Table of Contents
Disconnect Switches
Enclosed switches Stainless steel enclosure 150 × 150 × 120 mm 20 A / 25 A / 32 A Main/Emergency-Off Switch Main Switch 3 ... 4 pole
IP66 Brushed stainless steel enclosure Cover interlock in ON position Order code structure:
Type - Switching programme - Mounting form
Ordering example: 3 pole Main/Emergency-Off Switch, 25 A, N-padlock device:
Type
Rated data (IEC 60947) Operational current Ie Operational power (at 380 – 440 V)
AC-21A (A)
AC-23A (kW)
AC-3 (kW)
H216 H220 H226
20 25 32
5.5 7.5 11
3.7 5.5 7.5
H220 - 41300 - 097N4
Detailed technical data page 108.
Switching progr.
Poles
Auxiliary contacts n/o
41300 41311 41320 41400 41411 41420
3 3 3 4 4 4
n/c
0 1 2 0 1 2
0 1 0 0 1 0 Switching diagrams and further switching programmes (3 ... 4 pole) page 95.
Mounting form
Main/Emergency-Off Switch
Mounting form
097N4
N-padlock device yellow/red
097N1
N-padlock device black
097M4
M-padlock device yellow/red
097M1
M-padlock device black
097V4
padlockable with V-handle yellow/red
097V1
padlockable with V-handle silver/black
Operator
Operator
Main Switch
Dimensions in mm:
Mounting form
H1
B1
T1
T2
H2
B2
097N4 / 097N1 097M4 / 097M1 097V4 / 097V1
150 150 150
150 150 150
120 120 120
33 38 39
132 132 132
85 85 85
Blank side walls Mounting brackets see page 105.
Switch Catalogue
89