4.15

41

6.3

1.63

46

15

65

6.3

2.58

58

15

220 233 253 246 260 284

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

10

7

13

10

Notes: 1. Fourth conductor is used as grounding conductor. 2. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 3. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 4. Two current carrying conductors. 5. Three current carrying conductors. 6. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

20


Parallel Cord Type SPT-C Parallel Cord, Thermoplastic Insulated

Description Two copper flexible copper conductor, paralleled and PVC insulated.

Construction Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60째 C) Integral insulation with separation membrane, and polarization ridges in one conductor.

Characteristics Operating Temperature 60째 C. Operating Voltage 300 V. (600V optional)

Applications Service Cord, for portable electrical devices. Open wiring installation, in portable extensions with terminals.

Specifications CENTELSA SPT Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

CENTELSA Specifications for SPT-C Cables

Certifications CENTELSA SPT-C Paralleled cords are certified by: CIDET (Colombia). Cert. No. 02004, according to RETIE (Colombian Technical Code of Electrical Installations) requirements 21


Colors White, grey brown and black. Optional with red strip at one conductor for polarization indication.

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

22


Paralleled Cord Type SPT-C 300V, 60°C (International System Unit) Parallel Cord, Thermoplastic Insulated Standards: UL 62, NTC 2356 and CENTELSA specifications for SPT-C cables

COPPER CONDUCTOR SIZE AWG

2 2 2 2 2 2

X X X X X X

STRANDS

22 20 18 16 14 12

7 10 16 26 41 65

STRAND SECTION DIAMETER (mm2) (mm)

0.254 0.254 0.254 0.254 0.254 0.254

DIAMETER (mm)

0.35 0.51 0.81 1.32 2.08 3.29

0.76 0.97 1.23 1.51 1.98 2.52

INSULATION THICKNESS (mm)

0.51 0.51 0.64 0.64 0.64 0.64

EXTERNAL DIMENSIONS (mm)

1.86 2.07 2.59 2.87 3.34 3.88

X X X X X X

3.72 4.14 5.17 5.73 6.67 7.75

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

AMPACITY 2 (A)

14 17 28 39 57 84

49.6 34.7 21.7 13.3 8.46 5.34

2 10 13 18 25

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cord Type SPT-C 300V, 60°C) Parallel Cord, Thermoplastic Insulated Standards: UL 62, NTC 2356 and CENTELSA specifications for SPT-C cables COPPER CONDUCTOR SIZE AWG

2 2 2 2 2 2

X X X X X X

STRANDS

22 20 18 16 14 12

7 10 16 26 41 65

STRAND SECTION DIAMETER (kcmil) (mils)

10.0 10.0 10.0 10.0 10.0 10.0

0.70 1.00 1.60 2.60 4.10 6.50

DIAMETER (mils)

30 38 48 59 78 99

INSULATION THICKNESS (mils)

20 20 25 25 25 25

EXTERNAL DIMENSIONS (mils)

73 82 102 113 131 153

X X X X X X

147 163 204 226 263 305

APPROX. TOTAL WEIGHT (lb/kft)

9 12 19 26 38 56

DC RESISTANCE AT 20°C 1 (ohm/kft)

AMPACITY 2 (A)

15.1 10.6 6.61 4.07 2.58 1.63

2 10 13 18 25

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

23


Paralleled Cord Type SPT-1 SPT-2 SPT-3 Parallel Cord, Thermoplastic Insulated

Description Two copper flexible copper conductor, paralleled and PVC insulated. Conductor Flexible soft copper conductor, Class M stranded for SPT-1 and SPT2 Flexible soft copper conductor, Class K stranded for SPT-3 Insulation Flame Retardant Polyvinyl chloride (PVC 60째 C) Integral insulation with separation membrane, and polarization ridges in one conductor.

Characteristics Operating Temperature 60째 C. Operating Voltage 300 V.

Applications SPT-1: Portable lamps feeders, fans, radios, clocks, household appliances and office equipment. SPT-2: Same as above, stereo and video devices SPT-3: Freezers, coolers, air conditioning equipment, dish washing machines, waste disposers and office equipment.

Specifications CENTELSA SPT-1, SPT-2 and SPT-3 Paralleled Cords are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords 24


UL 62, NTC-2356 Flexible Cord and Fixture Wire.

Colors White, grey, brown and black.

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

25


Paralleled Cords Type SPT-1 SPT-2 SPT-3 300V, 60°C (International System Unit) Parallel Cord, Thermoplastic Insulated Standard: UL 62, NTC 2356. Flexible and Fixture Wire

COPPER CONDUCTOR TYPE

SPT-1 SPT-2

SPT-3

SIZE AWG

2 2 2 2 2 2 2 2 2

X X X X X X X X X

STRANDS

20 18 18 16 18 16 14 12 10

26 41 41 65 16 26 41 65 104

STRAND SECTION DIAMETER (mm2) (mm)

0.160 0.160 0.160 0.160 0.254 0.254 0.254 0.254 0.254

0.52 0.82 0.82 1.31 0.81 1.32 2.08 3.29 5.27

DIAMETER (mm)

0.92 1.16 1.16 1.48 1.23 1.51 1.98 2.52 3.21

INSULATION THICKNESS (mm)

0.76 0.76 1.14 1.14 1.52 1.52 2.03 2.41 2.79

EXTERNAL DIMENSIONS (mm)

2.52 2.76 3.53 3.85 4.39 4.67 6.16 7.48 8.96

X 4.63 X 5.11 X 6.78 X 7.42 X 8.49 X 9.05 X 11.01 X 12.87 X 15.04

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

AMPACITY 2 (A)

17 24 36 50 51 68 115 177 268

33.6 21.3 21.3 13.5 21.7 13.3 8.46 5.34 3.34

2 10 10 13 10 13 18 25 30

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cords Type SPT-1 SPT-2 SPT-3 300V, 60°C Parallel Cord, Thermoplastic Insulated Standard: UL 62, NTC 2356. Flexible and Fixture Wire COPPER CONDUCTOR TYPE

SPT-1 SPT-2

SPT-3

SIZE AWG

2 2 2 2 2 2 2 2 2

X X X X X X X X X

STRANDS

20 18 18 16 18 16 14 12 10

26 41 41 65 16 26 41 65 104

STRAND SECTION DIAMETER (kcmil) (mils)

6.3 6.3 6.3 6.3 10.0 10.0 10.0 10.0 10.0

1.03 1.63 1.63 2.58 1.60 2.60 4.10 6.50 10.40

DIAMETER (mils)

36 46 46 58 48 59 78 99 126

INSULATION THICKNESS (mils)

30 30 45 45 60 60 80 95 110

EXTERNAL DIMENSIONS (mils)

99 109 139 152 173 184 243 295 353

X X X X X X X X X

182 201 267 292 334 356 434 507 592

APPROX. TOTAL WEIGHT (lb/kft)

12 16 24 33 35 46 77 119 180

DC RESISTANCE AT 20°C 1 (ohm/kft)

10.3 6.50 6.50 4.10 6.61 4.07 2.58 1.63 1.02

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

26

AMPACITY 2 (A)

2 10 10 13 10 13 18 25 30


Cables Type TFF and TWK Thermoplastic Insulation, Flexible Fixture Wire Thermoplastic Insulation, Suitable for Wet Locations, Class K Stranding

Description Soft copper flexible conductor PVC insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60째 C)

Characteristics Operation Temperature 60째 C. Operating Voltage 600 V.

Applications Internal equipment wiring, boards, in ducts or raceways. Also used in low voltage automotive wiring.

Specifications CENTELSA TFF and TWK Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire, for TFF UL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

Colors Black, white, red, green, yellow, blue.

27


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

28


Cables Type TFF and TWK 600V, 60°C (International System Units) Thermoplastic Insulation, Flexible Fixture Wire Thermoplastic Insulation, Suitable for Wet Locations, Class K Stranding Standard:

TYPE

TFF

TWK

UL 62, NTC 2356. Flexible and Fixture Wire, for TFF UL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

SIZE AWG

18 16 14 12 10 8 6

STRANDS

16 26 41 65 104 168 266

STRAND SECTION CONDUCTOR DIAMETER (mm2) DIAMETER (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.81 1.32 2.08 3.29 5.27 8.51 13.48

1.23 1.51 1.98 2.52 3.21 3.66 4.12

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

AMPACITY 2 (A)

0.76 0.76 0.76 0.76 0.76 1.14 1.52

2.83 3.11 3.58 4.12 4.81 6.04 7.28

15 20 29 42 63 104 164

21.7 13.3 8.46 5.34 3.34 2.07 1.30

10 13 18 25 30 40 55

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type TFF and TWK 600V, 60°C Thermoplastic Insulation, Flexible Fixture Wire Thermoplastic Insulation, Suitable for Wet Locations, Class K Stranding Standard:

TYPE

TFF

TWK

UL 62, NTC 2356. Flexible and Fixture Wire, for TFF UL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

SIZE AWG

18 16 14 12 10 8 6

STRANDS

16 26 41 65 104 168 266

STRAND SECTION CONDUCTOR DIAMETER (kcmil) DIAMETER (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.60 2.60 4.10 6.50 10.40 16.80 26.60

48 59 78 99 126 144 162

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20°C 1 (ohm/kft)

AMPACITY 2 (A)

30 30 30 30 30 45 60

111 122 141 162 189 238 287

10 14 20 28 42 70 110

6.61 4.07 2.58 1.63 1.02 0.630 0.398

10 13 18 25 30 40 55

Notes: 1. Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

29


Cables Type TFFN Thermoplastic Insulation, Flexible Fixture Wire, Nylon Jacket

Description Soft copper conductor, PVC insulated and with a Nylon covering Construction Conductor

Flexible soft copper conductor, Class K stranded Insulation Polyvinyl Chloride (PVC 90째 C), flame retardant Jacket Abrasion resistant Nylon Characteristics Operating Temperature 90째C. Operating Voltage 600 V. Applications TFFN cables and wires are used generally in internal equipment and board wiring. Installation: in ducts tubing and boards. Special for locations with abrasive environment, oil, grease, gasoline and other chemical agents contaminated ambient. Its reduced diameter permits an optimum utilization of ducts or sites where is installed. Standards CENTELSA TFFN wires and cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire

30


Colors Black, white, red, yellow, blue. Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

31


Cable Type TFFN 600V (International System Units) Thermoplastic Insulation, Fixture Wire, Nylon Jacket (90° C) Standard: UL 62, NTC-2356. Flexible Cord and Fixture Wire. SIZE AWG

STRANDS

18 16

16 26

STRAND SECTION CONDUCTOR DIAMETER (mm2) DIAMETER (mm) (mm)

0.254 0.254

0.81 1.32

1.23 1.51

INSULATION THICKNESS (mm)

0.38 0.38

DIAMETER JACKET OVER THICKNESS INSULATION (mm) (mm)

2.06 2.36

0.10 0.10

DIAMETER OVER JACKET (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

AMPACITY 2 (A)

2.29 2.59

11 17

21.4 13.4

6 8

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cable Type TFFN 600V, 90°C Thermoplastic Insulation, Fixture Wire, Nylon Jacket Standard: UL 62, NTC-2356. Flexible Cord and Fixture Wire. SIZE AWG

STRANDS

18 16

16 26

STRAND SECTION CONDUCTOR INSULATION DIAMETER (kcmil) DIAMETER THICKNESS (mils) (mils) (mils)

10.0 10.0

1.60 2.60

48 59

15 15

DIAMETER JACKET DIAMETER OVER THICKNESS OVER INSULATION (mils) JACKET (mils) (mm)

81 93

4 4

90 102

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20°C 1 (ohm/kft)

AMPACITY 2 (A)

8 11

6.51 4.10

6 8

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

32


Lighting Cables

Description Soft copper flexible conductor PVC insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 105째 C)

Characteristics Operating Temperature 105째 C. Operating Voltage 600 V.

Applications Lighting connections and high temperature applications.

Specifications CENTELSA LIGHTING Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 83, NTC-1332 Thermoplastic insulated Wires and Cables UL 62, NTC-2356 Flexible Cord and Fixture Wire (Sizes 20 to 16 AWG)

CENTELSA Specifications for LIGHTING Cables Colors Black, white, red, yellow, blue.

33


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

34


Lighting Cables 105째C (International System Units) Standard:

SIZE AWG

UL 62, NTC 2356. Flexible and Fixture Wire UL 83, NTC-1332 Thermoplastic insulated Wires and Cables CENTELSA Specifications for LIGHTING Cables

STRANDS

20 18 16 14 12 10 8 6

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

10 16 26 41 65 104 168 266

0.51 0.81 1.32 2.08 3.29 5.27 8.51 13.48

0.97 1.23 1.51 1.98 2.52 3.21 3.66 4.12

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.52

2.23 2.49 2.77 3.24 3.78 4.47 5.52 6.58

9 13 18 26 39 59 96 152

34.7 21.7 13.3 8.46 5.34 3.34 2.07 1.30

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Lighting Cables 105째C Standard:

SIZE AWG

20 18 16 14 12 10 8 6

UL 62, NTC 2356. Flexible and Fixture Wire UL 83, NTC-1332 Thermoplastic insulated Wires and Cables CENTELSA Specifications for LIGHTING Cables

STRANDS

10 16 26 41 65 104 168 266

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.00 1.60 2.60 4.10 6.50 10.40 16.80 26.60

38 48 59 78 99 126 144 162

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20째C 1 (ohm/kft)

30 30 30 30 30 30 45 60

88 98 109 128 149 176 217 259

6 8 12 18 26 40 65 102

10.6 6.6 4.1 2.58 1.63 1.02 0.63 0.40

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

35


Cables Type XGW Cross (X) Linked Polyethylene Insulated 125째C, General Purpose Wire

Description Soft copper flexible conductor XLPE insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame retardant Black Cross Linked Polyethylene (XLPE 125째C)

Characteristics Operating Temperature 125째 C.

Applications Used generally in internal equipment and board wiring. Installation in ducts or raceways. High temperature applications. Also used in automotive low voltage wiring. Insulation resistant to abrasion, gasoline, oil, solvents and chemical agents.

Specifications CENTELSA XGW Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords

CENTELSA Specifications for XGW Cables

36


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

37


Cables Type XGW 600V, 125°C (International System Units) Cross (X) Linked Polyethylene Insulated 125°C, General Purpose Wire Standard: CENTELSA Specifications for XGW Cables

SIZE AWG

20 18 16 14 12 10 8

STRANDS

10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.97 1.23 1.51 1.98 2.52 3.21 3.66

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

0.74 0.76 0.81 0.89 0.94 1.04 1.09

2.19 2.49 2.85 3.44 4.06 4.91 5.42

9 13 18 28 41 64 95

34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type XGW 600V, 125°C Cross (X) Linked Polyethylene Insulated 125°C, General Purpose Wire Standard: CENTELSA Specifications for XGW Cables SIZE AWG

20 18 16 14 12 10 8

STRANDS

10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.00 1.60 2.60 4.10 6.50 10.40 16.80

38 48 59 78 99 126 144

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20°C 1 (ohm/kft)

29 30 32 35 37 41 43

84 95 110 133 157 191 211

6 8 12 19 28 43 64

10.6 6.61 4.07 2.58 1.63 1.02 0.630

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

38


Cables Type HTS-C Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150째C, C: Common use

Description Soft tinned copper flexible conductor Thermoset Elastomer insulated.

Construction Conductor Flexible tinned soft copper conductor, Class K stranded Insulation Black Thermoset Elastomer Flame retardant (XLPE 150째C)

Characteristics Operating Temperature 150째 C.

Applications Used generally in internal equipment and board wiring. Installation in ducts or raceways, transit zones, high temperature applications. Also used in automotive low voltage wiring. Flexible insulation, low smoke emissions, non halogenated, lead free and excellent thermal stability.

Specifications CENTELSA HTS-C Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords

CENTELSA Specifications for HTS-C Cables

39


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

40


Cables Type HTS-C 600V, 150°C (International System Unit) Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150°C, C: Common use Standard: CENTELSA Specifications for HTS-C Cables

SIZE AWG

18 16 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0

STRANDS

16 26 41 65 104 168 266 420 665 836 1064 1323 1666 2107

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.81 1.32 2.08 3.29 5.27 8.51 13.48 21.28 33.70 42.36 53.91 67.04 84.42 106.76

1.23 1.51 1.98 2.52 3.21 3.66 4.12 6.72 8.58 9.77 11.10 12.47 14.10 15.97

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20°C 1 (ohm/km)

0.73 0.79 0.82 0.90 0.90 1.10 1.19 1.27 1.29 1.29 1.29 1.29 1.54 1.54

2.77 3.17 3.70 4.42 5.11 5.94 6.60 9.36 11.26 12.45 13.78 15.15 17.30 19.17

14 20 29 44 65 101 151 239 365 451 564 691 878 1094

22.6 13.9 8.8 5.6 3.5 2.1 1.4 0.9 0.5 0.4 0.3 0.3 0.2 0.2

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type HTS-C 600V, 150°C Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150°C, C: Common use Standard: CENTELSA Specifications for HTS-C Cables

SIZE AWG

18 16 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0

STRANDS

16 26 41 65 104 168 266 420 665 836 1064 1323 1666 2107

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.60 2.60 4.10 6.50 10.40 16.80 26.60 42.00 66.50 83.60 106.40 132.30 166.60 210.70

48 59 78 99 126 144 162 265 338 385 437 491 555 629

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

29 31 32 36 36 43 47 50 51 51 51 51 61 61

109 125 146 174 201 234 260 369 443 490 543 596 681 755

APPROX. TOTAL WEIGHT (lb/kft)

9 14 20 30 44 68 102 161 245 303 379 464 590 735

DC RESISTANCE AT 20°C 1 (ohm/kft)

6.9 4.23 2.68 1.69 1.06 0.65 0.41 0.26 0.16 0.13 0.10 0.08 0.06 0.05

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

41


Automotive Cables Type GPT General Purpose Thermoplastic Insulated

Description Soft copper flexible conductor PVC insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 75째 C)

Characteristics Operating Temperature 75째 C. Operating Voltage 50 V.

Applications Low voltage automotive wiring. Insulation resistant to abrasion gasoline and oil.

Specifications CENTELSA GPT Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords SAE J1128 NTC-1116 Primary Low Voltage Cables Colors Black, white, red, yellow, blue, brown, orange grey and violet.

42


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

43


Automotive Cables Type GPT 50V, 75째C (International System Units) General Purpose Thermoplastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

SIZE AWG

22 20 18 16 14 12 10 8

STRANDS

7 10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.35 0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.76 0.97 1.23 1.51 1.98 2.52 3.21 3.66

INSULATION THICKNESS (mm)

0.58 0.58 0.58 0.58 0.58 0.66 0.79 0.94

DIAMETER OVER INSULATION (mm)

1.76 1.97 2.23 2.51 2.98 3.62 4.51 5.20

APPROX. TOTAL WEIGHT (kg/km)

6 8 11 16 24 38 59 93

DC RESISTANCE AT 20째C 1 (ohm/km)

49.6 34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type GPT 50V, 75째C General Purpose Thermoplastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables SIZE AWG

STRANDS

22 20 18 16 14 12 10 8

7 10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

0.70 1.00 1.60 2.60 4.10 6.50 10.40 16.80

30 38 48 59 78 99 126 144

INSULATION THICKNESS (mils)

23 23 23 23 23 26 31 37

DIAMETER OVER INSULATION (mils)

69 78 88 99 117 143 178 205

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

44

APPROX. TOTAL WEIGHT (lb/kft)

4 5 8 11 16 25 40 62

DC RESISTANCE AT 20째C 1 (ohm/kft)

15.1 10.6 6.61 4.07 2.58 1.63 1.02 0.630


Automotive Cables Type TWP Thin Wall, Thermo Plastic Insulated

Description Soft copper flexible conductor PVC insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 75째 C)

Characteristics Operating Temperature 75째 C. Operating Voltage 50 V.

Applications Low voltage automotive wiring where the reduced diameter offers an optimum utilization of site in which is installed. Insulation resistant to abrasion gasoline and oil.

Specifications CENTELSA TWP Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords SAE J1128 NTC-1116 Primary Low Voltage Cables Colors Black, white, red, yellow, blue, brown, orange grey and violet.

45


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

46


Automotive Cable Type TWP 50V, 75째C (Internacional System Units) Thin Wall, ThermoPlastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

SIZE AWG

22 20 18 16 14 12 10 8

STRANDS

7 10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.35 0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.76 0.97 1.23 1.51 1.98 2.52 3.21 3.66

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

0.40 0.40 0.40 0.40 0.40 0.45 0.50 0.55

1.44 1.65 1.91 2.19 2.66 3.32 4.07 4.58

5 7 10 15 22 35 55 86

49.6 34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cable Type TWP 50V, 75째C Thin Wall, ThermoPlastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables SIZE AWG

STRANDS

22 20 18 16 14 12 10 8

7 10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

0.70 1.00 1.60 2.60 4.10 6.50 10.40 16.80

30 38 48 59 78 99 126 144

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20째C 1 (ohm/kft)

16 16 16 16 16 18 20 22

55 63 73 84 103 127 157 178

3 4 7 10 15 24 37 58

15.1 10.6 6.61 4.07 2.58 1.63 1.02 0.630

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

47


Automotive Cables Type SGT. Battery Cable Starter or Ground, General Purpose Thermoplastic Insulated

Description Soft copper flexible conductor PVC insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 75째 C)

Characteristics Operating Temperature 75째 C. Operating Voltage 50 V.

Applications SGT cables are used to connect the system of engine Start-up. Insulation is resistant to abrasion, gasoline, oil, solvents and chemical agents.

Specifications CENTELSA SGT Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords

SAE J1127 NTC-1955 Battery Cables

48


Packaging Wood reels or spools upon request. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

Automotive Cables Type SGT 50V, 75째C (International System Unit) Starter or Ground, General Purpose Thermoplastic Insulated Standard: SAE J1127 NTC-1955. Battery Cables

SIZE AWG

6 4 2 1 1/0 2/0 3/0 4/0

STRANDS

266 420 665 836 1064 1323 1666 2107

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

13.48 21.28 33.70 42.36 53.91 67.04 84.42 106.76

4.12 6.72 8.58 9.77 11.10 12.47 14.10 15.97

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

1.52 1.65 1.65 1.65 1.65 1.65 1.98 1.98

6.58 9.40 11.26 12.45 13.78 15.15 17.30 19.17

152 243 368 454 568 697 886 1105

1.30 0.826 0.522 0.415 0.326 0.262 0.208 0.165

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type SGT 50V, 75째C Starter or Ground, General Purpose Thermoplastic Insulated Standard: SAE J1127 NTC-1955. Battery Cables SIZE AWG

STRANDS

6 4 2 1 1/0 2/0 3/0 4/0

266 420 665 836 1064 1323 1666 2107

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

26.60 42.00 66.50 83.60 106.40 132.30 166.60 210.70

162 265 338 385 437 491 555 629

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20째C 1 (ohm/kft)

60 65 65 65 65 65 78 78

259 370 443 490 543 596 681 755

102 163 247 305 382 469 595 742

0.398 0.252 0.159 0.127 0.0994 0.0800 0.0635 0.0502

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

49


Automotive Cables Type SXL Special Purpose, Cross (X) Linked Polyethylene Insulated

Description Soft copper flexible conductor XLPE insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame retardant Cross Linked Polyethylene (XLPE 125째C)

Characteristics Operating Temperature 125째 C. Operating Voltage 50 V.

Applications Low voltage automotive, special for vane motor. Applications where heavy duty requires more than GPT cables. Insulation resistant to abrasion gasoline and oil.

Specifications CENTELSA SXL Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords SAE J1128 NTC-1116 Primary Low Voltage Cables Colors Black, red, orange 50


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

51


Automotive Cables Type SXL 50V, 75째C (International System Unit) Special Purpose, Cross (X) Linked Polyethylene Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

SIZE AWG

20 18 16 14 12 10 8

STRANDS

10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.97 1.23 1.51 1.98 2.52 3.21 3.66

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

0.74 0.76 0.81 0.89 0.94 1.04 1.09

2.19 2.49 2.85 3.44 4.06 4.91 5.42

9 13 18 28 41 64 95

34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type SXL 50V, 75째C Special Purpose, Cross (X) Linked Polyethylene Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables SIZE AWG

STRANDS

20 18 16 14 12 10 8

10 16 26 41 65 104 168

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.00 1.60 2.60 4.10 6.50 10.40 16.80

38 48 59 78 99 126 144

INSULATION THICKNESS (mils)

29 30 32 35 37 41 43

DIAMETER OVER INSULATION (mils)

84 95 110 133 157 191 211

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

52

APPROX. TOTAL WEIGHT (lb/kft)

6 8 12 19 28 43 64

DC RESISTANCE AT 20째C 1 (ohm/kft)

10.6 6.61 4.07 2.58 1.63 1.02 0.630


Silicon Cables Type SF Silicon Insulated Flexible

Description Soft copper flexible conductor Silicon Rubber insulated.

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Silicon Rubber natural color (Beige)

Characteristics Operation Temperature 200째 C. Operating Voltage 600 V.

Applications High temperature applications like motors wiring, internal wiring of luminaries, ballast, dryers, ovens, freezers, coolers Excellent insulation performance at high temperatures

Specifications CENTELSA SF Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire

53


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

Silicon Cable Type SF 600V, 200째C (International System Unit) Silicon Insulated Flexible

Standard: UL 62, NTC-2356. Flexible and Fixture Wire

SIZE AWG

18 16 14 12 10

STRANDS

16 26 41 65 104

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254

0.81 1.32 2.08 3.29 5.27

1.23 1.51 1.98 2.52 3.21

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

0.76 0.76 0.76 0.76 0.76

2.83 3.11 3.58 4.12 4.81

13 19 27 40 60

21.7 13.3 8.46 5.34 3.34

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Silicon Cable Type SF 600V, 200째C Silicon Insulated Flexible

Standard: UL 62, NTC-2356. Flexible and Fixture Wire

SIZE AWG

STRANDS

18 16 14 12 10

16 26 41 65 104

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0

1.60 2.60 4.10 6.50 10.40

48 59 78 99 126

INSULATION THICKNESS (mils)

30 30 30 30 30

DIAMETER OVER INSULATION (mils)

111 122 141 162 189

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

54

APPROX. TOTAL WEIGHT (lb/kft)

9 13 18 27 40

DC RESISTANCE AT 20째C 1 (ohm/kft)

6.61 4.07 2.58 1.63 1.02


Welding Cable

Description Soft copper flexible conductor with Elastomer Thermoplastic insulation

Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Black Elastomer Thermoplastic i(TPR 105째C)

Characteristics Operation Temperature 105째 C. Operating Voltage 600 V.

Applications Extra hard service Cable, flexible and resistant to heavy-duty, for electric welding equipments. Insulation: Rough handling, abrasion and spark welding resistant.

Specifications CENTELSA SF Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire

55


Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are available upon request.

56


Welding Cable 600V, 105oC (International System Units) BS 638. Arc welding power coerces equipment and accessories. CENTELSA Specifications for HTS-C Cables

Standard:

SIZE AWG

STRANDS

6 4 2 1 1/0 2/0 3/0 4/0 250 300 350

266 420 665 836 1064 1323 1666 2107 2499 2989 3458

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

13.48 21.28 33.70 42.36 53.91 67.04 84.42 106.76 126.63 151.45 175.22

4.12 6.72 8.58 9.77 11.10 12.47 14.10 15.97 17.40 19.02 20.61

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20째C 1 (ohm/km)

AMPACITY 2 (A)

2.00 2.00 2.00 2.20 2.40 2.40 2.60 2.80 2.80 3.00 3.20

8.28 10.88 12.74 14.31 16.04 17.41 19.46 21.73 23.16 25.20 27.21

168 258 389 487 616 756 947 1189 1390 1658 1933

1.30 0.826 0.522 0.415 0.326 0.262 0.208 0.165 0.139 0.116 0.100

125 170 232 270 318 369 431 505 566 639 705

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacity based on 5 minutes working cycles and 80% Load Factor. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

WELDING Cable 600V, 105oC BS 638. Arc welding power coerces equipment and accessories. CENTELSA Specifications for HTS-C Cables

Standard:

SIZE AWG

STRANDS

6 4 2 1 1/0 2/0 3/0 4/0 250 300 350

266 420 665 836 1064 1323 1666 2107 2499 2989 3458

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

26.60 42.00 66.50 83.60 106.40 132.30 166.60 210.70 249.90 298.90 345.81

162 265 338 385 437 491 555 629 685 749 811

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20째C 1 (ohm/kft)

AMPACITY 2 (A)

79 79 79 87 94 94 102 110 110 118 126

326 428 502 563 631 685 766 856 912 992 1071

113 174 261 327 414 508 636 799 934 1114 1299

0.398 0.252 0.159 0.127 0.0994 0.0800 0.0635 0.0502 0.0423 0.0354 0.0306

125 170 232 270 318 369 431 505 566 639 705

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacity based on 5 minutes working cycles and 80% Load Factor. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

57