Nemko 04ATEX1073X
[15]
[13]
Supplement 5
[14]
EC-TYPE EXAMINATION CERTIFICATE No
Date: 2006-06-28
Page 1 of 1
Nemko 04ATEX1073X
Description of Equipment or Protective System The certificate is extended to cover changes and specification of alternative safety components. The changes do not alter the safety characteristics of the product.
[16]
Report No 68314 and the listed Descriptive Documents
Descriptive Documents Number 9150079-912 9150079-922 9150079-932 [17]
Description/Title MB, ATEX (and IECEx) IBH, ATEX (and IECEx) IBF, ATEX (and IECEx)
Issue 3 3 2
Date 0616 0616 0616
Special Conditions for Safe Use As specified in the Schedule and Supplements 1 and 2.
[18]
Essential Health and Safety Requirements Covered by item 9
Oslo, 2006-06-28
Rolf Hoel Certification Department
This certificate may only be reproduced in its entirety and without any change, schedule included. Postal address: P.O.Box 73 Blindern N-0314 OSLO, NORWAY
Office address: GaustadallĂŠen 30 0373 OSLO +47 22 96 05 50
Telephone: +47 22 96 03 30 Fax:
Enterprise number: NO 974404532
Sheets 10 7 5
Nemko 04ATEX1073X
[15]
[13]
Supplement 6
[14]
EC-TYPE EXAMINATION CERTIFICATE No
Date: 2007-05-07
Page 1 of 3
Nemko 04ATEX1073X
Description of Equipment or Protective System The certificate is extended to include the following: A variation Radar Level Transmitter 5300 series. Changes of the electronic boards common for both 5400 series and 5300 series. The changes of the electronics do not alter the safety characteristics of the product. Compliance with the technical requirements of the standards EN 60079-0: 2004, EN 60079-1: 2003 for the 5400 and 5300 series. Change of manufacturers name and labelling: Rosemount Tank Radar AB
Type Designations and Classifications and Safety Data for Radar Level Transmitter 5300 series 530abcdefghijklm. Guided Wave Radar a b c d e f g h i j k l
= = = = = = = = = = = =
Model: Liquid level, Liquid level and interface, or Solid level transmitter Signal output: Hart or Fieldbus Housing material: Polyurethane covered aluminium or Stainless steel Conduit/cable Threads: ½-14 NPT, M20 x 1.5 Type of tank sealing (temperature, pressure) Process connection and probe material Sealing O-ring material Probe type Probe length unit Probe length Process connection size Hazardous locations specification: E1, KA, KB, KC, I1, IA, KE, KF, KG, KI, KJ, KK according to this certificate m = Additional options coding for: Integral digital display, bar code tag, SST tag plate, hydrostatic testing, factory configuration, alarm limits, calibration data, material traceability certification, NACE material, long stud, mounting bracket, transient protection, low temperature start up, centering disc, remote mounting, vapour compensation, weather protection, safety certification, overfill protection, special option
Models for Intrinsically Safe Power Supplies Type 5300 Hart® 4-20mA: Models 530xHxxxxxxxxxI1 or 530xHxxxxxxxxxKE II 1 G , II 1 D T73 C EEx ia IIC T4 Ta:-40 C to 70 C
or 530xHxxxxxxxxxKF
or 530xHxxxxxxxxxKG
This certificate may only be reproduced in its entirety and without any change, schedule included. Postal address: P.O.Box 73 Blindern N-0314 OSLO, NORWAY
Office address: Gaustadalléen 30 0373 OSLO +47 22 96 05 50
Telephone: +47 22 96 03 30 Fax:
Enterprise number: NO 974404532
Nemko 04ATEX1073X Safety Parameters. Maximum input voltage. Maximum inutput current. Maximum inutput power. Maximum internal capacitance Maximum internal inductance
Ui: Ii: Pi: Ci: Li:
Date: 2007-05-07
Page 2 of 3
30V 130mA 1,0W 7,25nF Negligible
Type 5300 Foundation Fieldbus: Models 530xFxxxxxxxxxI1 or 530xFxxxxxxxxxKE
or 530xFxxxxxxxxxKF
or 530xFxxxxxxxxxKG
or 530xFxxxxxxxxxKJ
or 530xFxxxxxxxxxKK
II 1 G , II 1 D T63 C EEx ia IIC T4 Ta:-40 C to 60 C Safety Parameters. Maximum input voltage. Maximum input current. Maximum input power. Maximum internal capacitance Maximum internal inductance
Ui: Ii: Pi: Ci: Li:
30V 300mA 1,5W 0 nF Negligible
Type 5300 Foundation Fieldbus FISCO: Models 530xFxxxxxxxxxIA or 530xFxxxxxxxxxKI II 1 G , II 1 D T63 C EEx ia IIC T4 Ta:-40 C to 60 C Safety Parameters. Maximum input voltage. Ui: Maximum input current. Ii: Maximum input power. Pi: Maximum internal capacitance Maximum internal inductance
17,5V 380mA 5,32W Ci: 0 nF Li: <1 H
Models for Non-Intrinsically Safe Power Supplies Maximum safe voltage: Um 250VAC Type 5300 Hart® 4-20mA: Models 530xHxxxxxxxxxE1
or 530xHxxxxxxxxxKA
or 530xHxxxxxxxxxKB
or 530xHxxxxxxxxxKC
II 1/2 G , II 1 D T73 C EEx iad IIC T4 Ta:-40 C 70 C Nominal supply voltage is up to 42,4V Type 5300 Foundation Fieldbus: Models 530xFxxxxxxxxxE1 or 530xFxxxxxxxxxKA
or 530xFxxxxxxxxxKB
or 530xFxxxxxxxxxKC
II 1/2 G , II 1 D T63 C EEx iad IIC T4 Ta:-40 C 60 C Nominal supply voltage is up to 32V DC
This certificate may only be reproduced in its entirety and without any change, schedule included. Postal address: P.O.Box 73 Blindern N-0314 OSLO, NORWAY
Office address: Gaustadalléen 30 0373 OSLO +47 22 96 05 50
Telephone: +47 22 96 03 30 Fax:
Enterprise number: NO 974404532
Nemko 04ATEX1073X [16]
Date: 2007-05-07
Page 3 of 3
Report No 78420 and the listed Descriptive Documents
Descriptive Documents Description
Drawing No.
Issue
Date
Installation Drawing 5400 Cert. Dwg. Block Diagram 5400 Cert. Dwg. Bbh Fieldbus Output Board Schematic Fieldbus Output Board Pwb Fieldbus Output Board Assembly 160 Segment Lcd Board Pwb 160 Segment Lcd Board Assembly Cert. Dwg. (Assembly) 5300 Cert. Dwg. Labels Atex 5300 Installation Drawing 5300 Cert. Dwg. Block Diagram 5300 Cert. Dwg. Mb 5300 Cert. Dwg. Pmmdc 5300 Cert. Dwg. Is Lumped Capacitance 5300 Cert. Dwg. Probes 5300 Cert. Dwg. Remote Mounting 5300
9150079-907 9150079-902 9240030-909 00848-4200 00848-4201 00848-4202 03031-0590 03031-0591 9240030-932 9240030-923 9240030-938 9240030-935 9240030-941 9240030-926 9150079-993 9240030-944 9240099-903
4 4 2 AF AG AY AC AH 1 1 1 1 1 1 1 1 1
0644 0644 0644 12/28/06 12/29/06 12/29/06 12/11/03 3/19/04 0646 0646 0644 0644 0644 0644 0644 0646 0643
[17]
Special Conditions for Safe Use 1.
The intrinsically safe circuits do not withstand the 500V AC test as specified in EN 50020 clause 6.4.12.
2.
Probes covered with plastic and/or with plastic discs will have a non-conducting area that exceeds the maximum permissible areas for Group IIC and Category II 1G according to EN 50284 clause 4.4.3 (4 cm2). Therefore, when the antenna is used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
3.
[18]
Impact and friction hazards need then to be considered according to EN 50284 clause 4.3.1 when the transmitter and part of antennas exposed to the exterior atmosphere of the tank is made with light metal alloys and used in category II 1 G Essential Health and Safety Requirements Covered by item 9
Oslo, 2007-05-07
Rolf Hoel Certification Manager, Ex-products
This certificate may only be reproduced in its entirety and without any change, schedule included. Postal address: P.O.Box 73 Blindern N-0314 OSLO, NORWAY
Office address: GaustadallĂŠen 30 0373 OSLO +47 22 96 05 50
Telephone: +47 22 96 03 30 Fax:
Enterprise number: NO 974404532