Toshiba Estia - installatørvejledning

Page 24

Engineering Data Book

4.HYDRO UNIT

3-way mixing valve connection Required Actuator Specification Electrical Specification: 230 V; 50 Hz; <100 mA The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating system. • Connect the 3-way mixing valve to terminals 2, 3 and 4 on Terminal Block 04 (for Type 1 mixing valve) or on terminals 1, 2 and 3 on Terminal Block 04 (for Type 2 mixing valve). • Connect the 3-way mixing valve in accordance with the diagrams below: Type 1: SPDT

Type 2: SPDT

port “A” to Zone 2 Heating

port “A” to Zone 2 Heating Hydro Unit TB 04

Hydro Unit

1 open

port “AB” to Hydro unit

port “A” close

TB 04

port “A” close

1

port “AB” to Hydro unit

2

open

3

2

4

3 4

port “B” BLANK OFF

port “B” BLANK OFF

Hot water cylinder connection (optional) Earth leakage breaker INPUT Power 230 V ~ 50 Hz

2 1

4 1

2

L

Hot water cylinder

Hot water cylinder electrical box connections

Hydro Unit

24

N

Terminal block 03