ROOF INTEGRITY THERMOGRAPHIC INSPECTION FOR: CLIENT LOCATION: ADDRESS

DATE: 25/11/13 TI JOB NO. TI-17646

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Introduction to your Ti Thermal Imaging LTD roofing thermographic inspection This thermographic roof inspection has been carried out using a Flir camera with data input onto a purpose built tablet PC platform for instantaneous results and report generation. A Webmanager houses all data that is permanently accessible over the internet allowing the user to track and monitor problems and their repair status. The inspection specification is listed below: 1. 1. 2. 3. 4.

IR camera: Flir ThermaCAM Software: Tablet PC and Webmanager enabled Thermographer: ITC Trained Extech Instruments for humidity/wind speed etc Leico laser distance measurements

This investigation is employing the use of thermographics and infra-red in order to assess the integrity of the building roof insulation. The intention is to identify areas of thermal anomaly which could be as a result of damp or wet roof insulation and also it will highlight areas of potential air leakage which may lead to water ingress. Infra-red thermographic measurement works on temperature differential. Damp and dry roof insulation possess different thermal masses so this means they heat up and cool down at different rates. This inspection can either be performed 1 hour after dark as damp areas will retain their heat longer or 1 hour after sunrise where damp areas will remain cooler for longer. Ambient temperature is a crucial part of this inspection and we have the ability to exploit the differentials in temperature between night and daytime where the roof insulation will equilibrate to ambient. Additionally, solar load can assist with temperature change although this is not absolutely necessary as is commonly thought. Initial visual inspection of the site took place in order to familiarise with any irregularities or access problems. Accessibility: Full access to roof th th Areas: Above 5 6 and plantroom Thermal Clutter: None Image Capture: All areas

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Executive summary Object Parameters for this Inspection Inspection Commencing Weather Wind Speed Ambient Temperature External

17.30 Dry <2mph 6ºC

The roof was imaged at between 17.30 and 19.00 to take advantage of the changing temperatures and solar gain the roof was receiving. The day had considerable solar gain, clear skies and no rain making conditions ideal. Summary of findings:

EXTENSIVE DAMP ROOF INSULATION

All roof areas suggest areas of damp roof insulation: th  6 floor West facing – By access door  Main building roof – North and South areas of the West and East ends th  6 floor South facing – South end  Plant room – By steps It is suggested the roof areas be investigated further to confirm damp and perhaps to investigate further for penetrations which might lead to the root cause.

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


6th floor West facing roof

N

Main roof

6th floor South facing roof Plantroom


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Report pages: The combined report contains the following pages: NB Page numbers have been left in for additional ID purposes. Page numbers run in sequence beginning at #1 for each section but do not run in sequence for the whole combined report. 1. 2. 3. 4. 5.

Cover Page for Visual: This is a summary report which offers the amount of problems found and their severity grade. It is for a complete site overview. List of all open problems: This is the full list of areas found with problems and includes their locations. Inspection Inventory: This is a full inventory of areas inspected and their test status. Documentation pages: These pages include the details of all anomalies found for individual areas. Cost Benefit Analysis: This is only used for when the option of quantifying the elevations is exercised and offers Cost of energy used in £, quantity in kwHr and amount of CO2 generated in KG. All these values are based on a yearly period.

The Webmanager contains all of the above reports and lists problems, cost benefits and baseline trends in easy to source locations. To view your current and previous inspections, please logon to your personal Webmanager using your username and password already supplied. If you do not have this please contact Ti on 0845 4586315. http://193.228.155.40/inspectrend or www.thermalimaging.co.uk Webmanager tutorial snapshot: Navigate to the area you need using one of the 6 tabs at the top of the screen: Overview Inspection Inventory Problems Cost Benefit Baseline

Summary listing all problems active or closed with severity grade. Select site and then hit search to reveal historical list of inspections. Select more next to the inspection that you want to see further details of. At the bottom of the page is a “Reports” button. Hit this to display your reports. The complete report will be the very first one and will be prefixed by “1_” in order for it to be located at the very top of the list. Select site and then hit search to reveal a full inventory of surveyed areas, test status, priority to site operation and last inspected date. Select site and then hit search to reveal a list of all open/closed problems found with severity grade, repair status and date found. Attach a work order here for remedial action and view the problem in its own individual report page. Select site and then hit search to reveal the quantified results if you have exercised this option. Select site and then hit search to reveal baseline trend data for all areas surveyed. Here you can view individual trend reports for each area where the latest IR/DC images are displayed with a historical temperature graph for baseline temp/current insp. Temp and threshold temp.

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Cover Page for Visual Executive and Operations summary of problems found Also available on your Webmanager Overview page Please use your login details provided http://193.228.155.40/inspectrend

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


INFRARED THERMOGRAPHIC INSPECTION OF VISUAL PROBLEMS

Page 1

Report Date: 25/11/2013

Provided for Overview:

The Infrared Inspection was performed by TI Thermal Imaging, by a certified infrared Thermographer. All of the items inspected are listed in this InspecTrend report. Any anomalies are listed in order of priority based on the component's temperature rise, as measured from a reference component of equal type and load at the time of the inspection. TI Thermal Imaging assumes no liability directly or indirectly as a result of this inspection. Current Inspection No: Prior Inspection No:

2262 November 21, 2013

Priority

Current Inspection

Temp Rise

1-Critical 2-Serious 3-Important 4-Minor

Prior Inspection NA NA NA NA

0 = 0% 14 = 93% 0 = 0% 0 = 0% Total Tested Problems:

Number of New Documented Problems: Number of Tested re-occuring Problems:

15 15 =100% 0 = 0%

Number of prior problems which were Not Tested this inspection :

NA

Number of Total Open Problems Number of prior problems which tested Normal this inspection

15 NA

: :

NA

Percent of Change NA NA NA NA NA

NA NA

NA NA

I hereby certify the above project was inspected by myself or under my direction and that the enclosed data is the direct result of this inspection. TI Thermal Imaging Wallace, Richard Certification Level/No.: ITC Level II * Summary of reoccuring problems on following page(s)

This inspection & report was performed & generated by: TI Thermal Imaging


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

List of Open Problems Full list of thermal, mechanical and visual issues found Also available on your Webmanager Problems page Please use your login details provided http://193.228.155.40/inspectrend

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Page: 1 of 2

List of All Open Problems

Operation Priority Key CTO = Critical to operation ETO = Essential to operation NON = Non-essential to operation UNC = Un-Classified

Report Date: 25/11/2013 Prior Inspection No : Current Inspection No : 2262

November 21, 2013

Prob# Asset ID V3

-

Insp# Equipment: 6TH FLOOR SOUTH FACING ROOF \ CENTRE BUTTRESS 5-6

Temp Rise

% Load

Severity

Status

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

Component: Elevated surface temperature at AR1

V2

-

Equipment: 6TH FLOOR SOUTH FACING ROOF \ CENTRE-BUTTRESS 3-4 Component: Elevated surface temperature at AR1

V4

-

Equipment: 6TH FLOOR SOUTH FACING ROOF \ EAST SIDE BUTTRESS 7-8 Component: Elevated surface temperature at AR1

V5

-

Equipment: 6TH FLOOR SOUTH FACING ROOF \ VIEW EAST Component: Elevated surface temperature at AR1

V6

-

Equipment: 6TH FLOOR SOUTH FACING ROOF \ VIEW WEST Component: Elevated surface temperature at AR1

V1

-

Equipment: 6TH FLOOR WEST FACING ROOF \ VIEW NORTH RIGHT SIDE Component: Elevated surface temperature at AR1

V8

-

Equipment: MAIN BUILDING ROOF \ ADJACENT PLANT ROOM VIEW EAST Component: Elevated surface temperature at AR1

V 15 -

Equipment: MAIN BUILDING ROOF \ ADJACENT PLANT ROOM VIEW EAST Component: Elevated surface temperature at AR1 and AR2

This inspection & report was performed & generated by: TI Thermal Imaging


Page: 2 of 2

List of All Open Problems

Operation Priority Key CTO = Critical to operation ETO = Essential to operation NON = Non-essential to operation UNC = Un-Classified

Report Date: 25/11/2013 Prior Inspection No : Current Inspection No : 2262

November 21, 2013

Prob# Asset ID V7

-

Insp# Equipment: MAIN BUILDING ROOF \ ADJACENT PLANT ROOM VIEW WEST

Temp Rise

% Load

Severity

Status

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

2262

2-Serious

TESTED

Component: Elevated surface temperature at AR1

V 10 -

Equipment: MAIN BUILDING ROOF \ BUTTRESS 3-4 Component: Elevated surface temperature at AR1

V9

-

Equipment: MAIN BUILDING ROOF \ EAST END Component: Elevated surface temperature at AR1

V 13 -

Equipment: MAIN BUILDING ROOF \ VIEW WEST NORTH Component: Elevated temperature at AR1

V 14 -

Equipment: MAIN BUILDING ROOF \ VIEW WEST NORTH EAST END Component: Elevated surface temperature at AR1

V 12 -

Equipment: MAIN BUILDING ROOF \ VIEW WEST SOUTH Component: Elevated surface temperature at AR1 and AR2

V 11 -

Equipment: PLANT ROOM ROOF \ VIEW WEST NORTH SIDE Component: Elevated surface temperature at AR1

This inspection & report was performed & generated by: TI Thermal Imaging


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Inspection Inventory Pages Equipment listing and test status Also available on your Webmanager Inventory page with Photos Please use your login details provided http://193.228.155.40/inspectrend

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Current Inspection Inventory Status By Inspection Order

Page: 1 Equipment Test Status Key

Problem Type Key

TBT = To Be Tested NT/NL = Not Tested/No Load NT/TC = Not Tested/Time Constraint NT/UR = Not Tested/Under Repair NT/LO = Not Tested/Locked Out NT/NA = Not Tested/Not Available

TD = T/D Electrical M = Mechanical V = Visual Inspection Operation Priority Key Prior Inspection No: Current Inspection No: 2262

Report Date: 25/11/2013 Inspected By :

Wallace, Richard

Work Order

Asset ID

CTO = Critical to operation ETO = Essential to operation NON = Non-essential to operation UNC = Un-Classified

NT/NS = Not Tested/Not Specified NSFI = Not Selected for this insp.

Equipment Description

CTO

Tested

Problem #

6TH FLOOR WEST FACING ROOF VIEW NORTH RIGHT SIDE

CTO CTO

TESTED TESTED

V1

CTO CTO

TESTED TESTED

CTO CTO

TESTED TESTED

CENTRE-BUTTRESS 3-4 CENTRE BUTTRESS 5-6 EAST SIDE BUTTRESS 7-8

CTO CTO CTO

TESTED TESTED TESTED

V2 V3 V4

VIEW EAST VIEW WEST

CTO CTO

TESTED TESTED

V5 V6

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW WEST

CTO CTO

TESTED TESTED

V7

-

ADJACENT PLANT ROOM VIEW EAST EAST END BUTTRESS 3-4

CTO CTO CTO

TESTED TESTED TESTED

V8, V15 V9 V10

NI NI

-

WEST SECTION OPPOSITE PLANT ROOM VIEW WEST SOUTH EAST SIDE

CTO CTO

TESTED TESTED

NI NI

-

VIEW WEST SOUTH VIEW WEST NORTH

CTO CTO

TESTED TESTED

V12 V13

NI NI NI

-

CTO CTO CTO

TESTED TESTED TESTED

V14

NI NI

-

VIEW WEST NORTH SIDE VIEW EAST NORTH SIDE

CTO CTO

TESTED TESTED

V11

NI

-

VIEW EAST SOUTH SIDE

CTO

TESTED

NI NI

-

NI NI

-

NI NI

-

NI NI NI

-

NI NI

-

NI NI

-

NI NI NI

VIEW NORTH LEFT SIDE VIEW SOUTH 6TH FLOOR SOUTH FACING ROOF WEST SIDE BUTTRESS 1-2

VIEW WEST NORTH EAST END PLANT ROOM ROOF VIEW WEST SOUTH SIDE

This inspection and report was performed and generated by: TI Thermal Imaging

Test Status Notes


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Documentation pages for Visual findings Details of Visual problems found Also available on your Webmanager Problems page Please use your login details provided http://193.228.155.40/inspectrend

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Page 1

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/1

Asset ID: -

Is Chronic:

No

6TH FLOOR WEST FACING ROOF VIEW NORTH RIGHT SIDE

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1160A.jpg File: DC_1163.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:39 PM Time: 05:22 PM Wallace, Richard ITC Level II


Page 2

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/2

Asset ID: -

Is Chronic:

No

6TH FLOOR SOUTH FACING ROOF CENTRE-BUTTRESS 3-4

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1174A.jpg File: DC_1175.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:42 PM Time: 05:37 PM Wallace, Richard ITC Level II


Page 3

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

Current Prob No: Visual/3

Asset ID: -

Is Chronic:

No

6TH FLOOR SOUTH FACING ROOF CENTRE BUTTRESS 5-6

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1178A.jpg File: DC_1179.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:45 PM Time: 05:40 PM Wallace, Richard ITC Level II


Page 4

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/4

Asset ID: -

Is Chronic:

No

6TH FLOOR SOUTH FACING ROOF EAST SIDE BUTTRESS 7-8

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1180A.jpg File: DC_1181.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:46 PM Time: 05:41 PM Wallace, Richard ITC Level II


Page 5

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/5

Asset ID: -

Is Chronic:

No

6TH FLOOR SOUTH FACING ROOF VIEW EAST

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Further investigation required

File: IR_1182A.jpg File: DC_1185.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:59 PM Time: 05:44 PM Wallace, Richard ITC Level II


Page 6

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/6

Asset ID: -

Is Chronic:

No

6TH FLOOR SOUTH FACING ROOF VIEW WEST

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1184A.jpg File: DC_1185.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:57 PM Time: 05:44 PM Wallace, Richard ITC Level II


Page 7

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/7

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW WEST

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1188A.jpg File: DC_1189.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:48 PM Time: 05:47 PM Wallace, Richard ITC Level II


Page 8

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/8

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW EAST

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Further investigation required

File: IR_1190A.jpg File: DC_1191.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:49 PM Time: 05:50 PM Wallace, Richard ITC Level II


Page 9

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/9

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF EAST END

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1194A.jpg File: DC_1195.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 09:09 PM Time: 05:52 PM Wallace, Richard ITC Level II


Page 10

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/10

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF BUTTRESS 3-4

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1196A.jpg File: DC_1197.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 08:56 PM Time: 05:53 PM Wallace, Richard ITC Level II


Page 11

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/11

Asset ID: -

Is Chronic:

No

PLANT ROOM ROOF VIEW WEST NORTH SIDE

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1200A.jpg File: DC_1201.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 09:18 PM Time: 05:56 PM Wallace, Richard ITC Level II


Page 12

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/12

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF VIEW WEST SOUTH

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1 and AR2

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1214A.jpg File: DC_1215.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 09:26 PM Time: 06:01 PM Wallace, Richard ITC Level II


Page 13

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/13

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF VIEW WEST NORTH

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1216A.jpg File: DC_1217.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 09:32 PM Time: 06:01 PM Wallace, Richard ITC Level II


Page 14

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/14

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF VIEW WEST NORTH EAST END

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1218A.jpg File: DC_1219.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 09:35 PM Time: 06:01 PM Wallace, Richard ITC Level II


Page 15

Visual Problem Documentation Work Order#: Location/Equipment Information

InspectionNo: Report Date:

NOT ISSUED

Current Prob No: Visual/15

Asset ID: -

Is Chronic:

No

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW EAST

Problem severity:

2-Serious

2262 25/11/2013

Classification:

Buildings

Observations:

Elevated surface temperature at AR1 and AR2

What is the Cause:

Suspected damp roof insulation

Recommendations:

Repair or replace insulation as necessary

File: IR_1228A.jpg File: DC_1229.jpg

Date: 25/11/2013 Date: 25/11/2013 Technician: Certification Level/No.:

This inspection & report was performed & generated by: TI Thermal Imaging

Time: 09:45 PM Time: 06:05 PM Wallace, Richard ITC Level II


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Benchmark Baseline Trending Full list of equipment baseline trends is also available on your Webmanager Please use your login details provided http://193.228.155.40/inspectrend

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Page: 1

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR WEST FACING ROOF \ VIEW NORTH RIGHT SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1164.jpg

0 2262

DC_1165.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 3 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 2

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR WEST FACING ROOF \ VIEW NORTH LEFT SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1166.jpg

0 2262

DC_1167.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 3

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR WEST FACING ROOF \ VIEW SOUTH Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1168.jpg

0 2262

DC_1169.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 1 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 4

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR SOUTH FACING ROOF \ WEST SIDE BUTTRESS 1-2 Equipment ID: -

Work Order:

NI

9 8

Threshold

7

Measured

6

Ambient

5 4 3 2 1

IR_1172.jpg

0 2262

DC_1173.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 8 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes POSSIBLE HEAT FROM PLANT


Page: 5

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR SOUTH FACING ROOF \ CENTRE-BUTTRESS 3-4 Equipment ID: -

Work Order:

NI

6.2 6

Threshold

5.8

Measured

5.6

Ambient

5.4 5.2 5 4.8 4.6

IR_1174.jpg

4.4 2262

DC_1175.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 5 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 6

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR SOUTH FACING ROOF \ CENTRE BUTTRESS 5-6 Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1178.jpg

0 2262

DC_1179.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 3 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 7

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR SOUTH FACING ROOF \ EAST SIDE BUTTRESS 7-8 Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1180.jpg

0 2262

DC_1181.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 8

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR SOUTH FACING ROOF \ VIEW EAST Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1182.jpg

0 2262

DC_1183.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 9

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

6TH FLOOR SOUTH FACING ROOF \ VIEW WEST Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1184.jpg

0 2262

DC_1185.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 10

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ ADJACENT PLANT ROOM VIEW WEST Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1186.jpg

0 2262

DC_1187.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 11

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ ADJACENT PLANT ROOM VIEW EAST Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1190.jpg

0 2262

DC_1191.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 12

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ EAST END Equipment ID: -

Work Order:

NI

6 Threshold 5 Measured 4

Ambient

3 2 1

IR_1194.jpg

0 2262

DC_1195.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 5

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 13

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ BUTTRESS 3-4 Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1196.jpg

0 2262

DC_1197.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 14

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ WEST SECTION OPPOSITE PLANT ROOM Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1198.jpg

0 2262

DC_1197.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 15

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ VIEW WEST SOUTH EAST SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1212.jpg

0 2262

DC_1213.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 16

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ VIEW WEST SOUTH Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1214.jpg

0 2262

DC_1215.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 17

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ VIEW WEST NORTH Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1216.jpg

0 2262

DC_1217.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 18

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

MAIN BUILDING ROOF \ VIEW WEST NORTH EAST END Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1218.jpg

0 2262

DC_1219.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 2 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 19

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

PLANT ROOM ROOF \ VIEW WEST SOUTH SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1202.jpg

0 2262

DC_1203.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 1 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 20

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

PLANT ROOM ROOF \ VIEW WEST NORTH SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1204.jpg

0 2262

DC_1205.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 1 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 21

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

PLANT ROOM ROOF \ VIEW EAST NORTH SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1206.jpg

0 2262

DC_1207.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 1 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Page: 22

Equipment Baseline Trending Report By Inspection Order

Current Inspection No: 2262

Report Date:

November 21, 2013

25/11/2013

PLANT ROOM ROOF \ VIEW EAST SOUTH SIDE Equipment ID: -

Work Order:

NI

7 Threshold

6

Measured

5

Ambient

4 3 2 1

IR_1208.jpg

0 2262

DC_1209.jpg

Inspection History: Inspection No

Date Inspected

Test Status

2262

25/11/2013

TESTED

Measured Temp Threshold Temp 1 C

5

C

Ambient Temp Status Note 6

C

This report was generated by InspecTrend and this inspection was performed by: TI Thermal Imaging ritten consent.

Customer Notes


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Work Order Documentation pages Fax or Email back Corrective Work Orders Also available on your Webmanager Problems page Please use your login details provided http://193.228.155.40/inspectrend

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87


Page: 1

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-1

Current Prob No: Visual/1

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

6TH FLOOR WEST FACING ROOF VIEW NORTH RIGHT SIDE

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1160A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1163.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 2

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-2

Current Prob No: Visual/2

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

6TH FLOOR SOUTH FACING ROOF CENTRE-BUTTRESS 3-4

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1174A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1175.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 3

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #: Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-3

Current Prob No: Visual/3

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

6TH FLOOR SOUTH FACING ROOF CENTRE BUTTRESS 5-6

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1178A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1179.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 4

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-4

Current Prob No: Visual/4

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

6TH FLOOR SOUTH FACING ROOF EAST SIDE BUTTRESS 7-8

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1180A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1181.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 5

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-5

Current Prob No: Visual/5

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

6TH FLOOR SOUTH FACING ROOF VIEW EAST

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1182A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1185.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure:

Parts Req. After Failure:

Repair Procedure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Further investigation required

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 6

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-6

Current Prob No: Visual/6

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

6TH FLOOR SOUTH FACING ROOF VIEW WEST

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1184A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1185.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 7

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-7

Current Prob No: Visual/7

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW WEST

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1188A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1189.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 8

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-8

Current Prob No: Visual/8

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW EAST

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1190A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1191.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes Repaired By:

Root Cause: Parts Req. Before Failure:

Parts Req. After Failure:

Repair Procedure:

25/11/2013

Further investigation required

Repair Notes: Repair Recommendation: Further investigation required

This inspection & report was performed & generated by: TI Thermal Imaging

No

Unknown


Page: 9

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-9

Current Prob No: Visual/9

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF EAST END

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1194A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1195.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Page: 10

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-10

Current Prob No: Visual/10

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF BUTTRESS 3-4

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1196A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1197.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Page: 11

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-11

Current Prob No: Visual/11

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

PLANT ROOM ROOF VIEW WEST NORTH SIDE

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1200A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1201.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Page: 12

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-12

Current Prob No: Visual/12

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF VIEW WEST SOUTH

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1 and AR2

Observations:

Elevated surface temperature at AR1 and AR2

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1214A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1215.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Page: 13

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-13

Current Prob No: Visual/13

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF VIEW WEST NORTH

Hazard Classification:

Buildings

Hazard Group:

Elevated temperature

Hazard Issue:

at AR1

Observations:

Elevated temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1216A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1217.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Page: 14

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-14

Current Prob No: Visual/14

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF VIEW WEST NORTH EAST END

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1

Observations:

Elevated surface temperature at AR1

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1218A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1219.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Page: 15

Documentation/ Work Order Visual: Please add Corrective Work Order Work Order #:

NOT ISSUED

Corrective Work Order #: InspectionNo: Report Date:

PLEASE ADD CORRECTIVE WORK ORDERS ABOVE

2262 25/11/2013

2262-15

Current Prob No: Visual/15

Location/Equipment Information

Repair Priority:

2-Serious

Asset ID: Barcode:

NI

Hazard Type:

Visual

Location:

MAIN BUILDING ROOF ADJACENT PLANT ROOM VIEW EAST

Hazard Classification:

Buildings

Hazard Group:

Elevated surface temperature

Hazard Issue:

at AR1 and AR2

Observations:

Elevated surface temperature at AR1 and AR2

What is the Cause:

Suspected damp roof insulation

Photo File:

IR_1228A.jpg

Repair Information Consequences of Failure:

Photo Date:

25/11/2013

Photo File:

DC_1229.jpg

PLEASE FAX BACK AFTER REPAIR TO: 0871 900 4978 OR INFO@THERMALIMAGING.CO.UK Repair Date:

Photo Date:

Loss to Production Yes

No

Repaired By:

Root Cause: Parts Req. Before Failure: Repair Procedure:

Parts Req. After Failure:

25/11/2013

Repair or replace insulation as necessary

Repair Notes: Repair Recommendation: Repair or replace insulation as necessary

This inspection & report was performed & generated by: TI Thermal Imaging

Unknown


Ti Thermal Imaging LTD Unit 8, Weybridge Business Centre, 66 York Road, Weybridge, Surrey, KT13 9DY Tel: 0845 458 6315 Fax: 0871 9004978 E-mail: info@thermalimaging.co.uk Web: www.thermalimaging.co.uk

Client Work Appraisal We are continually trying to improve our service and ensure that all our inspections are carried out to the highest standards. Please use the form below to add your comments, anonymously if you prefer and send back to us at the address above or: Email: info@thermalimaging.co.uk Fax: +44 870 9004971 TI Job Number: (Optional)

Excellent

Good

Mediocre

Poor

Office: Response time to enquiry Content of information sent on enquiry Telephone and email manner Price Value Engineer: Time keeping Appearance Code of conduct Subject knowledge Method of work Engineer flexibility Inspection Specification: Equipment and software Report content Report delivery time Report retrieval Other Comments:

Report generated by Ti Thermal Imaging LTD. Company Registered in England: 04450573 VAT No. 828 6288 87

Comments


Flat roof inspection sample