Eland Cables’ Datasheet Electrical Cable | Product Group Control Flexible
CY LSZH Control Flexible Cable Eland Product Group A5B Application For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment. Used as interconnecting cable for measuring, controlling or regulation in control equipment for assembly and production lines, conveyors and for computer units. Suitable for fixed installations or for flexible use when temporarily moved, and in conditions of medium mechanical stress. Can be used outdoors when protected, and in dry or moist conditions indoors. These cables with copper screening are ideally suitable for interference free data and signal transmission in measuring and control technology. Standards Generally to BS6500, VDE0250 Conductor Class 5 flexible plain stranded copper conductors to BS EN 60228:2005 (previously BS6360), VDE0295, IEC 60228 Insulation XLPE (Cross-Linked Polyethylene) Braiding TCWB (Tinned Copper Wire Braid) Sheath LSZH (Low Smoke Zero Halogen) Sheath Colour Grey Voltage Rating 300/500V Temperature Rating Fixed: -35°C to +85°C Flexing: -5°C to +85°C Minimum Bending Radius 10 x overall diameter Core Identification Black with White numbers (3 cores and above includes Green/Yellow) Coloured cores available
www.eland.co.uk
Dimensions Eland Part Number
No. of Cores x Cross Sectional Area # x mm²
Nominal Overall Diameter mm
Nominal Weight kg/Km
FCGCXT Gland
CY Control Flexible Cable - 2 Cores A5B020075CYLSZH
2 x 0.75
6.0
54
20SS
A5B02010CYLSZH
2 x 1.00
6.2
60
20SS
A5B02015CYLSZH
2 x 1.50
6.8
70
20SS
A5B02025CYLSZH
2 x 2.50
8.0
104
20S
CY LSZH Control Flexible Cable - 3 Cores A5B030075CYLSZH
3 x 0.75
6.3
65
20SS
A5B03010CYLSZH
3 x 1.00
6.5
73
20SS
A5B03015CYLSZH
3 x 1.50
7.2
90
20S
A5B03025CYLSZH
3 x 2.50
8.6
140
20S
A5B03040CYLSZH
3 x 4.00
9.5
175
20S
CY LSZH Control Flexible Cable - 4 Cores A5B040075CYLSZH
4 x 0.75
6.8
77
20SS
A5B04010CYLSZH
4 x 1.00
7.0
89
20S
A5B04015CYLSZH
4 x 1.50
7.8
108
20S
A5B04025CYLSZH
4 x 2.50
9.4
173
20S
A5B04040CYLSZH
4 x 4.00
11.1
236
20S
A5B04060CYLSZH
4 x 6.00
12.8
339
20
A5B0410CYLSZH
4 x 10.00
16.1
502
25
A5B0416CYLSZH
4 x 16.00
19.2
771
25
A5B0425CYLSZH
4 x 25.00
20.2
1420
32
A5B0435CYLSZH
4 x 35.00
24.4
1750
32
CY LSZH Control Flexible Cable - 5 Cores A5B050075CYLSZH
5 x 0.75
7.3
91
20S
A5B05010CYLSZH
5 x 1.00
7.6
105
20S
A5B05015CYLSZH
5 x 1.50
8.4
125
20S
A5B05025CYLSZH
5 x 2.50
10.0
206
20S
A5B05040CYLSZH
5 x 4.00
12.1
288
20
CY LSZH Control Flexible Cable - 7 Cores A5B070075CYLSZH
7 x 0.75
7.8
115
20S
A5B07010CYLSZH
7 x 1.00
8.4
139
20S
A5B07015CYLSZH
7 x 1.50
9.3
160
20S
A5B07025CYLSZH
7 x 2.50
10.8
267
20S
CY LSZH Control Flexible Cable - 12 Cores A5B120075CYLSZH
12 x 0.75
10.1
177
20S
A5B12010CYLSZH
12 x 1.00
10.4
207
20S
A5B12015CYLSZH
12 x 1.50
11.8
279
20
CY LSZH Control Flexible Cable - 18 Cores A5B180075CYLSZH
18 x 0.75
11.6
250
20
A5B18010CYLSZH
18 x 1.00
12.4
295
20
A5B18015CYLSZH
18 x 1.50
14.0
350
25
Issue_01_0508
Eland Cables’ Datasheet
CY LSZH Control Flexible Cable [Continued] Conductors Class 5 flexible Copper Conductors for Single Core and Multi-Core cables 1
2
3
Nominal Cross Sectional Area mm2
Maximum Diameter of Wires in Conductor mm
Maximum Resistance of Conductor at 20ºC Plain Wires ohms/Km
0.75
0.21
26.0000
1.00
0.21
19.5000
1.50
0.26
13.3000
2.50
0.26
7.9800
4.00
0.31
4.9500
6.00
0.31
3.3000
10.00
0.41
1.9100
16.00
0.41
1.2100
25.00
0.41
0.7800
35.00
0.41
0.5540
Table in accordance with BS EN 60228:2005 (previously BS6360)
Electrical Characteristics Current Carrying Capacity (amperes) at 30ºC Nominal Cross Sectional Area mm²
Current Rating Amps
0.75
12
1.00
15
1.50
18
2.50
26
4.00
34
6.00
44
10.00
61
16.00
82
25.00
108
35.00
135
Conversion Factors Multi-Conductor cables with cross sectional area up to 10mm2 No. of Cores
Conversion Factor
5
0.75
7
0.65
10
0.55
14
0.50
19
0.45
24
0.40
40
0.35
61
0.30