ICON Base Instrumentation cable

Page 36

ICON® Base

36

ICON® Instrumentation Cable

EN 50288-7

Multi-Pair, XLPE-Insulation, Individual & Collective Screen, PVC-Sheath

Characteristics ■■ ■■ ■■ ■■ ■■ ■■ ■■

■■

Oil

reduced flame propagation oil resistant sunlight resistant indoor and outdoor installation on racks, trays, in conduits for direct burial blue for intrinsically safe systems available reinforced

FR

RE-2X(St)Yv-fl PiMF

90 °C / 300 V

Construction Conductor

Technical data plain annealed copper wire, stranded, size:

Flame propagation

0.5 mm2, 0.75 mm2, 1 mm2, 1.3 mm2,

- Test on single cable

IEC 60332-1-2

1.5 mm , 2.5 mm

- Test on bunched cables

IEC 60332-3-24 (Cat. C) ASTM D 2863 (min. 30 %)

2

2

Insulation

cross-linked polyethylene XLPE

Colour code

black / white, continuously numbered on

Limiting Oxygen Index (LOI)

white core (1, 2, 3...) for multi-element

Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

24 µm aluminium / PETP tape over tinned

Amount of halogen acid gas

IEC 60754-1 (max. 23 %)

copper drain wire, 0.6 mm Ø, plastic tape

Oil resistance

ICEA S-73-532

under and above screen

Sunlight resistance

UL 1581 section 1200

Temperature range

-30 °C up to +90 °C

Individual screen

Wrapping

at least 1 layer of plastic tape

Collective screen

24 µm aluminium / PETP tape over tinned copper drain wire, 0.5 mm

Outer sheath

(during operation)

2

polyvinyl chloride PVC, reinforced, black,

-5 °C up to +50 °C

blue for intrinsically safe systems

(during installation) Minimum bending radius

7.5 x cable diameter

Cable marking LEONI KERPEN ICON INSTRUMENTATION CABLE SIZE 300 V RP EN 50288-7 CE PRODUCTION LOT CODE LENGTH MARKING

Electrical Properties at 20 °C Conductor cross-section

nom.

0.5 mm2

0.75 mm2

1 mm2

1.3 mm2

1.5 mm2

2.5 mm2

Conductor resistance

max.

36.7 Ω/km

25.0 Ω/km

18.5 Ω/km

14.2 Ω/km

12.3 Ω/km

7.6 Ω/km

115 nF/km

115 nF/km

115 nF/km

115 nF/km

115 nF/km

Insulation resistance

min.

Mutual capacitance 2 to 4 elements:

max.

Inductance

max.

L/R ratio

max.

5000 MΩ x km 115 nF/km

1 mH/km 25 µH/Ω

40 µH/Ω

Test voltage Urms (core : core)

1500 V

Test voltage Urms (core : screen)

1500 V

Operating voltage

300 V

60 µH/Ω

www.leoni-industrial-projects.com


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.