Propane Equipment Catalog

Page 177

171

LP PIPE & TUBING SIZING TABLES

LP PIPE & TUBING SIZING TABLES

Pipe Sizing Between Second-Stage Regulator and Appliance:* Nominal Pipe Size, Schedule 80 PIPE 1 / 2” LENGTH, FT 0.546 10 20 30 40 50 60 80 100 125 150 200 250 300 350 400

207 142 114 98 87 78 67 59 53 48 41 36 33 30 28

3 / 4” 0.742

1” 0.957

11 / 4 ” 1.278

11 / 2 ” 1.5

2” 1.939

462 318 255 218 193 175 150 133 118 107 91 81 73 68 63

901 619 497 426 377 342 292 259 230 208 178 158 143 132 122

1924 1322 1062 909 805 730 625 553 491 444 380 337 305 281 261

2928 2012 1616 1383 1226 1111 951 842 747 677 579 513 465 428 398

5741 3946 3169 2712 2404 2178 1864 1652 1464 1327 1135 1006 912 839 780

3” 2.9

31 / 2 ” 3.364

4” 3.826

16503 11342 9108 7795 6909 6260 5358 4748 4208 3813 3264 2892 2621 2411 2243

24357 16740 13443 11506 10197 9239 7908 7009 6212 5628 4817 4269 3868 3559 3311

34137 23462 18841 16125 14292 12949 11083 9823 8706 7888 6751 5983 5421 4987 4640

Note: Maximum undiluted propane capacities listed are based on a 11-in. w.c. setting and 0.5in. w.c. pressure drop. Capacities in 1000 Btu/hr.

Pipe Sizing Between First-Stage and Second-Stage Regulators:*

Copper Tube Sizing Between Second-Stage Regulator and Appliance:*

Outside Diameter Copper Tubing, Type K

Outside Diameter Copper Tubing, Type K

TUBING 3 / 8” LENGTH, FT 0.305 30 40 50 60 70 80 90 100 150 200 250 300 350 400 450 500 600 700 800 900 1000 1500 2000

284 243 216 195 180 167 157 148 119 102 90 82 75 70 66 62 56 52 48 45 43 34 29

1 / 2” 0.402

5 / 8” 0.527

3 / 4” 0.652

7 / 8” 0.745

587 502 445 403 371 345 374 306 246 210 186 169 155 144 136 128 116 107 99 93 88 71 60

1193 1021 905 820 754 702 659 622 500 428 379 343 316 294 276 260 236 217 202 189 179 144 123

2085 1785 1582 1433 1319 3227 1151 1087 873 747 662 600 552 514 482 455 412 379 353 331 313 251 215

2959 2532 2244 2033 1871 1740 1633 1542 1239 1060 940 851 783 729 654 646 585 538 501 470 444 356 305

TUBING 3 / 8” LENGTH, FT 0.305 10 20 30 40 50 60 80 100 125 150 200 250 300 350 400

45 31 25 21 19 17 15 13 11 10 9 8 7 7 6

1 / 2” 0.402

5 / 8” 0.527

3 / 4” 0.652

7 / 8” 0.745

93 64 51 44 39 35 30 27 24 21 18 16 15 14 13

188 129 104 89 79 71 61 54 48 44 37 33 30 28 26

329 226 182 156 138 125 107 95 84 76 65 58 52 48 45

467 321 258 221 196 177 152 134 119 108 92 82 74 68 63

Note: Maximum undiluted propane capacities listed are based on an 11-in. w.c. setting and 0.5-in. w.c. pressure drop. Capacities in 1000 Btu/hr.

Notes: 1. Maximum undiluted propane capacities listed are based on a gauge pressure of 10-psi first-stage setting and 1-psi pressure drop. Capacities in 1000 Btu/hr. 2. To convert to capacities at a gauge pressure of 5 psi setting with 10 percent (0.5 psi) pressure drop, multiply values by 0.606. To convert to capacities at a gauge pressure of 15 psi setting with 10 percent (1.5 psi) pressure drop, multiply values by 1.380. * This section is an excerpt from the NFPA 58 Liquified Petroleum Gas Code — 2001 Edition

The VICTOR Propane Equipment Catalog


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.