DC

Air Circuit Breakers Moulded Case Circuit Breakers &

www.terasaki.co.jp CAT REF. ’13-I73E


TABLE OF CONTENTS

1.General ………………………………………1-1 Introduction ……………………………………………1-2

5.Outline Dimensions …………………………5-1 DC Air Circuit Breakers Outline Dimensions

General …………………………………………………1-3

AR216S, AR220S 3P…………………………………5-2

Selection Chart …………………………………………1-4

AR325S, AR332S 3P…………………………………5-4 AR325-NDH 4P ………………………………………5-6

2.Ratings and Specifications ………………2-1

AR440SB 3P …………………………………………5-8

Air Circuit Breakers for DC350V-800V ………………2-2

AR440S 3P …………………………………………5-10

Moulded Case Circuit Breakers for DC350V-600V …2-3

DC Moulded Case Circuit Breakers Outline Dimensions

Moulded Case Circuit Breakers for DC750V-1000V…2-5 Switch-disconnectors for DC600V-1000V ……………2-7

S160-SD, S160-GD, S160-SDN, S250-SD, S250-GD, S250-SDN 3P ……5-12 S400-ND 3P …………………………………………5-13

3.Characteristics ………………………………3-1

S800-ND 3P …………………………………………5-13

Time/Current characteristic curves,

S1000-ND 2P, 3P……………………………………5-14

Ambient Compensating Curves

XS1250ND 2P, 3P …………………………………5-15

S160-SD, S160-GD, S250-SD, S250-GD 3P ………3-2

XS1600ND 2P, 3P …………………………………5-16

S400-ND, S800-ND 3P ………………………………3-3

XS2000ND 2P, 3P …………………………………5-17

S1000-ND 2P, 3P ……………………………………3-3

XS2500ND, XS3200ND 2P, 3P ……………………5-18

XS1250ND, XS1600ND, XS2000ND 2P, 3P ………3-4

PVS160-SDL, PVS250-SDL 3P ……………………5-19

XS2500ND, XS3200ND 2P, 3P ……………………3-5

PVS160-SDL, PVS250-SDL,

PVS160-SDL, PVS250-SDL 3P, 4P ………………3-6 PVS160-SDH, PVS250-SDH 4P ……………………3-6

PVS160-SNL, PVS250-SNL 4P …………5-19 PVS160-SDH, PVS250-SDH,

PVS400-NDL 3P ……………………………………3-6

PVS160-SNH, PVS250-SNH 4P ………5-20

PVS400-NDL, PVS400-NDH, PVS800-NDH 4P …3-7

PVS400-NDL 3P ……………………………………5-21

PVS800-NDL 3P, 4P …………………………………3-7

PVS400-NDL, PVS400-NDH 4P …………………5-22 PVS400-NNL, PVS400-NNH 4P …………………5-22

4.Mounting and Connection …………………4-1

PVS800-NDL 3P ……………………………………5-23

Connection of conductors to DC circuit breakers …4-2

PVS800-NDL, PVS800-NDH 4P …………………5-24

Insulation distance DC600V or less …………………4-7

PVS800-NNL, PVS800-NNH 4P …………………5-24

Insulation distance DC750V-1000V PVS160-SDL 3P, PVS250-SDL 3P …………………4-8 PVS160-SDL 4P, PVS250-SDL 4P PVS160-SNL 4P, PVS250-SNL 4P ………4-9 PVS160-SDH 4P, PVS250-SDH 4P PVS160-SNH 4P, PVS250-SNH 4P ……4-10 PVS400-NDL 3P ……………………………………4-11 PVS400-NDL 4P, PVS400-NDH 4P ………………4-12 PVS400-NNL 4P, PVS400-NNH 4P ………………4-13 PVS800-NDL 3P ……………………………………4-14 PVS800-NDL 4P, PVS800-NDH 4P ………………4-15 PVS800-NNL 4P, PVS800-NNH 4P ………………4-16


General

General

1

1

Introduction ………………………………………………………………………1-2 General ……………………………………………………………………………1-3 Selection Chart …………………………………………………………………1-4

1-1


Introduction

In recent years, as part of the drive to reduce greenhouse gas emissions, significant attention is now being directed towards the energy produced by large-scale photovoltaic (solar), wind, and biomass energy power generation. The total power generation capacity of facilities for these new energy sources is expected to exceed that produced by nuclear energy by approximately 2030. To aid and support these new technologies, Terasaki now offer a new, broad range of dedicated DC air circuit breakers and moulded case circuit breakers. The new range of Terasaki DC circuit breakers are ideally suited for all types of industries, buildings, as well as the information technology and communications sectors where highly reliable sources of electric power are required.

1-2

AR220S

PVS400-NDL

DC

DC

Air Circuit Breakers

Moulded Case Circuit Breakers

Rated current 2000A Rated breaking capacity DC600V 40kA

Rated current 400A Rated breaking capacity DC750V 10kA


General

Electrical and electronic equipment used in the advanced information and communications sectors requires a highly reliable power source. Should a power failure occur, and to assist with continuity of electrical power, it is

General

DC power sources for the Uninterruptible Power Supply (UPS) market

1

standard practice to install an Uninterruptable Power Supply (UPS). A data centre is where Internet servers and other systems for data communications, such as fixed, mobile, and IP telephones are installed. At the data centre, AC power from the main system power source is sent to the UPS, and is temporarily converted to DC power. A storage battery is then charged with this DC power, which is reconverted back into AC power and then sent to the information equipment.

Building and Industrial power back-up A UPS is typically required for critical power systems in department stores, hotels, hospitals, theaters, and office buildings. For example, in semiconductor manufacturing plants that feature advanced automation as a part of their production processes, UPS systems with large battery capacities are used to take measures against any large-scale power outage affecting critical manufacturing facilities.

Photovoltaic power generation Photovoltaic (or Solar) power generation, which is attracting attention as clean energy, ranges from simple generation of up to several kilowatts for home use, to larger systems of 100 kilowatts or greater for industrial use. In the "School New Deal" program, one of the governmental measures during the economic crisis, were for ecofriendly modifications which advocated the use of photovoltaic power generation at schools. One example is a power distribution system linked to a source of photovoltaic power generation. The current produced from the photovoltaic solar cells is sent to a power conditioner via a diode with a DC circuit breaker in a junction box and then converted into AC, which can then be supplied to a load via a distribution board.

Rationalization of use of electric power via large-capacity storage battery Energy from new power sources such as wind and photovoltaic power generation do not have a stable output. A lithium ion battery and a sodium-sulfur (NAS) battery can suppress such fluctuations by load leveling. The battery is charged at night using a lower electrical power rate at night and discharged at daytime when the electrical power usage rate is higher, and in addition, any new electrical power generated can also be saved. For this purpose, large-capacity storage battery systems are used at wind and photovoltaic power generation facilities. The use of these types of systems is expected to grow across all user sectors requiring large amounts of power, plus as an additional measure against possible power outages.

1-3


Selection Chart Frame size (A)

Voltage

160

250

400

800

800V

Air Circuit Breakers 600V

1000V

PVS160-SDH

PVS250-SDH

PVS400-NDH

PVS800-NDH

4P 5kA/5kA

4P 5kA/5kA

4P 5kA/5kA

4P 5kA/5kA

PVS160-SDL

PVS250-SDL

PVS400-NDL

PVS800-NDL

3P 5kA/5kA

3P 5kA/5kA

3P 10kA/5kA

3P 10kA/10kA

PVS160-SDL

PVS250-SDL

PVS400-NDL

PVS800-NDL

4P 10kA/5kA

4P 10kA/5kA

4P 10kA/10kA

4P 10kA/10kA

750V

Moulded Case Circuit Breakers

600V

500V

350V

S160-SD

S160-GD

S250-SD

S250-GD

3P 5kA/5kA

3P 10kA/5kA

3P 5kA/5kA

3P 10kA/5kA

S400-ND

S800-ND

3P 15kA/15kA

3P 20kA/10kA

S160-SD

S160-GD

S250-SD

S250-GD

3P 7.5kA/7.5kA

3P 15kA/7.5kA

3P 7.5kA/7.5kA

3P 15kA/7.5kA

S160-SD

S250-SD

S400-ND

S800-ND

3P 10kA/10kA

3P 10kA/10kA

3P 20kA/20kA

3P 30kA/15kA

250V

1000V

Switch-disconnectors

800V

600V

1-4

PVS160-SNH

PVS250-SNH

PVS400-NNH

PVS800-NNH

4P

4P

4P

4P

PVS160-SNL

PVS250-SNL

PVS400-NNL

PVS800-NNL

4P

4P

4P

4P

S160-SDN

S250-SDN

3P

3P


1 1000

1250

1600

2000

2500

3200

4000

General

AR325-NDH 4P 30kA/30kA

AR216S

AR220S

AR325S

AR332S

AR440S

3P 40kA/40kA

3P 40kA/40kA

3P 40kA/40kA

3P 40kA/40kA

3P 40kA/40kA

XS1250ND

XS1600ND

XS2000ND

XS2500ND

XS3200ND

3P 20kA/15kA

3P 20kA/15kA

3P 20kA/15kA

3P 20kA/15kA

3P 20kA/15kA

XS1250ND

XS1600ND

XS2000ND

XS2500ND

XS3200ND

3P 50kA/25kA

3P 50kA/25kA

3P 50kA/25kA

3P 50kA/25kA

3P 50kA/25kA

S1000-ND

XS1250ND

XS1600ND

XS2000ND

XS2500ND

XS3200ND

2P 50kA/20kA

2P 50kA/30kA

2P 50kA/30kA

2P 50kA/30kA

2P 50kA/30kA

2P 50kA/30kA

S1000-ND 3P 20kA/10kA

S1000-ND 3P 30kA/15kA

S160-SD Number of poles

3P 5kA/5kA Icu

Ics

1-5


Air Circuit Breakers for DC350V-800V ………………………………………2-2 Moulded Case Circuit Breakers for DC350V-600V …………………………2-3 Moulded Case Circuit Breakers for DC750V-1000V ………………………2-5 Switch-disconnectors for DC600V-1000V …………………………………2-7

2 Ratings and Specifications

2

Ratings and Specifications

2-1


Air Circuit Breakers for DC350V-800V tly shor Sale

Frame size (A) Type Rated current(max.)〔In〕A Number of poles Rated insulation voltage〔Ui〕 V Rated operational voltage〔Ue〕 V Rated impulse withstand voltage〔U imp〕 kV ■Rated breaking cap, kA JIS C 8201-2-1 Ann.1 Ann.2 DC IEC 60947-2 Icu/Ics ①② Rated short time withstand current〔Icw〕 kA Latching current kA Total breaking time (s) ■Closing operation time Spring charging time (s) max. Close time (s) max. ■No. of operating cycles Mechanical life with maintenance without maintenance Electrical life without maintenance ■Outline dimension mm Draw-out type b a

c

d

Weight kg Reverse connection

DC

AC DC

800V 600V 500V 350V 1s 3s

600V a b c d

1600

2000

2500

2500

3200

4000

4000

AR216S

AR220S

AR325S

AR325-NDH

AR332S

AR440SB

AR440S

1600 3 1000 600 12

2000 3 1000 600 12

2500 3 1000 600 12

2500 4 1000 800 12

3200 3 1000 600 12

4000 3 1000 600 12

4000 3 1000 600 12

― 40/40 40/40 40/40 65 50 65 0.04

― 40/40 40/40 40/40 65 50 65 0.04

― 40/40 40/40 40/40 85 65 85 0.04

30/30 ― ― ― 85 65 85 0.04

― 40/40 40/40 40/40 85 65 85 0.04

― 40/40 40/40 40/40 100 75 85 0.04

― 40/40 40/40 40/40 100 85 100 0.04

10 0.08

10 0.08

10 0.08

10 0.08

10 0.08

10 0.08

10 0.08

30000 15000 1000

25000 12000 1000

20000 10000 500

20000 10000 500

20000 10000 500

15000 8000 500

15000 8000 500

354 460 345 40 76 Yes

354 460 345 40 79 Yes

460 460 345 40 105 Yes

580 460 345 40 125 Yes

460 460 345 40 105 Yes

460 460 345 140 126 Yes

631 460 375 53 139 Yes

Notes: ― : “no” or “not available”. ① : AGR over-current release can not be used for DC. Please prepare DC over-current relay and connect with shunt trip device. ② : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 15ms for short circuit

2-2


Moulded Case Circuit Breakers for DC350V-600V Frame size (A) Type Number of poles ■Ratings Rated current, A Calibrated at 45°C

*2 poles breaker is same outline dimensions as 3 poles breaker. Rated insulation voltage〔Ui〕 V Rated impulse withstand voltage 〔U imp〕 kV ■Rated breaking capacity, kA JIS C 8201-2-1 Ann.1 Ann.2 DC IEC 60947-2 Icu/Ics ④⑤

600V 500V 350V 250V

160

160

250

250

400

800

1000

S160-SD

S160-GD

S250-SD

S250-GD

S400-ND

S800-ND

S1000-ND

3

3

3

3

3

3

2*

25 (16-25) 32 (20-32) 40 (25-40) 63 (40-63) 80 (50-80) 100 (63-100) 125 (80-125) 160 (100-160) 690 8

25 (16-25) 32 (20-32) 40 (25-40) 63 (40-63) 80 (50-80) 100 (63-100) 125 (80-125) 160 (100-160) 690 8

100 (63-100) 125 (80-125) 160 (100-160) 200 (125-200) 250 (160-250)

100 (63-100) 125 (80-125) 160 (100-160) 200 (125-200) 250 (160-250)

250 (160-250) 400 (250-400)

630 (400-630) 800 (500-800)

1000

800 8

800 8

800 8

800 8

800 8

5/5 7.5/7.5 10/10 ―

10/5 15/7.5 ― ―

5/5 7.5/7.5 10/10 ―

10/5 15/7.5 ― ―

15/15 15/15 20/20 ―

20/10 20/10 30/15 ―

― ― ― 50/20

20/10 20/10 30/15 ―

75 130+50 ⑰ 68 95 0.8

75 130+50 ⑰ 68 95 0.8

105 165+55 ⑰ 68 95 1.5

105 165+55 ⑰ 68 95 1.5

140 260 103 145 4.2

210 273 103 145 8.5

210 273 103 145 9.8

10.8

' ○(BAR) ○ ― ― ― ― ― ○⑪ ―

' ○(BAR) ○ ― ― ― ― ― ○⑪ ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

● ● ● ● ― ● ● ― ● ― ― ― ● ● ●⑫ ●⑫ ●⑬ ● ●

● ● ● ● ― ● ● ― ● ― ― ― ● ● ●⑫ ●⑫ ●⑬ ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑫ ●⑫ ●⑬ ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑫ ●⑫ ●⑬ ● ●

● ● ● ● ● ● ● ― ● ― ● ●

● ● ● ● ● ● ● ● ● ― ● ●

● ● ● ● ● ● ● ● ● ― ● ●

● ● ●③ ● ●

● ● ●③ ● ●

● ● ●③ ● ●

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Fixed thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

3

d

a

c

b

a b c d

Exterior

Interior

Weight (' marked standard type) kg ■Connections and Mountings Front-connected (FC) Terminal screws With extension bars Rear-connected (RC) Flat bar studs Plug-in (PM) For switchboards For distribution boards Draw-out type (DR) TemPlug70 (PG) TemPlug45B (PG4) DIN rail mount Clip-in chassis mount ■Accessories (optional) Symbol Auxiliary switch AX Alarm switch AL Shunt trips SH Undervoltage trips UV Motor operator MC External operating Breaker-mounted HB handle Door-mounted (variable depth) HP Toggle extension HA Mechanical interlock Slide type MS Rear-connected type MB Link type ML Wire type MW Toggle holder HH Toggle lock HL Terminal cover For front-connected CF For rear-connected and plug-in CR Interpole barrier BA Terminal block for lead TF Door flange DF ■Standard specifications Overcurrent trip mechanism Colour of cover Trip button (Colour) Handle position indication (ON: Red, OFF: Green) Suitability for isolation Reverse connection

Ratings and Specifications

■External dimensions, mm

2

Notes: ' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. ③ : Line side interpole barriers are supplied as standard. (Front connection only) ④ : Connect 3pole or 4pole in series when over DC250V. ⑤ : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 5ms for short circuit ≦ 10KA less than 10ms for short circuit ≦ 20KA less than 15ms for short circuit > 20KA ⑪ : Provided with DIN rail adaptor. ⑫ : Line side terminal cover is supplied as standard at any voltage. ⑬ : Possible to fit on load side (option). ⑰ : + means the dimension of the terminal cover. See outline dimensions for details.

2-3


Moulded Case Circuit Breakers for DC350V-600V Frame size (A) Type Number of poles ■Ratings Rated current, A Calibrated at 45°C

*2 poles breaker is same outline dimensions as 3 poles breaker. Rated insulation voltage〔Ui〕 V Rated impulse withstand voltage 〔U imp〕 kV ■Rated breaking capacity, kA JIS C 8201-2-1 Ann.1 Ann.2 DC IEC 60947-2 Icu/Ics ④⑤

AC

600V 500V 350V 250V

1250

1600

2000

2500

XS1250ND

XS1600ND

XS2000ND

XS2500ND

XS3200ND

2*

2*

2*

2*

2*

3

3

3

3200 3

1250 ①

1600 ①

2000 ①

2500 ①

3200 ①

690 8

690 8

690 8

690 8

690 8

― ― ― 50/30

20/15 50/25 50/25 ―

― ― ― 50/30

26.0

210 370 140 191 24.0

20/15 50/25 50/25 ―

― ― ― 50/30

27.0

320 450 185 245 50.0

20/15 50/25 50/25 ―

― ― ― 50/30

54.0

320 450 185 245 55.7

3

20/15 50/25 50/25 ―

― ― ― 50/30

20/15 50/25 50/25 ―

62.5

320 450 185 245 55.7

62.5

■External dimensions, mm d

a

b

c

a b c d

Exterior

Interior

Weight (' marked standard type) kg ■Connections and Mountings Front-connected (FC) Terminal screws With extension bars Rear-connected (RC) Flat bar studs Plug-in (PM) For switchboards For distribution boards Draw-out type (DR) TemPlug70 (PG) TemPlug45B (PG4) DIN rail mount Clip-in chassis mount ■Accessories (optional) Symbol Auxiliary switch AX Alarm switch AL Shunt trips SH Undervoltage trips UV Motor operator MC External operating Breaker-mounted HB handle Door-mounted (variable depth) HP Toggle extension HA Mechanical interlock Slide type MS Rear-connected type MB Link type ML Wire type MW Toggle holder HH Toggle lock HL Terminal cover For front-connected CF For rear-connected and plug-in CR Interpole barrier BA Terminal block for lead TF Door flange DF ■Standard specifications Overcurrent trip mechanism Colour of cover Trip button (Colour) Handle position indication (ON: Red, OFF: Green) Suitability for isolation Reverse connection

210 370 140 191 23.8 ― ' ○ ― ― ― ― ― ― ―

― ○ ' ― ― ○ ― ― ― ―

― ○ ' ― ― ○ ― ― ― ―

― ― ' ― ― ― ― ― ― ―

― ― ' ― ― ― ― ― ― ―

● ● ● ● ● ● ● ●⑥ ● ● ― ●

● ● ● ● ● ● ● ●⑥ ● ● ― ●

● ● ● ― ● ― ●⑦ ●② ● ● ― ―

● ● ● ― ● ― ●⑦ ●② ● ● ― ―

● ● ● ― ● ― ●⑦ ●② ● ● ― ―

― ― ●③ ● ●

― ― ●③ ● ●

― ― ― ● ●

― ― ― ● ●

― ― ― ● ●

Magnetic(adjustable) ① Grey Yes (Red) Yes Yes Non

Magnetic(adjustable) ① Grey Yes (Red) Yes Yes Non

Magnetic(adjustable) ① Grey Yes (Red) Yes Non Non

Magnetic(adjustable) ① Grey Yes (Red) Yes Non Non

Magnetic(adjustable) ① Grey Yes (Red) Yes Non Non

Notes: ' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. ① : Instantaneous trip oinly. ② : Supplied as standard. ③ : Line side interpole barriers are supplied as standard. (Front connection only) ④ : Connect 3pole in series when over DC250V. ⑤ : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 5ms for short circuit ≦ 10KA less than 10ms for short circuit ≦ 20KA less than 15ms for short circuit > 20KA ⑥ : One is supplied with every five breakers. Please specify if more are required. ⑦ : Fixed depth. (not adjustable)

2-4


Moulded Case Circuit Breakers for DC750V-1000V Frame size (A) Type Number of poles ■Ratings Rated current, A Calibrated at 45°C

Interior Exterior

Colour of cover Trip button (Colour) Handle position indication (ON: Red, OFF: Green) Suitability for isolation Reverse connection

160

250

PVS160-SDL

PVS160-SDH

PVS250-SDL

250

PVS250-SDH

3

4

4

3

4

4

50 (32-50) 63 (40-63) 100 (63-100) 125 (80-125) 160 (100-160)

50 (32-50) 63 (40-63) 100 (63-100) 125 (80-125) 160 (100-160)

50 (32-50) 63 (40-63) 100 (63-100) 125 (80-125) 160 (100-160)

100 (63-100) 125 (80-125) 160 (100-160) 200 (125-200) 250 (160-250)

100 (63-100) 125 (80-125) 160 (100-160) 200 (125-200) 250 (160-250)

100 (63-100) 125 (80-125) 160 (100-160) 200 (125-200) 250 (160-250)

800 8

800 8

1000 8

800 8

800 8

1000 8

― 5/5

― 10/5

5/5 ―

― 5/5

― 10/5

5/5 ―

105 165+55×2 ⑰ 68 95 1.5

140 165+55×2 ⑰ 68 95 1.9

140+55×2 ⑰ 165 68 95 1.9

105 165+55×2 ⑰ 68 95 1.5

140 165+55×2 ⑰ 68 95 1.9

140+55×2 ⑰ 165 68 95 1.9

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes ⑱

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes ⑱

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes ⑱

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes ⑱

2 Ratings and Specifications

*2 poles breaker is same outline dimensions as 3 poles breaker. Rated insulation voltage〔Ui〕 V AC Rated impulse withstand voltage 〔U imp〕 kV ■Rated breaking capacity, kA JIS C 8201-2-1 Ann.1 Ann.2 DC 1000V IEC 60947-2 Icu/Ics ①② 750V ■External dimensions, mm a d a c b b c d Weight (' marked standard type) kg ■Connections and Mountings Front-connected (FC) Terminal screws With extension bars Rear-connected (RC) Flat bar studs Plug-in (PM) For switchboards For distribution boards Draw-out type (DR) TemPlug70 (PG) TemPlug45B (PG4) DIN rail mount Clip-in chassis mount ■Accessories (optional) Symbol Auxiliary switch AX Alarm switch AL Shunt trips SH Undervoltage trips UV Motor operator MC External operating Breaker-mounted HB handle Door-mounted (variable depth) HP Toggle extension HA Mechanical interlock Slide type MS Rear-connected type MB Link type ML Wire type MW Toggle holder HH Toggle lock HL Terminal cover For front-connected CF For rear-connected and plug-in CR Interpole barrier BA Terminal block for lead TF Door flange DF ■Standard specifications Overcurrent trip mechanism

160

Notes: ' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. ① : Connect 3poles or 4poles in series. ② : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 5ms for short circuit ≦ 10KA less than 10ms for short circuit ≦ 20KA less than 15ms for short circuit > 20KA ⑧ : Both line and load side terminal covers are supplied as standard. ⑰ : + means the dimension of the terminal cover. See outline dimensions for details. ⑱ : Two breakers are available, for ordlnary connection or for reverse connection. Please specify either.

2-5


Moulded Case Circuit Breakers for DC750V-1000V Frame size (A) Type Number of poles ■Ratings Rated current, A Calibrated at 45°C

Exterior

Interior

*2 poles breaker is same outline dimensions as 3 poles breaker. Rated insulation voltage〔Ui〕 V AC Rated impulse withstand voltage 〔U imp〕 kV ■Rated breaking capacity, kA JIS C 8201-2-1 Ann.1 Ann.2 DC 1000V IEC 60947-2 Icu/Ics ①② 750V ■External dimensions, mm a d a c b b c d Weight (' marked standard type) kg ■Connections and Mountings Front-connected (FC) Terminal screws With extension bars Rear-connected (RC) Flat bar studs Plug-in (PM) For switchboards For distribution boards Draw-out type (DR) TemPlug70 (PG) TemPlug45B (PG4) DIN rail mount Clip-in chassis mount ■Accessories (optional) Symbol Auxiliary switch AX Alarm switch AL Shunt trips SH Undervoltage trips UV Motor operator MC External operating Breaker-mounted HB handle Door-mounted (variable depth) HP Toggle extension HA Mechanical interlock Slide type MS Rear-connected type MB Link type ML Wire type MW Toggle holder HH Toggle lock HL Terminal cover For front-connected CF For rear-connected and plug-in CR Interpole barrier BA Terminal block for lead TF Door flange DF ■Standard specifications Overcurrent trip mechanism Colour of cover Trip button (Colour) Handle position indication (ON: Red, OFF: Green) Suitability for isolation Reverse connection

400

400

800

PVS400-NDL

PVS400-NDH

PVS800-NDL

800

PVS800-NDH

3

4

4

3

4

4

250 (160-250) 400 (250-400)

250 (160-250) 400 (250-400)

250 (160-250) 400 (250-400)

630 (400-630) 800 (500-800)

630 (400-630) 800 (500-800)

630 (400-630) 800 (500-800)

800 8

1150 8

1150 8

800 8

1150 8

1150 8

― 10/5

― 10/10

5/5 ―

― 10/10

― 10/10

5/5 ―

140 260 103 145 4.2

185 260 103 145 5.6

185 260 103 145 5.6

210 273 103 145 8.5

280 273 103 145 11.5

280 273 103 145 11.5

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

● ● ● ● ● ● ● ― ― ― ― ●

● ● ● ● ● ● ● ― ― ― ― ●

● ● ● ● ● ● ● ― ― ― ― ●

● ● ● ● ● ● ● ● ― ― ― ●

● ● ● ● ● ● ● ● ― ― ― ●

● ● ● ● ● ● ● ● ― ― ― ●

● ● ●⑯ ● ―

● ● ●⑨ ● ―

● ● ●⑨ ● ―

● ● ●⑯ ● ―

● ● ●⑩ ● ―

● ● ●⑩ ● ―

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Adj. thermal, fixed magnetic Grey Yes (Red) Yes Yes Yes

Notes: ' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. ① : Connect 3poles or 4poles in series. ② : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 5ms for short circuit ≦ 10KA less than 10ms for short circuit ≦ 20KA less than 15ms for short circuit > 20KA ⑨ : For front connection, both line and load side interpole barriers are supplied as standard. For rear connection, line side interpole barriers are supplied as standard. ⑩ : For front connection, 5pcs line side interpole barriers and 3pcs load side interpole barriers are supplied as standard. For rear connection, 5pcs line side interpole barriers are supplied as standard. ⑯ : For front connection and rear connection, 2pcs line side interpole barriers are supplied as standard.

2-6


Switch-disconnectors for DC600V-1000V Frame size (A) Type Number of poles ■Ratings Rated current, A

Rated insulation voltage〔Ui〕 V Rated operational voltage V Rated short circuit making capacity, kA Rated short time withstand current, kA Rated impulse withstand voltage 〔U imp〕 kV ■Performance Utilization category ①② JIS C 8201-3 IEC 60947-3 ■External dimensions, mm d

a

DC

a b c d

Exterior

Interior

Weight (' marked standard type) kg ■Connections and Mountings Front-connected (FC) Terminal screws With extension bars Rear-connected (RC) Flat bar studs Plug-in (PM) For switchboards For distribution boards Draw-out type (DR) TemPlug70 (PG) TemPlug45B (PG4) DIN rail mount Clip-in chassis mount ■Accessories (optional) Symbol Auxiliary switch AX Alarm switch AL Shunt trips SH Undervoltage trips UV Motor operator MC External operating Breaker-mounted HB handle Door-mounted (variable depth) HP Toggle extension HA Mechanical interlock Slide type MS Rear-connected type MB Link type ML Wire type MW Toggle holder HH Toggle lock HL Terminal cover For front-connected CF For rear-connected and plug-in CR Interpole barrier BA Terminal block for lead TF Door flange DF ■Standard specifications Colour of cover Trip button (Colour) Handle position indication (ON: Red, OFF: Green) Suitability for isolation Reverse connection

160

160

250

250

250

S160-SDN

PVS160-SNL

PVS160-SNH

S250-SDN

PVS250-SNL

PVS250-SNH

3

4

4

3

4

4

160

160

160

250

250

250

690 600 2 2(0.3sec.) 8

800 800 3 3(0.3sec.) 8

1000 1000 3 3(0.3sec.) 8

800 600 3 3(0.3sec.) 8

800 800 3 3(0.3sec.) 8

1000 1000 3 3(0.3sec.) 8

DC-22A

DC-22A

DC-22A

DC-22A

DC-22A

DC-22A

75 130 68 95 0.8

140 165+55×2 ⑰ 68 95 1.9

140 165+55×2 ⑰ 68 95 1.9

105 165 68 95 1.5

140 165+55×2 ⑰ 68 95 1.9

140 165+55×2 ⑰ 68 95 1.9

' ○(BAR) ○ ― ― ― ― ― ○⑪ ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

● ● ● ● ― ● ● ― ● ― ― ― ● ● ●⑫ ●⑫ ●⑬ ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑫ ●⑫ ●⑬ ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

● ● ● ● ● ● ● ― ● ― ● ● ● ● ●⑧ ●⑧ ― ● ●

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes ⑱

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes ⑱

2 Ratings and Specifications

b

c

DC

160

Notes: ' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. ① : Connect 3poles or 4poles in series. ② : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 5ms for short circuit ≦ 10KA less than 10ms for short circuit ≦ 20KA less than 15ms for short circuit > 20KA ⑧ : Both line and load side terminal covers are supplied as standard. ⑪ : Provided with DIN rail adaptor. ⑫ : Line side terminal cover is supplied as standard at any voltage. ⑬ : Possible to fit on load side (option). ⑰ : + means the dimension of the terminal cover. See outline dimensions for details. ⑱ : Two breakers are available, for ordlnary connection or for reverse connection. Please specify either.

2-7


Switch-disconnectors for DC600V-1000V Frame size (A) Type Number of poles ■Ratings Rated current, A

Rated insulation voltage〔Ui〕 V Rated operational voltage V Rated short circuit making capacity, kA Rated short time withstand current, kA Rated impulse withstand voltage 〔U imp〕 kV ■Performance Utilization category ①② JIS C 8201-3 IEC 60947-3 ■External dimensions, mm d

a

b

c

DC

DC

a b c d

Exterior

Interior

Weight (' marked standard type) kg ■Connections and Mountings Front-connected (FC) Terminal screws With extension bars Rear-connected (RC) Flat bar studs Plug-in (PM) For switchboards For distribution boards Draw-out type (DR) TemPlug70 (PG) TemPlug45B (PG4) DIN rail mount Clip-in chassis mount ■Accessories (optional) Symbol Auxiliary switch AX Alarm switch AL Shunt trips SH Undervoltage trips UV Motor operator MC External operating Breaker-mounted HB handle Door-mounted (variable depth) HP Toggle extension HA Mechanical interlock Slide type MS Rear-connected type MB Link type ML Wire type MW Toggle holder HH Toggle lock HL Terminal cover For front-connected CF For rear-connected and plug-in CR Interpole barrier BA Terminal block for lead TF Door flange DF ■Standard specifications Colour of cover Trip button (Colour) Handle position indication (ON: Red, OFF: Green) Suitability for isolation Reverse connection

400

400

800

800

PVS400-NNL

PVS400-NNH

PVS800-NNL

PVS800-NNH

4

4

4

4

400

400

630 800

630 800

1150 800 9 5(0.3sec.) 8

1150 1000 9 5(0.3sec.) 8

1150 800 17 10(0.3sec.) 8

1150 1000 17 10(0.3sec.) 8

DC-22A

DC-22A

DC-22A

DC-22A

185 260 103 145 5.6

185 260 103 145 5.6

280 273 103 145 11.5

280 273 103 145 11.5

' ○(BAR) ○ ― ― ― ― ― ― ―

' ○(BAR) ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

― ' ○ ― ― ― ― ― ― ―

● ● ● ● ● ● ● ― ― ― ― ●

● ● ● ● ● ● ● ― ― ― ― ●

● ● ● ● ● ● ● ● ― ― ― ●

● ● ● ● ● ● ● ● ― ― ― ●

● ● ●⑨ ● ―

● ● ●⑨ ● ―

● ● ●⑩ ● ―

● ● ●⑩ ● ―

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes Yes

Grey Yes (Red) Yes Yes Yes

Notes: ' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”. ① : Connect 4poles in series. ② : The time constant (L/R) of the circuit should be,

less than 2.0ms nearby rated current less than 5ms for short circuit ≦ 10KA less than 10ms for short circuit ≦ 20KA less than 15ms for short circuit > 20KA ⑨ : For front connection, both line and load side interpole barriers are supplied as standard. For rear connection, line side interpole barriers are supplied as standard. ⑩ : For front connection, 5pcs line side interpole barriers and 3pcs load side interpole barriers are supplied as standard. For rear connection, 5pcs line side interpole barriers are supplied as standard.

2-8


3

Characteristics 3 Characteristics

Time/Current characteristic curves, Ambient Compensating Curves S160-SD, S160-GD, S250-SD, S250-GD 3P ……………………………3-2 S400-ND, S800-ND 3P ……………………………………………………3-3 S1000-ND 2P, 3P ……………………………………………………………3-3 XS1250ND, XS1600ND, XS2000ND 2P, 3P ……………………………3-4 XS2500ND, XS3200ND 2P, 3P ……………………………………………3-5 PVS160-SDL, PVS250-SDL 3P, 4P ………………………………………3-6 PVS160-SDH, PVS250-SDH 4P …………………………………………3-6 PVS400-NDL 3P ……………………………………………………………3-6 PVS400-NDL, PVS400-NDH, PVS800-NDH 4P …………………………3-7 PVS800-NDL 3P, 4P ………………………………………………………3-7

3-1


Time/Current characteristic curves, Ambient Compensating Curves Type

Time/Current characteristic curves, Ambient Compensating Curves

3 2

140

1 40 30 20

125A

Percent current rating

minute

hour

S160-SD 3P S160-GD 3P

10 6 4 2

Tripping Time

1 40 30 20

Max.

10 6 4

Calibrated temperature

25A

100A

40A

120

80A 110

63A 160A

100

32A

90

2 second

130

Min.

1 0.6 0.4

calibrated at 45°C

25A

160A

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04

Rated current (A) Magnetic trip current (A) 25 750 32 750 40 750 63 1220 80 1220 100 1940 125 1940 160 2070 Notes : Setting current ±20%

0.02

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

100 125

0.01 0.005

Percent Rated Current

hour minute

0.1 0.06 0.04

0.02

0.02

8000

3000 4000 5000

1500 2000

700

0.005

1000

0.01

0.005

300 400 500

0.01

Percent Rated Current

8000

0.2

0.1 0.06 0.04

3000 4000 5000

1 0.6 0.4

0.2

200

250A(Min)

2 second

1 0.6 0.4

100 125

second

2 100-200A(Min)

10 6 4

300 400 500

10 6 4

250A(Max)

1 40 30 20

200

Tripping Time

2

100-200A(Max)

1 40 30 20

10 6 4

100 125

2

1 40 30 20

1500 2000

10 6 4

3 2

700

1 40 30 20

1000

3 2

Tripping Time

minute

hour

S250-SD 3P S250-GD 3P

Percent Rated Current

Rated current (A) Magnetic trip current (A) 100 1300 125 1625 160 2080 200 2600 250 2750 Notes : Setting tolerance ±20%

Percent current rating

140

Calibrated temperature

130

200A,250A 120

110 100

125A,160A 100A

90 calibrated at 45°C

5

15

25

35

45

Ambient temperature (°C)

3-2

55


Time/Current characteristic curves, Ambient Compensating Curves Time/Current characteristic curves, Ambient Compensating Curves

minute

hour

S400-ND 3P

3 2

140

Calibrated temperature

1 40 30 20

Percent current rating

Type

10 6 4 2

Tripping Time

1 40 30 20

120

400A

110 100 250A

10 6 4

90

2

second

130

calibrated at 45°C

1 0.6 0.4

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

0.005

100 125

0.01

Rated current (A) Magnetic trip current (A) 250 3000 400 4800 Notes : Setting tolerance ±20%

3

Percent Rated Current

140

1 40 30 20

Calibrated temperature

130

Percent current rating

hour minute

3 2

10 6 4 2 1 40 30 20

Tripping Time

Characteristics

S800-ND 3P

10 6 4

120

800A

110 630A 100 90

second

2

calibrated at 45°C

1 0.6 0.4

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

100 125

0.01 0.005

Percent Rated Current

3 2

140

1 40 30 20 10 6 4

Max.

2

Tripping Time

1 40 30 20 Min.

10 6 4

120 110 100 90

2

calibrated at 45°C

1 0.6 0.4

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

Percent Rated Current

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

0.01 0.005

100 125

second

Calibrated temperature

130

Percent current rating

minute

hour

S1000-ND 2P, 3P

Rated current (A) Magnetic trip current (A) 630 6300 800 8000 Notes : Setting tolerance ±20%

Rated current (A) Magnetic trip current (A) 1000 8000 Notes : Setting tolerance ±20%

3-3


Time/Current characteristic curves, Ambient Compensating Curves Type

Time/Current characteristic curves, Ambient Compensating Curves hour

XS1250ND 2P, 3P

3 2 1 40

minute

20 10 6 4 2

Tripping Time

1 40 20 10

Setting tolerance 6 (Scale4) 4

Setting tolerance (Scale8)

second

2 1

Adjustable setting range of magnetic trip. Five stages within this range.

0.6 0.4 0.2

Rated current (A) Scale 1250

0.1 0.06 0.04

Magnetic trip current (A) 8 7.1 6.3 8000 7100 6300

5 5000

4 4000

Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.

0.02

30000

20000

8000

10000

5000 6000

3000

2000

1000 1250

0.01 0.006

Note: Magnetic trip only. Use the external over-current relay.

Rated Current (A)

hour

XS1600ND 2P, 3P

3 2 1 40

minute

20 10 6 4 2

Tripping Time

1 40 20 10

Setting tolerance 6 (Scale4) 4

Setting tolerance (Scale8)

second

2 1

Adjustable setting range of magnetic trip. Five stages within this range.

0.6 0.4 0.2

Rated current (A) Scale 1600

0.1 0.06 0.04

Magnetic trip current (A) 8 7.1 6.3 8000 7100 6300

5 5000

4 4000

Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.

0.02

30000

20000

10000

8000

5000 6000

3000

2000

0.006

1000 1250

0.01

Note: Magnetic trip only. Use the external over-current relay.

Rated Current (A)

hour

XS2000ND 2P, 3P

3 2 1 40

minute

20 10 6 4 2

Tripping Time

1 40 20 10

Setting tolerance 6 (Scale4) 4

Setting tolerance (Scale8)

second

2 1

Adjustable setting range of magnetic trip. Five stages within this range.

0.6 0.4 0.2

Rated current (A) Scale 2000

0.1 0.06 0.04

Magnetic trip current (A) 8 7.1 6.3 8000 7100 6300

5 5000

Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.

0.02

Rated Current (A)

3-4

30000

20000

10000

8000

5000 6000

3000

2000

1000 1250

0.01 0.006

4 4000

Note: Magnetic trip only. Use the external over-current relay.


Time/Current characteristic curves, Ambient Compensating Curves Type

Time/Current characteristic curves, Ambient Compensating Curves hour

XS2500ND 2P, 3P

3 2 1 40

minute

20 10 6 4 2

Tripping Time

1 40 20 10

Setting tolerance 6 (Scale4) 4

Setting tolerance (Scale8)

second

2 1

Adjustable setting range of magnetic trip. Five stages within this range.

0.6 0.4 0.2

Rated current (A) Scale 2500

0.1 0.06 0.04

Magnetic trip current (A) 8 7.1 6.3 8000 7100 6300

5 5000

4 4000

Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.

0.02

Note: Magnetic trip only. Use the external over-current relay.

Rated Current (A)

hour

Characteristics

XS3200ND 2P, 3P

3 2 1 40

minute

20 10 6 4 2 1 40

Tripping Time

3

30000

20000

8000

10000

5000 6000

3000

2000

1000 1250

0.01 0.006

20 10

Setting tolerance (Scale6)

6 4

Setting tolerance (Scale12)

1

Adjustable setting range of magnetic trip. Five stages within this range.

0.6 0.4 0.2

Rated current (A) Scale 3200

0.1 0.06 0.04

Magnetic trip current (A) 12 11 10 12000 11000 10000

8 8000

6 6000

Notes : Setting tolerance ±10% at 12000A and ±25% for other settings.

0.02

Rated Current (A)

30000

20000

10000

8000

5000 6000

3000

0.006

2000

0.01 1000 1250

second

2

Note: Magnetic trip only. Use the external over-current relay.

3-5


Time/Current characteristic curves, Ambient Compensating Curves Time/Current characteristic curves, Ambient Compensating Curves

hour

0.2

0.1 0.06 0.04

0.1 0.06 0.04

0.02

0.02

8000

3000 4000 5000

1500 2000

700

0.005

1000

0.01

0.005

300 400 500

0.01

Percent Rated Current

Percent Rated Current

PVS160-SDL, PVS160-SDH Rated current (A) Magnetic trip current (A) 50 650 63 819 100 1300 125 1625 160 2080 Notes : Setting tolerance ±20%

140

Percent current rating

50A

PVS250-SDL, PVS250-SDH Rated current (A) Magnetic trip current (A) 100 1300 125 1625 160 2080 200 2600 250 2750 Notes : Setting tolerance ±20%

3 2

200A,250A

120

110

100A 100

125A,160A

5

15

25

35

45

55

140

Calibrated temperature

1 40 30 20 10 6 4

1 40 30 20

Tripping Time

63A

Ambient temperature (°C)

2

130 120

400A

110 100 250A

10 6 4

90

2

second

Calibrated temperature

130

90 calibrated at 45°C

Percent current rating

minute

hour

PVS400-NDL 3P

8000

second

1 0.6 0.4

0.2

200

250A(Min)

2

3000 4000 5000

50-200A(Min)

1 0.6 0.4

100 125

second

2

10 6 4

300 400 500

10 6 4

250A(Max)

1 40 30 20

200

Tripping Time

2

50-200A(Max)

100 125

2 1 40 30 20

10 6 4

1500 2000

10 6 4

1 40 30 20

700

1 40 30 20

3 2

1000

3 2

minute

minute

hour

PVS160-SDL 3P, 4P PVS160-SDH 4P PVS250-SDL 3P, 4P PVS250-SDH 4P

Tripping Time

Type

calibrated at 45°C

1 0.6 0.4

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

Percent Rated Current

3-6

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

100 125

0.01 0.005

Rated current (A) Magnetic trip current (A) 250 2000 400 3200 Notes : Setting tolerance ±20%


Time/Current characteristic curves, Ambient Compensating Curves Time/Current characteristic curves, Ambient Compensating Curves

minute

hour

PVS400-NDL 4P

3 2

140

Calibrated temperature

1 40 30 20

Percent current rating

Type

10 6 4 2

Tripping Time

1 40 30 20

120

400A

110 100 250A

10 6 4

90

2

second

130

calibrated at 45°C

1 0.6 0.4

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

100 125

0.01 0.005

Percent Rated Current

140

Calibrated temperature

1 40 30 20

Percent current rating

hour minute

3 2

10 6 4 2

Tripping Time

1 40 30 20

400A

110 100 250A

10 6 4

90

2

second

130 120

3 Characteristics

PVS400-NDH 4P

Rated current (A) Magnetic trip current (A) 250 3000 400 4800 Notes : Setting tolerance ±20%

calibrated at 45°C

1 0.6 0.4

5

15

25

35

45

55

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

100 125

0.01 0.005

Percent Rated Current

3 2

140

1 40 30 20 10 6 4 2 1 40 30 20

Tripping Time

Calibrated temperature

130

Percent current rating

minute

hour

PVS800-NDL 3P, 4P PVS800-NDH 4P

Rated current (A) Magnetic trip current (A) 250 2000 400 3200 Notes : Setting tolerance ±20%

10 6 4

120

800A

110 630A 100 90

calibrated at 45°C

1 0.6 0.4

800A

5

15

25

35

45

55

630A

Ambient temperature (°C)

0.2 0.1 0.06 0.04 0.02

Percent Rated Current

8000

3000 4000 5000

1500 2000

700

1000

300 400 500

200

0.01 0.005

100 125

second

2

Rated current (A) Magnetic trip current (A) 630 3500 800 3500 Notes : Setting tolerance ±20%

3-7


4

Mounting and Connection 4 Mounting and Connection

Connection of conductors to DC circuit breakers…………………………4-2 Insulation distance DC600V or less …………………………………………4-7 Insulation distance DC750V-1000V PVS160-SDL 3P, PVS250-SDL 3P …………………………………………4-8 PVS160-SDL 4P, PVS250-SDL 4P, PVS160-SNL 4P, PVS250-SNL 4P ………………………………4-9 PVS160-SDH 4P, PVS250-SDH 4P, PVS160-SNH 4P, PVS250-SNH 4P ……………………………4-10 PVS400-NDL 3P………………………………………………………………4-11 PVS400-NDL 4P, PVS400-NDH 4P ………………………………………4-12 PVS400-NNL 4P, PVS400-NNH 4P ………………………………………4-13 PVS800-NDL 3P………………………………………………………………4-14 PVS800-NDL 4P, PVS800-NDH 4P ………………………………………4-15 PVS800-NNL 4P, PVS800-NNH 4P ………………………………………4-16

4-1


Connection of conductors to DC circuit breakers It is more difficult to interrupt DC current than AC current because DC current does not have a zero point. Therefore for high DC voltages, 3-pole or 4-pole circuit breaker main contacts are connected in series to ensure breaking performance. As illustrated below, the main power conductors for DC-use air circuit breakers, moulded case circuit breakers, and switch disconnectors shall be connected generally as shown below but also depending on the type of breaker, the number of poles, and the DC operating voltage. Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Grounded system (Protection + Isolation function)

Source

Source

Source

Ordinally connection Load

Load

Load

Load

Load

Load

Reverse connection

Source

Source Source

Type of breakers

S1000-ND

No.s of poles

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

2P

≦250

50kA/20kA

≦250

50kA/20kA

≦150

50kA/20kA

✽:2 poles breaker is a 3 pole breaker with the center pole omitted.

Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Grounded system (Protection + Isolation function)

Source

Source

Source

Ordinally connection

Type of breakers

XS1250ND

No.s of poles

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

2P

≦250

50kA/30kA

≦250

50kA/30kA

≦150

50kA/30kA

XS1600ND

2P

≦250

50kA/30kA

≦250

50kA/30kA

≦150

50kA/30kA

XS2000ND

2P

≦250

50kA/30kA

≦250

50kA/30kA

≦150

50kA/30kA

XS2500ND

2P

≦250

50kA/30kA

≦250

50kA/30kA

≦150

50kA/30kA

XS3200ND

2P

≦250

50kA/30kA

≦250

50kA/30kA

≦150

50kA/30kA

✽:2 poles breaker is a 3 pole breaker with the center pole omitted.

4-2

Load

Load

Load


Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Source

Grounded system (Protection + Isolation function)

Source

Source

Ordinally connection Load

Load

Load

Load

Load

Load

Reverse connection

Source

4

Source Source

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

≦600

5kA/5kA

≦500

7.5kA/7.5kA

≦600

5kA/5kA

≦400

5kA/5kA

≦500

7.5kA/7.5kA

≦350

7.5kA/7.5kA

≦350

10kA/10kA

≦600

10kA/5kA

≦350

10kA/10kA

≦250

10kA/10kA

≦600

10kA/5kA

≦400

10kA/5kA

3P

≦500

15kA/7.5kA

≦500

15kA/7.5kA

≦350

15kA/7.5kA

S250-SD

3P

S250-SD

3P

≦600

5kA/5kA

≦600

5kA/5kA

≦400

5kA/5kA

≦500

7.5kA/7.5kA

≦500

7.5kA/7.5kA

≦350

7.5kA/7.5kA

S250-SD S250-GD

3P

≦350

10kA/10kA

≦350

10kA/10kA

≦250

10kA/10kA

3P

≦600

10kA/5kA

≦600

10kA/5kA

≦400

10kA/5kA

S250-GD

3P

≦500

15kA/7.5kA

≦500

15kA/7.5kA

≦350

15kA/7.5kA

S400-ND

3P

≦600

15kA/15kA

≦600

15kA/15kA

≦400

15kA/15kA

S400-ND

3P

≦350

20kA/20kA

≦350

20kA/20kA

≦250

20kA/20kA

S800-ND

3P

≦600

20kA/10kA

≦600

20kA/10kA

≦400

20kA/10kA

S800-ND

3P

≦350

30kA/15kA

≦350

30kA/15kA

≦250

30kA/15kA

S1000-ND

3P

≦600

20kA/10kA

≦600

20kA/10kA

≦400

20kA/10kA

S1000-ND

3P

≦350

30kA/15kA

≦350

30kA/15kA

≦250

30kA/15kA

PVS160-SDL ①

3P

≦750

5kA/5kA

≦750

5kA/5kA

≦500

5kA/5kA

PVS250-SDL ①

3P

≦750

5kA/5kA

≦750

5kA/5kA

≦500

5kA/5kA

PVS400-NDL

3P

≦750

10kA/5kA

≦750

10kA/5kA

≦500

10kA/5kA

PVS800-NDL

3P

≦750

10kA/10kA

≦750

10kA/10kA

≦500

10kA/10kA

S160-SDN

3P

≦600

≦600

≦400

S250-SDN

3P

≦600

≦600

≦400

Applicable voltage (V)

S160-SD

3P

S160-SD

3P

S160-SD

3P

S160-GD

3P

S160-GD

Rated breaking capacity Icu/Ics

Mounting and Connection

Rated breaking capacity Icu/Ics

No.s of poles

Type of breakers

Note ①:Two breakers are available for ordlnary connection and for reverse connection. Use the ordinally connected breakers for ordinal connection and the reverse connected breakers for reverse connection. Do not use contrary.

4-3


Connection of conductors to DC circuit breakers

Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Source

Grounded system (Protection + Isolation function)

Source

Source

Ordinally connection Load

Type of breakers

4-4

No.s of poles

Applicable voltage (V)

Load

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Load

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

XS1250ND

3P

≦600

20kA/15kA

≦600

20kA/15kA

≦400

20kA/15kA

XS1250ND

3P

≦500

50kA/25kA

≦500

50kA/25kA

≦350

50kA/25kA

XS1600ND

3P

≦600

20kA/15kA

≦600

20kA/15kA

≦400

20kA/15kA

XS1600ND

3P

≦500

50kA/25kA

≦500

50kA/25kA

≦350

50kA/25kA

XS2000ND

3P

≦600

20kA/15kA

≦600

20kA/15kA

≦400

20kA/15kA

XS2000ND

3P

≦500

50kA/25kA

≦500

50kA/25kA

≦350

50kA/25kA

XS2500ND

3P

≦600

20kA/15kA

≦600

20kA/15kA

≦400

20kA/15kA

XS2500ND

3P

≦500

50kA/25kA

≦500

50kA/25kA

≦350

50kA/25kA

XS3200ND

3P

≦600

20kA/15kA

≦600

20kA/15kA

≦400

20kA/15kA

XS3200ND

3P

≦500

50kA/25kA

≦500

50kA/25kA

≦350

50kA/25kA


Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Grounded system (Protection + Isolation function)

Source

Source

Source

Ordinally connection Load

Load

Load

Load

Load

Load

Reverse connection

4

Source

Source Source

No.s of poles

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

PVS160-SDL

4P

≦750

10kA/5kA

≦750

10kA/5kA

≦550

10kA/5kA

PVS250-SDL

4P

≦750

10kA/5kA

≦750

10kA/5kA

≦550

10kA/5kA

PVS160-SDH

4P

≦1000

5kA/5kA

≦1000

5kA/5kA

≦750

5kA/5kA

PVS250-SDH

4P

≦1000

5kA/5kA

≦1000

5kA/5kA

≦750

5kA/5kA

PVS400-NDL

4P

≦750

10kA/10kA

≦750

10kA/10kA

≦750

10kA/10kA ②

PVS400-NDH

4P

≦1000

5kA/5kA

≦1000

5kA/5kA

PVS800-NDL

4P

≦750

10kA/10kA

≦750

10kA/10kA

≦750

10kA/10kA

PVS800-NDH

4P

≦1000

5kA/5kA

≦1000

5kA/5kA

≦750

5kA/5kA

PVS160-SNL

4P

≦800

≦800

≦600

PVS250-SNL

4P

≦800

≦800

≦600

PVS160-SNH

4P

≦1000

≦1000

≦750

PVS250-SNH

4P

≦1000

≦1000

≦750

PVS400-NNL

4P

≦800

≦800

≦750

PVS400-NNH

4P

≦1000

≦1000

PVS800-NNL

4P

≦800

≦800

≦750

PVS800-NNH

4P

≦1000

≦1000

Mounting and Connection

Type of breakers

Note ②:The breaking capacity goes down to Icu10kA / Ics5kA for ground fault protection.

4-5


Connection of conductors to DC circuit breakers Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Source

Grounded system (Protection + Isolation function)

Source

Source

Ordinally connection Load

Load

Load

Load

Load

Load

Reverse connection

Source

Source Source

No.s of poles

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

AR216S ③

3P

≦600

40kA/40kA

≦600

40kA/40kA

≦400

40kA/40kA

AR220S ③

3P

≦600

40kA/40kA

≦600

40kA/40kA

≦400

40kA/40kA

AR325S ③

3P

≦600

40kA/40kA

≦600

40kA/40kA

≦400

40kA/40kA

AR332S ③

3P

≦600

40kA/40kA

≦600

40kA/40kA

≦400

40kA/40kA

AR440S ③

3P

≦600

40kA/40kA

≦600

40kA/40kA

≦400

40kA/40kA

Type of breakers

Note ③:AGR over-current release can not be used for DC. Please prepare DC over-current relay and connect with shunt trip device.

Non-grounded system (Protection + Isolation function)

Grounded system (Protection)

Grounded system (Protection + Isolation function)

Source

Source

Source

Ordinally connection Load

Load

Load

Load

Load

Load

Reverse connection Source Source Source

Type of breakers

AR325-NDH ③

No.s of poles

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

Applicable voltage (V)

Rated breaking capacity Icu/Ics

4P

≦800

30kA/30kA

≦800

30kA/30kA

≦600

30kA/30kA

Note ③:AGR over-current release can not be used for DC. Please prepare DC over-current relay and connect with shunt trip device.

4-6


Insulation distance DC600V or less The insulation distances between the breaker and earthed metal parts and insulators shown in the table below must be maintained to prevent arcing faults occurring due to conductive ionised gas. In addition, any exposed line-side conductors must be completely covered, right up the breaker casing or to below the height protected by any interpole barriers. This can done by using an insulation tube or tape, in order to provide positive protection against short circuit or ground fault due to metal chipping, surge voltage, dust particles or salt. If terminal covers are not being used, the interpole barriers supplied with the breaker as standard must be used. Insulating tube or tape

Sheathed wire

Interpole barrier Exposed conductor

Interpole barrier Compression terminal

Line side

Load side Interpole barrier

Top plate (earthed metal)

Insulation plate

(Insulation tube or tape is also acceptable)

Side plate B1

B1 B2

B1 B2

4

E B2

D A Insulation tube

or tape

Front connection, terminal screw

Front connection, extension bar

Rear connection, Plug-in

C

A . Distance from lower breaker to exposed live part of upper breaker terminal (front connection) or distance from lower breaker to end face of upper breaker (rear connection). B1. Distance from end face of breaker to top plate. B2. Distance from end face of breaker to insulation plate. C . Gap between breakers. D . Distance from side of breaker to side plate (earthed metal). E . Dimension of insulation over exposed conductors.

Mounting and Connection

A A

Insulation distance, mm (DC 600 V or less) Note ① Moulded Case Circuit Breakers

A Note ②

B1

B2

C

D

S160-SD

S160-GD

S160-SDN

50

50

50

Possible to set close Note ③

25

Not less than the length of the bare live part Note ④

S250-SD S400-ND XS1250ND

S250-GD S800-ND XS1600ND

S250-SDN S1000-ND XS2000ND

65 150 150

65 120 150

65 80 100

〃 〃 〃

50 80 100

〃 〃 〃

XS2500ND

XS3200ND

Notes: ①. Required to allow free and uninterrupted flow of arc gases. Ensure additional clearance or insulation distance if required to perform wiring, barrier installation or electrical work or to meet the need for more insulation distance between bare live parts and grounded metal members in a switchboard or the like. ②. The figures are for lower breakers. ③. When the accessories are fitted it is not possible to set close. ④. For front connected breakers, insulate all exposed conductors of the line side until the breaker end. If interpole barriers are packed, be sure to use the barriers; more over, insulate all exposed conductors by insulating tape or the like so that the tape overlaps with the barriers. ⑤. Be sure to install the terminal covers (supplied as standard) on the line side of the breakers. ✽. If using extension bars (optional), ensure the insulation distance specified for the application.

4-7


Insulation distance DC750V-1000V The insulation distances between the breaker and earthed metal parts and insulators shown in the table below must be maintained to prevent arcing faults occurring due to conductive ionised gas. In addition, any exposed line-side conductors must be completely covered, right up the breaker casing or to below the height protected by any terminal covers or interpole barriers. This can done by using an insulation tube or tape, in order to provide positive protection against short circuit or ground fault due to metal chipping, surge voltage, dust particles or salt. The terminal covers or the interpole barriers supplied with the breaker as standard must be used. For DC750V-1000V breakers, the front and the rear insulating plates must also be installed. PVS160-SDL 3P, PVS250-SDL 3P Front-connected 5

5

Terminal cover

B

Insulating plate (supplied as standard)

165

Insulating plate (supplied as standard)

Mounting plate

B

Mounting plate

Terminal cover

A

A

105

70

Rear-connected 5

5

Terminal cover

B

Insulating plate (supplied as standard)

165

Insulating plate (supplied as standard)

Mounting plate

B

Mounting plate

Terminal cover

A

A

105

70

Minimum insulation distance (mm) Type

PVS160-SDL 3P PVS250-SDL 3P

4-8

Insulating plate

Connection

Front-connected Rear-connected

A

B

50

65

Terminal caver 2pcs are supplied for line and load side as standard.

Insulating plate 2pcs of 115mmĂ—137.5mm are supplied as standard.


PVS160-SDL 4P, PVS250-SDL 4P, PVS160-SNL 4P, PVS250-SNL 4P Front-connected

165

B

Terminal cover

Mounting plate

Mounting plate

B

4

Terminal cover

A

140

A

68

165

B

Terminal cover

Mounting plate

Mounting and Connection

Rear-connected

B

Mounting plate

Terminal cover

A

140

A

68

Minimum insulation distance (mm) Type PVS160-SDL 4P PVS250-SDL 4P PVS160-SNL 4P PVS250-SNL 4P

Connection

Front-connected Rear-connected

Terminal caver

A

B

50

65

2pcs are supplied for line and load side as standard.

4-9


Insulation distance DC750V-1000V

PVS160-SDH 4P, PVS250-SDH 4P, PVS160-SNH 4P, PVS250-SNH 4P Front-connected 20

20

Terminal cover

B

Insulating plate (supplied as standard)

165

Insulating plate (supplied as standard)

Mounting plate

B

Mounting plate

Terminal cover

A

A

140

70

Rear-connected 20

20

Terminal cover

B

Insulating plate (supplied as standard)

165

Insulating plate (supplied as standard)

Mounting plate

B

Mounting plate

Terminal cover

A

A

140

70

Minimum insulation distance (mm) Type PVS160-SDH 4P PVS250-SDH 4P PVS160-SNH 4P PVS250-SNH 4P

4-10

Insulating plate

Connection

Front-connected Rear-connected

A

B

50

65

Terminal caver 2pcs are supplied for line and load side as standard.

Insulating plate 2pcs of 180mmĂ—137.5mm are supplied as standard.


PVS400-NDL 3P Front-connected

Ionised gas area

G

Interpole barrier

Insulating plate (supplied as standard)

420

260

D

E

Insulating plate

F

A

G

Mounting plate

B

4 C

105 C

140

Rear-connected

Ionised gas area

G

Interpole barrier

Insulating plate (supplied as standard)

Mounting plate

B

260

420

D

E

Insulating plate

F

A

G

Mounting and Connection

260

260 C

140

105

C

Minimum insulation distance (mm) Type

PVS400-NDL 3P

Insulating plate

Connection

Front-connected Rear-connected

A

B

C

D

E

F

G

Front panel side

Mounting plate side

160

80

80

30

140

160

60

Not supplied

Supplied as standard

4-11


Insulation distance DC750V-1000V

PVS400-NDL 4P, PVS400-NDH 4P Front-connected Front panel G

Ionised gas area

Interpole barrier

Insulating plate (supplied as standard)

D

E

A

F

G

420

Mounting plate

B

260

Insulating plate

305 C

Interpole barrier

105

C

185

Rear-connected Front panel G

Ionised gas area

Interpole barrier

Insulating plate (supplied as standard)

D

E

F

A

G

Mounting plate

B

260

420

Insulating plate

305 C

185

105

C

Minimum insulation distance (mm) Type

PVS400-NDL 4P PVS400-NDH 4P

4-12

Insulating plate

Connection

Front-connected Rear-connected

A

B

C

D

E

F

G

Front panel side

Mounting plate side

160

80

80

30

140

160

60

Not supplied

Supplied as standard


PVS400-NNL 4P, PVS400-NNH 4P Front-connected Front panel G

Ionised gas area

Interpole barrier

F

A

G

D

E

Insulating plate

260

Insulating plate

Mounting plate

B

4 185

C

Interpole barrier

Mounting and Connection

C

103

Rear-connected Front panel G

Ionised gas area

Interpole barrier

Insulating plate

D

E

F

A

G

260

Insulating plate

B

Mounting plate

C

185

C

103

Minimum insulation distance (mm) Type

PVS400-NNL 4P PVS400-NNH 4P

Insulating plate

Connection

Front-connected Rear-connected

A

B

C

D

E

F

G

Front panel side

Mounting plate side

120

80

80

30

80

80

40

Not supplied

Not supplied

4-13


Insulation distance DC750V-1000V

PVS800-NDL 3P Front-connected 330 Ionised gas area

Insulating plate (supplied as standard)

513

273

D

E

Insulating plate

F

A

Interpole barrier

B

Mounting plate

Rear-connected

G 210

105

C

330

Ionised gas area

A

Interpole barrier

Insulating plate (supplied as standard)

513

273

D

E

Insulating plate

F

G C

B

Mounting plate

G C

105

G 210

C

Minimum insulation distance (mm) Type

PVS800-NDL 3P

4-14

Insulating plate

Connection

Front-connected Rear-connected

A

B

C

D

E

F

G

Front panel side

160

80

80

80

140

160

60

Not supplied

Mounting plate side

Supplied as standard


PVS800-NDL 4P, PVS800-NDH 4P Front-connected 400

Front panel

Ionised gas area

Interpole barrier

D

E

A

F

Insulating plate (supplied as standard)

513

273

Insulating plate

Mounting plate

B

4 G

Rear-connected

105

C

280

Front panel

400

Ionised gas area

Insulating plate (supplied as standard)

D

E

F

A

Interpole barrier

513

273

Insulating plate

B

Mounting plate

Mounting and Connection

G C

105 G

G 280

C

C

Minimum insulation distance (mm) Type

PVS800-NDL 4P PVS800-NDH 4P

Insulating plate

Connection

Front-connected Rear-connected

A

B

C

D

E

F

G

Front panel side

Mounting plate side

160

80

80

80

140

160

60

Not supplied

Supplied as standard

4-15


Insulation distance DC750V-1000V

PVS800-NNL 4P, PVS800-NNH 4P Front-connected 400

Front panel G

Ionised gas area

Interpole barrier

Insulating plate

D

E

A

F

G

273

Insulating plate

B

Mounting plate

103 C

C

280

Rear-connected 400

Front panel

Ionised gas area

Interpole barrier

G

Insulating plate (supplied as standard)

D

E

F

A

G

273

Insulating plate

B

Mounting plate

103 C

280

C

Minimum insulation distance (mm) Type

PVS800-NNL 4P PVS800-NNH 4P

4-16

Insulating plate

Connection

Front-connected Rear-connected

A

B

C

D

E

F

G

Front panel side

Mounting plate side

120

80

80

80

80

80

60

Not supplied

Not supplied


5

Outline Dimensions

5 Outline Dimensions

DC Air Circuit Breakers Outline Dimensions AR216S, AR220S 3P …………………………………………………………5-2 AR325S, AR332S 3P …………………………………………………………5-4 AR325-NDH 4P…………………………………………………………………5-6 AR440SB 3P ……………………………………………………………………5-8 AR440S 3P ……………………………………………………………………5-10 DC Moulded Case Circuit Breakers Outline Dimensions S160-SD, S160-GD, S160-SDN, S250-SD, S250-GD, S250-SDN 3P …5-12 S400-ND 3P …………………………………………………………………5-13 S800-ND 3P …………………………………………………………………5-13 S1000-ND 2P, 3P ……………………………………………………………5-14 XS1250ND 2P, 3P ……………………………………………………………5-15 XS1600ND 2P, 3P ……………………………………………………………5-16 XS2000ND 2P, 3P ……………………………………………………………5-17 XS2500ND, XS3200ND 2P, 3P ……………………………………………5-18 PVS160-SDL, PVS250-SDL 3P ……………………………………………5-19 PVS160-SDL, PVS250-SDL, PVS160-SNL, PVS250-SNL 4P …………5-19 PVS160-SDH, PVS250-SDH, PVS160-SNH, PVS250-SNH 4P ………5-20 PVS400-NDL 3P………………………………………………………………5-21 PVS400-NDL, PVS400-NDH 4P ……………………………………………5-22 PVS400-NNL, PVS400-NNH 4P ……………………………………………5-22 PVS800-NDL 3P………………………………………………………………5-23 PVS800-NDL, PVS800-NDH 4P ……………………………………………5-24 PVS800-NNL, PVS800-NNH 4P ……………………………………………5-24

5-1


DC Air Circuit Breakers Outline dimensions (mm)

¡Type AR216S 3P, AR220S 3P Draw-out type Terminal size Type

t ○1

t ○2

t ○3

W

AR216S

20

15

25

22.5

AR220S

20

15

25

CP

rear panel cut

158.5

Maintenance space

158.5

500

490

329

335※2

405

460

front panel cut

CP

R

11

33

250 164

42.5

30

20

50

6

238

164 177

177

204

204

240

240

draw-out handle

For fitted with breaker fixing bolts

Maintenance space

Maintenance space

141

94

panel cut-out

Conductors including connecting bolts should be separated min-7mm from Draw-out arm. ※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ ※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

120

5-2

120

Mounting holes

4-ø14


P:ACB Front cover center line C

AR216S 3P, AR220S 3P conductor overlap. max 35

P C

35

85

15

85

t3 318 380

15

65

conductor overlap. max 35

515

Front connections

25 50 2-ø11

CONNECTED position

18

5

W

42.5 32

M8 screw earth terminal

3-ø11

7 21 29

40

140 ¶1 35

conductor overlap. max

t2

52

15 85

85

2-ø11

174

Horizontal terminals

138

265

110

25

9

141 345 385

t1

94

27

40

15.5

W

25

W

9

Vertical terminals

Outline Dimensions

14.5 14.5

25

25 25

W

2-ø11 12

85

15

15

ON-OFF button cover

85

32

21

17

149

14

15.5

ISOLATED position

Control circuit terminal cover (optional) 2-ø20 Lifting hole AR216S AR220S 35 35 conductor overlap. max 199

25 25 150.5

TEST position

385

Draw-out arm (comes out when breaker is drawn out)

5-3


DC Air Circuit Breakers Outline dimensions (mm)

¡Type AR325S 3P, AR332S 3P Draw-out type

CP

rear panel cut

211.5

Maintenance space

211.5

500

490

329

335※2

405

460

front panel cut

CP

R

11

250 216

33 60

30

20

50

6

238

216 230

230 draw-out handle

For fitted with breaker fixing bolts

panel cut-out

257

257

293

293 Maintenance space

141

94

Maintenance space

Conductors including connecting bolts should be separated min-7mm from Draw-out arm. ※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ ※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

4-ø14

172.5

5-4

172.5

Mounting holes


P:ACB Front cover center line C

35

P C 3-ø11

5

130

15

conductor overlap. max 35

AR325S 3P, AR332S 3P 130

515

Front connections

25 318

15

65

conductor overlap. max 35

83 25 25 11.5

21.5

11.5

21.5

28

10

25 25

25 25

83

88

380 CONNECTED position TEST position ISOLATED position 14

21

35

199 18

17

5 130

conductor overlap. max

130

25 25 25

100

4-ø11

120

12.5

15

54.5

32

100

M8 screw earth terminal

40

20

29 197.5 ¶1 conductor overlap. max 15

P C 5 130

80

25 25

15

35

27

7 21

110

130

15 154

30

3-ø11

385

Horizontal terminals

148

9

141 345 385

30

94

5

65

40

12.5

25 25 25

9

Vertical terminals

Outline Dimensions

12.5 12.5

12

165

ON-OFF button cover

265

P C

Control circuit terminal cover (optional) 2-ø20 Lifting hole

Draw-out arm (comes out when breaker is drawn out)

5-5


DC Air Circuit Breakers Outline dimensions (mm)

¡Type AR325-NDH 4P Draw-out type

CP

rear panel cut

211.5

Maintenance space

331.5

500

490

329

335※2

405

460

front panel cut

CP

R

11

250 216

33 60

30

20

50

6

238

336 230

350

257

377

draw-out handle For fitted with breaker fixing bolts

panel cut-out

293

413 Maintenance space

141

94

Maintenance space

Conductors including connecting bolts should be separated min-7mm from Draw-out arm. ※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ ※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

4-ø14

172.5

5-6

292.5

Mounting holes


P:ACB Front cover center line C

35

P C 3-ø11

130

15

conductor overlap. max 35

AR325-NDH 4P 5

130

130

515

Front connections

25 318

15

65

conductor overlap. max 35

83 11.5 25 25

10

28

88 21.5

28

21.5

25 25

10

11.5

25 25

25 25

88

83

380 CONNECTED position TEST position ISOLATED position 14

21

35

199 18

17

5 130

conductor overlap. max

130

130

25 25 25

100

4-ø11

120

12.5

15

54.5

32

100

M8 screw earth terminal

40 317.5

20

29 ¶1

conductor overlap. max 15

P C 5 130

80

25 25

15

35

27

7 21

110

130

130

15 154

30

3-ø11

385

Horizontal terminals

148

9

141 345 385

30

94

5

65

40

12.5

25 25 25

9

Vertical terminals

Outline Dimensions

12.5 12.5

12

165

ON-OFF button cover

265

P C

Control circuit terminal cover (optional) 2-ø20 Lifting hole

Draw-out arm (comes out when breaker is drawn out)

5-7


DC Air Circuit Breakers Outline dimensions (mm)

¡Type AR440SB 3P Draw-out type

rear panel cut front panel cut

CP

30 216

500

490

33

50

R 11 6

60

2

250

460

329

425

335 ※2

Maintenance space

211.5

211.5

P C

238 216

draw-out handle

230

230

257

257

panel cut-out For fitted with breaker fixing bolts

293

293

Maintenance space

141

94

Maintenance space

4-ø14 172.5

172.5

Mounting holes

※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

5-8


P:ACB Front cover center line C

AR440SB 3P

Control circuit terminal cover(optional)

CONNECTED position TEST position

P C 5

21

160

4-ø11 17.5 35 35 35

ON-OFF button cover

12

110

141

90

20

94

140

51

185

80

9

17.5

289

17

Front panel

211 160

18

ISOLATED position 14

48 conductor overlap. max

2-ø20 Lifting hole

22

M8 screw earth terminal (only right side)

Rear panel

29

5 29

15 422

265

65

345 485

20 L-Angle Steel to prevent ACB to fall down (Mounting holes not required)

Outline Dimensions

9

5-9


DC Air Circuit Breakers Outline dimensions (mm)

¡Type AR440S 3P Draw-out type

rear panel cut

P C

front panel cut

Maintenance space

435.5

42.5 250 164

500

490

238 441 For fitted with breaker fixing bolts Maintenance space

177 204 240

panel cut-out

Conductors including connecting bolts should be separated min-7mm from Draw-out arm. ※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ ※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

5-10

460

329 33

R1

50

405 20

16

335 ※2 30

P C

454

draw-out handle

481 517

Maintenance space


P:ACB Front cover center line C

42.5

AR440S 3P

181

P C

CONNECTED position

15

181

Control circuit terminal cover

50

TEST position

2-ø20 Lifting hole

199 ON-OFF button cover

P C

40 conductor overlap. max 417

18

20

25

42.5

40

100

165

120

25

12.5 12.5 12.5

17

25 25 25

12

100

25

12.5

4-ø11

M8 screw earth terminal

Front panel

32

21

5

27

14

15

ISOLATED position

7

295

35

428 94

141

193

397

4-ø14

Rear panel

¶1 Draw-out arm (comes out when breaker is drawn out)

Outline Dimensions

29

375

9

120

P C

5-11


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

S160-SD 3P, S160-GD 3P, S160-SDN 3P

Outline dimensions (mm)

16.5(max.) max.t5

66 61 60.3

With extension bars ✽ (optional)

14(max.) max.t5

Drilling plan (front view)

3P HL 25 25

28 4 3P HL

M5 0.8 screw (25-40A) M8 screw (63-160A)

50

Mounting hole

ø5 ø9 .5(2 (63 5-4 -16 0A 0A ) )

9(max.)

Terminal cover

3P HL

ø5 ø9 .5(2 (63 5-4 -16 0A 0A ) )

Preparation of conductor

6.5(max.)

Front-connected

C L

36.5

25

17

M4 0.7 Tapped hole

✽ Straight bars only. For line side, use with the terminal cover.

Drilling plan (front view) E

Panel cutout (front view)

DC

D

3P

3P HL

Mounting plate (max. t3.2)

HL 37.5

3P HL

52

95

Rated current (A) 25-40 63-160

Studs are horizontal direction only

102

A 10.5 12.5

B 6.5 8.5

C 4 4

D 13 13

102

52

25 50

25 25

77

F 4 5

E 16 16

Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.

S250-SD 3P, S250-GD 3P, S250-SDN 3P With extension bars ✽ (optional)

Preparation of conductor Terminal cover

65.5 Terminal cover

3P Conductor overlap, max

HL Mounting hole

23

35

35

4

28

3P HL

19

55

25(max.) max.t7 M8 screw

Drilling plan (front view)

30.5

3P

11(max.)

ø9

11.5

Front-connected

Mounting hole

38.5

M4✕0.7 Tapped hole

Outline dimensions (mm)

HL

C L

ø20

75 68

48

C L

M4✕0.7 Mounting screw

22

111 114

7.7

114

C L

102 45

130

F

Terminal cover

A

C

66 57 56

Terminal cover 5.3

A B

Detail of connecting part

ø8.3

B

10.5

Rear-connected

7.7

52 68 95

8.5

50 75

3P HL

C L

M4✕0.7 Mounting screw

22

Mounting hole

C L

111

C L

45

114 130

102

24 C L

22

70 105

46 60 68

✽ Straight bars only. For line side, use with the terminal cover.

Drilling plan (front view)

Terminal cover

3P 65.5

Mounting plate (max. t3.2)

ø24

HL

Panel cutout (front view)

3P

3P

HL

H 52.5 L

48

126 144

C L

C L

ø9

9

20

22

7

Conductor overlap, max 25 22

C L

144

C L

45

6

Terminal cover

102

HL

5.3

3P

M4✕0.7 Tapped hole

35 ø11

Detail of connecting part

165

Mounting hole

C L

22

7

10.5 95

Rear-connected

C L

126

C L M4✕0.7 Mounting screw

45

C L

165

102 45

144 165

24 C L

105 60 68

5-12

6 13 72 107

16

Stud can be turned 45° or 90°

35

35

M4✕0.7 Mounting screw

35 35

35

M4✕0.7 Tapped hole

53.5 107

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.


ASL : Arrangement Standard Line H L : Handle Frame Centre Line CL : Handle Centre Line

S400-ND 3P

Outline dimensions (mm)

ø11 12 (max.)

M10 screw

3P HL

CL M6 Mounting screw

CL

Trip button (red)

85.3 14.7 97 103 4 107 127.5 145 (With handle cap)

90 140

CL

Drilling plan (front view)

110 39

45

15

30 3

118 M6 Tapped hole

90

6

Conductor overlap max.

30 45 45

CL

ø3

Conductor 70 overlap max. 39 ø1 3 15

228 260

CL

92

214 228

103

8

3P CL

R6

102 90

Panel cutout (front view)

3P HL

HL

ø1

97 103 4 107 127.5 145

M6 Tapped hole

45 8 35

Rear-connected Stud can be turned 45° or 90° Mounting plate

214

260 349

CL

51

CL

8 36

44.5

102 90

228 260

CL

30 (max.)

Drilling plan (front view)

max. t10

116

Mounting hole

44.5 30 14.5

110

On side 36 Off side 35

148 120 HL 28

4

Interpole barrier (removable)

With extension bars (optional)

ø1

Preparation of conductor HL

30 14.5 44.5

Front-connected

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

Note: Studs are factory installed in horizontal direction both on the line and load sides.

S800-ND 3P

Outline dimensions (mm)

5

Front-connected Drilling plan (front view) 3

ø1

51

40 140 210

t1 L1

3P

126

HL

ASL

ASL 28 13

M8 Mounting screw

80

ASL

Trip button (red)

15 32 25 8

90 46.5 55.5 141 132 273

170

80

13

Mounting hole

Toggle extension (removable)

Conductor overlap, max

4 80.5

Rear-connected

t2 L2 103 107 127.5 145

Rated Current (A) 630 800

L1 32 32

Drilling plan (front view) ø15 for accessory wiring when necessary

3P

t2 8 10

Panel cutout (front view) 3P HL

8

3P HL

t1 8 10

ø4

Stud can be turned 90°

L2 34 35

HL

4 80.5

70

70

ASL

M8 Tapped hole

126

ASL

R6

20

117

M8 Mounting screw

ø13

42

28 13

103 107 127.5 145

32 25 8 122

ASL

30.5

126

13

117

103

10

Toggle extension (removable)

M8 Tapped hole

70

92

HL

117

3P

Outline Dimensions

Interpole barrier (removable)

Conductor overlap, max

172

70 43 70

70 43

Note: Studs are factory installed in horizontal direction both on the line and load sides.

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

5-13


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

S1000-ND 2P, 3P

Outline dimensions (mm) Preparation of conductor

Mounting hole 3P

80

90 45 140 210

15 32 25 8

51

ASL 28 13

M8 Mounting screw

Conductor overlap, max

4

Rear-connected

1

172

70

12 70

70

127.5 145

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

R6

117

ASL

122

45

M8 Tapped hole

ASL M8 Tapped hole

92

30.5 126 103

126

117

13

3P HL

3P HL

8 25 32 20 Conductor overlap, max

28 13

103 107

Panel cutout (front view)

ø5

ø15 for accessory wiring 3P when necessary HL

3

ø1

5-14

14 35 103 107 127.5 145

Drilling plan (front view)

ASL

M8 Tapped hole

70

Secured in vertical position only

Toggle extension (removable)

80.5

HL

ASL

80.5

4

3P

126

170

ASL

Toggle extension (removable)

80

110

ø1

13

Trip button (red)

Drilling plan (front view) 14 32

3

HL

117

Interpole barrier (removable)

46.5 55.5 132 141 273

Front-connected

43

70

70 43

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.


ASL : Arrangement Standard Line H L : Handle Frame Centre Line CL : Handle Centre Line

XS1250ND 2P, 3P

Outline dimensions (mm) Front-connected

Drilling plan (front view)

Mounting hole

Toggle extension (removable)

Conductor overlap, max

M8 Mounting screw

Rear-connected Drilling plan (front view)

Panel cutout (front view)

Mounting plate M8 Mounting screw

Conductor overlap, max

Insulating plate Mounting plate

5

Soft plastic tubing ø50 to be provided on center pole and neutral pole of vertical terminal type for insulation.

ø15 for accessory wiring when necessary

Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon.

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

Outline Dimensions

Note: Studs are factory installed in horizontal direction both on the line and load sides. Please specify when ordering if vertical direction is reqired.

5-15


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

XS1600ND 2P, 3P

Outline dimensions (mm) Front-connected

Drilling plan (front view) Insulating plate Toggle extension (removable)

Mounting angle

M8 Mounting screw

Conductor overlap, max

Rear-connected

Drilling plan (front view)

Panel cutout (front view)

Mounting angle

Conductor overlap, max

M8 Mounting screw

Insulation tube side Center pole (ON OFF side All poles )

Panel cutout dimensions shown give an allowance of 1.5mm around the handle escutcheon.

Breaker fixing screw

395 (draw-out) 325 (disconnected) 295 (test) 265 (connected)

Mounting hole Draw-out handle (removable)

ø12

ø12 Mounting hole

220

420

50 75 100 60

Toggle extension (removable)

200

225 ø12

105

220

Drilling plan (front view)

20 170

3P

※Contact TERASAKI if manual connection is required.

282 316 396 (connected) 526 (draw-out)

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-16

Conductor overlap, max

25 120

300 (max.)

15

70 70

20

70 20 25

90

Conductor overlap, max

200

Mounting angle

215

°

20 190

Draw-out Auxiliary circuit terminals (Automatic connection)


ASL : Arrangement Standard Line H L : Handle Frame Centre Line CL : Handle Centre Line

XS2000ND 2P, 3P

Outline dimensions (mm) Front-connected

Drilling plan (front view) 65 30

ø11

130 28.8

Mounting angle

HL 30

20 90

Mounting hole

Toggle extension (removable)

ASL 30

ASL

193

M10 Mounting screw

105 105 320

15 30 20 90

250

10

Conductor overlap, max

60

20 225 380

Drilling plan (front view) HL

HL

Mounting angle

185

245 340

20 30

232

ASL 30 79

ASL

160 ø11

Conductor overlap, max

HL

105

95 65

30

ASL

Panel cutout (front view)

30

M10 Mounting screw Toggle extension (removable)

ø12

18

Rear-connected

1 10

302

1

302

20 105 105

144

58 98.5

ASL

232

450

257

105

79

3P

0

R1

ø12 119

130 15

Panel cutout dimensions shown give an allowance of 2mm around the handle escutcheon.

Draw-out 561(draw-out) 371(disconnected) 341(test) 311(connected)

65 160 95 112 15 30 20

624

30

310 ※

405(max.)

※Contact TERASAKI if manual connection is required. Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

340(3P) HL

ø14

ø11

314 ASL

Mounting hole ø14 HL

308 13 371 466

25

ASL

ASL

° 90

20

105105 Conductor overlap, max 290(3P) Mounting angle

268

Outline Dimensions

Draw-out toggle (removable)

5

Drilling plan (front view)

20 232

Mounting hole

Manual operating toggle (removable)

20 280

3P HL 334

34

Auxiliary circuit terminals (Automatic connection)

5-17


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

XS2500ND 2P, 3P, XS3200ND 2P, 3P

Outline dimensions (mm) Front-connected 裏 面形 3P

M10 Mounting screw

Toggle extension (removable) 90 28.8

Mounting angle

113 40 90

1

30

250 320

ASL

193

58 98.5

ASL

HL

178

450

257

Mounting hole

10

185 245

20 40

20

20 ø14 105 105 Conductor overlap, max

150

340

Mounting angle

HL 30

HL

30 302

119 Panel cutout dimensions shown give an allowance of 2mm around the handle escutcheon. Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-18

79

ASL

R 10

144

ASL

232

105

ø12


ASL : Arrangement Standard Line H L : Handle Frame Centre Line CL : Handle Centre Line

PVS160-SDL 3P, PVS250-SDL 3P

Outline dimensions (mm)

ø9

Terminal cover

Mounting hole

35

23

Conductor overlap, max

35

Mounting hole

Drilling plan (front view)

29.6

3P

4

HL

19

55

25(max.) max.t7

3P HL 11.5

67.1 60.6 57.5

Terminal cover

11(max.)

HL

With extension bars ✽ (optional)

Preparation of conductor

3P

30.5

Front-connected

M8 screw

C L

C L M4✕0.7 Mounting screw

22

C L

22

55 Insulating plate 10.5

1.6t 47.6 61.6 69.6 96.6

115

Insulating plate

5.4

✽ Straight bars only. For line and load side, use with the terminal covers.

Rear-connected

Drilling plan (front view)

3P HL

Terminal cover

67.1 60.2 57.1

102

Mounting plate (max. t3.2)

3P

Insulating plate

3P

3P

HL

H 52.5 L

ø24

HL

Panel cutout (front view)

6

55

Terminal cover

165

Mounting hole 5.3

M4✕0.7 Tapped hole

35 Insulating plate

ø11

Insulating plate 70 105 115

C L

126

165

102 45

144 165

25.6 C L

48

C L

C L

1.6t 61.6 69.6 96.6

Stud can be turned 45° or 90°

16

35 35

35

M4✕0.7 Tapped hole

53.5 107

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

PVS160-SDL 4P, PVS250-SDL 4P, PVS160-SNL 4P, PVS250-SNL 4P

65.5 59 57.5

Terminal cover

With extension bars ✽ (optional)

Preparation of conductor ø9

Terminal cover

35

23

35

Drilling plan (front view)

Conductor overlap, max

35

Mounting hole

28

4P

4

HL

19

25(max.) max.t7

55

4P HL

30.5

4P

M8 screw

C L M4✕0.7 Mounting screw

22

55

10.5

46 60 68 95

140

7

✽ Straight bars only. For line and load side, use with the terminal covers.

Drilling plan (front view) Terminal cover 2.3 5.3

M4✕0.7 Tapped hole

35

Rear-connected 65.5 58.6 57.1

Mounting plate (max. t3.2)

4P

4P ø24

HL

Terminal cover

Panel cutout (front view) 4P

HL

52.5

HL

48

126 144

C L

C L

5.3

9

20

7

Conductor overlap, max 25 22 ø9

C L

22

144

45

C L

102

165

6

Mounting hole

C L

22

ø11

35 105 140

4P HL

C L

126

C L

165

C L

102 45

144 165

24

5 Outline Dimensions

Front-connected

Mounting hole

M4✕0.7 Mounting screw

35

70.4 105.4

Outline dimensions (mm)

HL

35

11.5

Insulating plate 10.5

6 13

11(max.)

5.3 105 115

55

9

20

22

5.4

Conductor overlap, max 25 22 ø9

C L

126 144

144

45

Insulating plate C L

35 105 140

10.5

60 68 95

6 13 72 107

35

16 35 Stud can be turned 45° or 90°

35

35

35 M4✕0.7 Mounting screw

35

M4✕0.7 Tapped hole

53.5 142

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

5-19


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

PVS160-SDH 4P, PVS250-SDH 4P, PVS160-SNH 4P, PVS250-SNH 4P

HL

67.1 60.6 57.5

Terminal cover

ø9

Terminal cover

Mounting hole

With extension bars ✽ (optional)

Preparation of conductor

Drilling plan (front view)

Conductor overlap, max

35

29.6

Mounting hole

4P

4

HL

19

55

25(max.) max.t7

23

4P HL 35 35

11.5

4P

30.5

Front-connected

11(max.)

Outline dimensions (mm)

M8 screw

C L M4✕0.7 Mounting screw

22

55 Insulating plate

10.5

1.6t 47.6 61.6 69.6 96.6

Insulating plate

Insulating plate

180 5.4

✽ Straight bars only. For line and load side, use with the terminal covers.

Drilling plan (front view) Terminal cover

67.1 60.2 57.1

Mounting plate (max. t3.2)

4P

Insulating plate

4P

HL

Terminal cover

Panel cutout (front view) 4P

ø24

HL

Insulating plate

52.5

HL

48

126 144

C L

C L

5.3 55

9

20

5.4

Conductor overlap, max 25 22 ø9

C L

22

144

45

C L

102

165

6

2.3 5.3 55

4P HL

M4✕0.7 Tapped hole

ø11

Rear-connected Mounting hole

C L

22

35 Insulating plate

35 105 140 180

126

C L

165

102 45

144 165

25.6 C L

140 180

5-20

Insulating plate

10.5

1.6t 61.6 69.6 96.6

6 13 70.4 105.4

16

Stud can be turned 45° or 90°

35 35

35

35

35 M4✕0.7 Mounting screw

35

M4✕0.7 Tapped hole

53.5 142

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.


ASL : Arrangement Standard Line H L : Handle Frame Centre Line CL : Handle Centre Line

PVS400-NDL 3P

Outline dimensions (mm) Front-connected

Drilling plan (front view)

8

86.9 98.6 104.6 129.1 146.6

HL

CL

214

CL

M6 Mounting screw

Insulating plate

1.6t

Insulating plate

CL

51

30 14.5 44.5

12 (max.)

HL

260 349

102 90

228 260

30 (max.)

8 37.6

44.5 30 14.5

110

100

416

ø11 1.6t

M10 screw

116

90 140

4

ON side : 37.6 OFF side : 36.6

Mounting hole

60

With extension bars (optional)

Preparation of conductor

3P HL

ø1

Interpole barrier (removable)

CL

M6 Tapped hole

45

13.1 Trip button (red)

120 148

8

36.6

60

Note: See section 4 for the installation of the insulating plate.

Rear-connected Insulating plate

Drilling plan (front view)

Mounting plate Interpole barrier

Panel cutout (front view)

3P HL

Stud can be turned 45° or 90°

HL

92

214 228

104.6 15 Conductor overlap, max

M6 Tapped hole

118 45 45

6

Conductor overlap, max ø1 3

15

39 108.4

68.4 39

228 260 30

45

ø3

3

98.6 104.6 129.1 146.6

ø1

8

30 45 45

CL

R6

CL

102 90

8

CL

Insulating plate

Note: Studs are factory installed in horizontal direction both on the line and load sides. See section 4 for the installation of the insulating plate.

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

5 Outline Dimensions 5-21


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

PVS400-NDL 4P, PVS400-NDH 4P

Outline dimensions (mm) Front-connected

Drilling plan (front view)

ø1 4

12 (max.)

102 90

228 260

420

100

CL

M6 Mounting screw

51

8 45 45 45 70 115 185

HL

Insulating plate

CL

Insulating plate

1.6t

86.9 98.6 104.6 129.1 146.6

CL

214

116

30 (max.)

260 349

M10 screw

8 37.6 HL

30 14.5 44.5

ø11 1.6t

44.5 30 14.5

110

ON side : 37.6 OFF side : 36.6

Mounting hole

60

With extension bars (optional)

Preparation of conductor 4P HL

Interpole barrier (removable)

CL

45

13.1 Trip button (red)

8

M6 Tapped hole

36.6

52.5 60 60 60 81.5 126.5

60

Note: See section 4 for the installation of the insulating plate.

Rear-connected

Insulating plate

Interpole barrier

Stud can be turned 45° or 90°

Drilling plan (front view)

Mounting plate

Panel cutout (front view)

4P HL HL

Conductor overlap, max

15

15

M6 Tapped hole

36.5 118 45 45 45

Note: Studs are factory installed in horizontal direction both on the line and load sides. See section 4 for the installation of the insulating plate.

Front-connected

With extension bars (optional)

Preparation of conductor

Drilling plan (front view)

ø11

M10 screw

30 (max.)

HL

30 14.5 44.5

Mounting hole

12 (max.)

110

ON side : 36 OFF side : 35

44.5 30 14.5

4

ø1

4P HL

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

PVS400-NNL 4P, PVS400-NNH 4P

Outline dimensions (mm)

Interpole barrier (removable)

92

45

6 ø3

Conductor overlap, max ø1 3

30

3

98.6 104.6 129.1 146.6

39 108.4

68.4 39

228 260

102 90

ø1

8

30 45 45 45

CL

R6

CL

214 228

104.6

8

CL

Insulating plate

8 36 HL

CL

M6 Mounting screw

51

8 45 45 45 70 115 185

85.3 97 103 127.5 145

CL

214

CL

260 349

102 90

228 260

116 CL

45

14.7 Trip button (red)

M6 Tapped hole

8 35

52.5 60 60 60 81.5 126.5

Note: See section 4 for the installation of the insulating plate.

Rear-connected

Drilling plan (front view)

Mounting plate Interpole barrier

Stud can be turned 45° or 90°

Panel cutout (front view)

4P HL HL

M6 Tapped hole

36.5 118 45 45 45

Note: Studs are factory installed in horizontal direction both on the line and load sides. See section 4 for the installation of the insulating plate.

5-22

92

214 228

103 Conductor overlap, max

15

39

45

6 ø3

Conductor overlap, max ø1 3

15

110

70 39

228 260 30

3

97 103 127.5 145

ø1

8

30 45 45 45

CL

R6

CL

102 90

8

CL

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.


ASL : Arrangement Standard Line H L : Handle Frame Centre Line CL : Handle Centre Line

PVS800-NDL 3P

Outline dimensions (mm) Front-connected 3P

Drilling plan (front view)

Mounting hole

t1

3 ø1

HL

L1 1.6t

Toggle extension (removable)

80

13

110

160

Interpole barrier (removable)

Insulating plate

HL

Mounting hole

40

15

80

32 25 8

51

Insulating plate 140 60

210

126

ASL

ASL 117

ASL

Trip button (red)

11.4

29.6

M8 Mounting screw

80

513

90 46.5 55.5 141 132 273

170

Conductor overlap, max

60

80.5

t2 L2 8 104.6 129.1 146.6

Rated Current (A) 630 (400-630) 800 (500-800)

Note: See section 4 for the installation of the insulating plate.

M8 Tapped hole

70

L1 L2 33.6 35.6 33.6 36.6

t1 8 10

t2 8 10

Rear-connected Drilling plan (front view)

ø15 for accessory wiring when necessary HL

3P HL

HL

80.5

104.6 129.1 146.6

70

M8 Mounting screw

70

ø13

8

ASL

M8 Tapped hole

Conductor overlap, max

126

ASL

172

70 43 70

R6

117

11.4 42

29.6

117

ASL

30.5

126

13

20 32 25 8 120.4

Insulating plate

104.6

10

Stud can be turned 90°

92

Toggle extension (removable)

Panel cutout (front view)

Insulating plate 8

1.6t

ø4

Interpole barrier

70 43

Mounting plate

Note: Studs are factory installed in horizontal direction both on the line and load sides. See section 4 for the installation of the insulating plate.

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

5 Outline Dimensions 5-23


ASL : Arrangement Standard Line H L : Handle Frame Centre Line C L : Handle Centre Line

DC Moulded Case Circuit Breakers

PVS800-NDL 4P, PVS800-NDH 4P

Outline dimensions (mm) Front-connected Interpole barrier (removable)

Mounting hole

4P HL

t1

1.6t

Toggle extension (removable)

80

13

110

L1

Drilling plan (front view)

3 ø1

Insulating plate

HL

Mounting hole

51

15

Insulating plate 70

70

70

105

ASL

M8 Mounting screw

t2 L2 8 104.6 129.1 146.6

Conductor overlap, max 80.5

280

M8 Tapped hole

70

175

60

ASL 11.4

29.6

80

32 25 8

40

117

ASL

Trip button (red)

126

90 46.5 55.5 141 132 273

513

170

Rated Current (A) 630 (400-630) 800 (500-800)

60

L1 L2 33.6 35.6 33.6 36.6

t1 8 10

t2 8 10

Note: See section 4 for the installation of the insulating plate.

Rear-connected

Drilling plan (front view)

Panel cutout (front view)

Insulating plate ø15 for accessory wiring when necessary H

4P HL

Stud can be turned 90°

HL

11.4

8 80.5

104.6 129.1 146.6

70

70

ø13

70

42

29.6

117

ASL

M8 Mounting screw

172

70 43 70

70

70 43

Mounting plate

Note: Studs are factory installed in horizontal direction both on the line and load sides. See section 4 for the installation of the insulating plate.

Front-connected

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.

PVS800-NNL 4P, PVS800-NNH 4P

Outline dimensions (mm) Mounting hole 4P

3 ø1

t1

170

ASL 51

15 70

70

70

105

80

HL

ASL

ASL 28 13

M8 Tapped hole

70

80

32 25 8

40

90 46.5 55.5 141 132 273

110

13

Drilling plan (front view)

L1

Toggle extension (removable)

126

HL

117

Interpole barrier (removable)

Trip button (red)

R6

ASL

M8 Tapped hole

Conductor overlap, max

126

30.5

ASL

117

13

20 32 25 8 120.4

126

Insulating plate

104.6

10

L

92

Toggle extension (removable)

ø4 8

1.6t

Interpole barrier

Conductor overlap, max

8

175

80.5

M8 Mounting screw

t2 L2 103 127.5 145

Rated Current (A) 630 (400-630) 800 (500-800)

280

L1 32 32

L2 34 35

t1 8 10

t2 8 10

Note: See section 4 for the installation of the insulating plate.

Rear-connected

Drilling plan (front view)

Panel cutout (front view)

Interpole barrier

HL

8 80.5

103 127.5 145

117

M8 Mounting screw

70

70

ø13

70

42

28 13

M8 Tapped hole

Conductor overlap, max

126

30.5

ASL

ASL

172

70 43 70

70

70 43

Note: Studs are factory installed in horizontal direction both on the line and load sides. See section 4 for the installation of the insulating plate.

5-24

R6

117

126

13

ASL

20 32 25 8 122

103

10

L

92

ø15 for accessory wiring when necessary H

4P HL

Stud can be turned 90°

ø4 8

Toggle extension (removable)

Panel cutout dimensions shown give an allowance of 1.0mm around the handle escutcheon.


TERASAKI ELECTRIC CO., LTD. Head Office: 7-2-10 Hannancho, Abenoku Osaka, Japan Circuit Breaker Division: 7-2-10 Kamihigashi, Hiranoku Osaka, Japan Telephone: Fax: Email:

81-6-6791-9323 81-6-6791-9274 int-sales@terasaki.co.jp http://www.terasaki.co.jp/

TERASAKI ELECTRIC (M) SDN, BHD.

TERASAKI ELECTRIC (EUROPE) LTD.

Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor Darul Ehsan, Malaysia

80 Beardmore Way, Clydebank Industrial Estate Clydebank, Glasgow, G81 4HT, Scotland (UK)

Telephone: Fax: Email:

Telephone: Fax: Email:

60-3-5549-3820 60-3-5549-3960 terasaki@terasaki.com.my

TERASAKI DO BRASIL LTDA. Rua Cordovil, 259-Parada De Lucas, 21250-450 Rio De Janeiro-R.J., Brazil Telephone: 55-21-3301-9898 Fax: 55-21-3301-9861 Email: terasaki@terasaki.com.br http://www.terasaki.com.br

TERASAKI ELECTRIC (CHINA) LTD. 72 Pacific Industrial Park, Xin Tang Zengcheng, Guangzhou 511340, China Telephone: Fax: Email:

86-20-8270-8556 86-20-8270-8586 terasaki@public.guangzhou.gd.cn

44-141-941-1940 44-141-952-9246 marketing@terasaki.co.uk http://www.terasaki.com/

TERASAKI ELECTRIC (EUROPE) LTD. FILIALE ITALIA Via Ambrosoli, 4A-20090 Rodano, Milano, Italy Telephone: Fax: Email:

39-02-92278300 39-02-92278320 terasaki@terasaki.it http://www.terasaki.it/

TERASAKI ELECTRIC (EUROPE) LTD. SUCURSAL EN ESPAÑA Pol. Ind. Coll de la Manya, C/Cal Ros dels Ocells 5-7, 08403 Granollers, Barcelona, Spain Telephone: Fax: Email:

34-93-879-60-50 34-93-870-39-05 terasaki@terasaki.es http://www.terasaki.es/

TERASAKI ELECTRIC GROUP SHANGHAI REPRESENTATIVE OFFICE

TERASAKI SKANDINAVISKA AB

Room No. 1405-6, Tomson Commercial Building 710 Dong Fang Road, Pudong, Shanghai, 200122, China

Telephone: Fax: Email:

Telephone: Fax: Email:

86-21-58201611 86-21-58201621 terasaki@vip.163.com

Box 2082 SE-128 22 Skarpnäck Sweden 46-8-556-282-30 46-8-556-282-39 info@terasaki.se http://www.terasaki.se/

TERASAKI ELECTRIC (SHANGHAI) CO., LTD.

TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.

Building 5 & 7, No.399 Xuanzhong Rd. Nanhui Industrial Zone, Shanghai, 201314, China

17 Tuas Street Singapore 638454

Telephone: Fax: Email:

86-21-5818-6340 86-21-5818-6350 tsc@terasaki.com.cn

Ratings and specifications are subject to change without notice.

CAT REF. ’13-I73E

Telephone: Fax: Email:

65-6425-4915 65-6425-4351 tecs@pacific.net.sg


13-i73e_dc_2013-6_web  