SPEC 1200
January, 2008
CVTC
®
XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs Product Construction Conductor:
• 18 AWG and 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8
Insulation:
CATALOG NUMBER
COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km
INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 343140* 343150* 343160* 343170* 343180* 343190* 343200* 343210* 343220*
2 4 8 12 16 20 24 36 50
18 18 18 18 18 18 18 18 18
7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152
0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015
0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38
0.050 0.050 0.050 0.060 0.060 0.070 0.070 0.070 0.080
1.27 1.27 1.27 1.52 1.52 1.78 1.78 1.78 2.03
0.410 0.475 0.605 0.750 0.830 0.955 1.030 1.210 1.425
10.41 12.07 15.37 19.05 21.08 24.26 26.16 30.73 36.20
30 55 105 156 207 252 302 452 637
45 82 156 232 308 375 449 673 948
73 109 117 174 215 320 308 458 392 583 494 735 583 868 830 1235 1145 1704
INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 343240* 343250* 343260* 343270* 343280* 343290* 343300* 343310* 343320*
2 4 8 12 16 20 24 36 50
16 16 16 16 16 16 16 16 16
7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192
0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015
0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38
0.050 0.050 0.060 0.060 0.070 0.070 0.070 0.080 0.080
1.27 1.27 1.52 1.52 1.78 1.78 1.78 2.03 2.03
0.455 0.530 0.710 0.855 0.955 1.055 1.160 1.380 1.580
11.56 13.46 18.03 21.72 24.26 26.80 29.46 35.05 40.13
42 80 155 230 306 375 456 674 945
Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.
63 96 143 119 160 238 231 293 436 342 425 632 455 563 838 558 664 988 679 780 1161 1003 1137 1692 1406 1518 2259
• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification
Shield:
Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire
Jacket:
• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)
Print:
• General Cable® (WC) CVTC XX/SPS XXAWG FR-XLP/PVC SHIELDED (UL) Type PLTC 90˚C SUN RES plus day/MONTH/YEAR OF MFG sequential footage mark
Options:
• Tinned copper conductor • Class C stranding • Overall shielded pairs • Ethylene Propylene Rubber (EPR) insulation • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Other constructions available upon request
Applications:
• In free air and raceways in accordance with NEC • Typical applications include audio, intercom, control, energy management and alarm circuits • In ducts, cable trays or conduit • In accordance with UL Subject 13 as PowerLimited Circuit Cable • In Class 3 circuits in accordance with NEC • Permitted for use in Class I Division 2 industrial hazardous locations per NEC
Features:
• Rated at 90˚C • Ripcord applied to all cables with jacket thickness of 60 mils or less • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant • Meets cold bend test at -25˚C
Compliances:
Industry Compliances: • UL 13 Type PLTC • UL 1581 Flame Tests Compliances: • UL 1581 VW-1 • IEEE 383 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable
Packaging:
• Material cut to length and shipped on non-returnable wood reels
Phone: 888-593-3355 www.generalcable.com