Maniero Elettronica Control Panels catalogue 2009

Page 10

CONTROL PANELS AND STARTERS FOR 1 230V SINGLE-PHASE ELECTRIC PUMP WITH THERMAL PROTECTION

QMD10/...kW-T Direct start control panel for 1 single-phase electric pump with thermal protection

Single-phase panels for control of electric pumps are proposed with thermal or ammetric protection. Ammetric protection allows with a single model to cover a wider range with power from 0,37 kW to 2,2 kW. N.B: For more than one pump please contact our technical/ sales service

P

COM

A

RUN

START

CONNECTION DIAGRAM

B

GENERAL CHARACTERISTICS:

– Control panel with electronic components; – Power supply ~ 50/60Hz 230V ±10%; – Very low voltage input for external control from pressure or float switch; – Very low voltage input for pressure switch or minimum level float against dry run or too full; – Selector for pressure or minimum level float (contacts N.C.) or (contacts N.O.); – Mains pilot light; – Operating motor light; – Min-max water level alarm light; Selector for automatic-off-manual operation (the last control is not latched);

– General disconnecting switch with door lock; – External push-button for thermal protection reset; – Motor protection fuse; – Thermoplastic box – Protected to IP 50.

ELECTRONIC SPARE PARTS: – Mother board SMM1T, code 223.31; – Synoptic panel for IP55, code 316.06.

OPERATING CONDITIONS: – Ambient temperature –5 to +40°C; – Relative moisture 50% with a max temperature of 40°C.

PROTECTED TO IP55 (OPTIONAL): – Switch cover, code 644.344; – Thermal relay cover, code 879.276.

TECHNICAL DATA AND OPERATING POWERS DIMENSIONS mm A

CODE

APPROX POWER AT 230V kW

QMD10/0,37kW-4T

232.21

0,37

0,5

4A

1,5

225

255

130

QMD10/0,55kW-6T

232.22

0,55

0,75

6A

1,5

225

255

130

QMD10/0,75kW-7T

232.23

0,75

1

7A

1,5

225

255

130

QMD10/1,1kW-10T

232.24

1,1

1,5

10A

1,5

225

255

130

QMD10/1,5kW-13T

232.25

1,5

2

13A

1,5

225

255

130

QMD10/2,2kW-18T

232.26

2,2

3

18A

1,5

225

255

130

* AMD10/0,37kW-4T

232.01

0,37

0,5

4A

0,8

180

200

100

* AMD10/0,55kW-6T

232.02

0,55

0,75

6A

0,8

180

200

100

* AMD10/0,75kW-7T

232.03

0,75

1

7A

0,8

180

200

100

* AMD10/1,1kW-10T

232.04

1,1

1,5

10A

0,8

180

200

100

* AMD10/1,5kW-13T

232.05

1,5

2

13A

0,8

180

200

100

* AMD10/2,2kW-18T

232.06

2,2

3

18A

0,8

180

200

100

MODEL

APPROX POWER AT 230V Hp

THERMAL PROTECTION

WEIGHT kg

DIMENSIONS mm B

DIMENSIONS mm P

* GENERAL CHARACTERISTICS: characteristics preset and operating conditions are the same as QMD10/...kW-T, but without “general disconnecting switch with door lock”.

NOTES: the value of the power rating is indicative, for a correct choice of the model, pls-check that motor ampere absorption is within thermal protection value.

6

www.manieroelettronica.it


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.