Industrial Catalog

Page 197

SPEC F125

January, 2008

Short Circuit Currents

Allowable Short Circuit Currents For Thermoset Insulated Aluminum Conductors Rated For 105°C Maximum Continuous Operation 1000000

Short Circuit Current—Amperes

100000

10000

Curves Based on the Formula 1000 2

[ ] t = 0.0125 log [ TT ++ 228 228 ] I A

2

10

1

I = Short Circuit Current–Amperes A = Conductor Area–Circular Mils t = Time of Short Circuit–Seconds T1 = Maximum Operating Temperature–105°C T2 = Maximum Short Circuit Temperature–250°C

100

10

8

6

4

2

1

1/0 2/0 3/0 4/0 250

350

500

750 1000

Conductor Size (AWG/kcmil) 1 Cycles 16 Cycles

2 Cycles 30 Cycles

4 Cycles 60 Cycles

8 Cycles 100 Cycles

Reprinted with permission from ICEA P-32-382 Short Circuit characteristics of Insulated Conductors, Copyright 2006, Insulated Cable Engineers Association, Carrollton, GA 30112. This reprint is not the referenced subject, which is represented only by the standard in its entirety. Phone: 888-593-3355 www.generalcable.com