Page 1

ISO 9001:2008 Certified

SIGNAL CONDITIONING & ISOLATION INPUT-THERMOCOUPLE

SENSOR SIGNAL CONDITIONER (THERMOCOUPLE TO VOLTAGE & CURRENT CONVERTER) MODEL NO: I TCX 2D XXX-3P

Overview

SIM  2.0 Thermocouple (TC) input type modules can be interfaced to any of the commonly available TC types; i.e. J,K,B,E,R,S,T,N to generate isolated 0-10V/4-20mA output. These modules comprise of in-built Cold Junction Compensation (CJC) calibrated to track the TC mV response at room temperature. The TC mV v/s V/I output is a linearly proportional value. The module can be calibrated to I/P v/s O/P range according to the user requirements. The user has the option of implementing non-linearity error compensation of the TC response in the Data Acquisition System interfaced to the Voltage/Current output of the modules to achieve better accuracy in temperature measurements.

Technical Specifications

Thermocouple Input Signal

Input Options: J Type(0 to +1200°C)* K Type(0 to +1370°C)* E Type(0 to +1000°C)*

Factory Set * Max. Temperature Range

B Type(800 to +1820°C)*

 Input Thermocouple types : J, K, B,E,R,S,T,N  In-built Cold junction compensation (CJC).

R Type(0 to +1750°C)* S Type(0 to +1750°C)*

 0-10V/4-20mA output

T Type(0 to +400°C)*

calibration provided as per

N Type(0 to +1300°C)* Input Resistance

Features

100 K Ohm

user requirement of input temp. range.

Output Signal

Output Options: 0- +5V, 0- +10V, 0-20mA, 4 20mA.

Factory Set

Load Resistance

For Output Voltage

>1 K Ohm

For Output Current

500 Ohm Max.

Accuracy

±0.2% of Span at 25°C

Linearity

0.1%

Temperature Drift

<0.01% / °C

 Slim & compact design.

Response Time

< 1Sec

 Energy Efficient Module.

Calibration

Zero & Span (Trimpot )

 Low Noise & Low drift for

Performance a. Electronic System

b. Thermocouple Non-linearity Compensation : Not provided

General Specifications 2KV - 3 Port.

Isolation Power Supply

Enclosure ABS Plastic, 35 mm DIN Rail Mounted. IP40 Protection class. Operating temp. range

Voltage

24VDC(nominal)

Operating Range

18 to 36 VDC

Ripple

< 100mVpp

Power Supply Current

150mA.Max

Single Output

W - 22.5mm H - 75mm D - 110mm 0 – 55°C

Storage temp. range

0 – 80°C

Relative Humidity

0– 90% RH Non-Condensing 3000 mts above MSL

Max. Altitude

 Thermocouple non-linearity not compensated  24VDC Power Supply.

long term stability  2kV 3 Port Isolation.

Applications  Heating Control Systems  Temperature monitoring systems  Data Acquisition Systems


Ordering Information: Isolation (I) I

Input Type I/P

I

Output Type O/P

V TC

I

Supply 24VDC Supply

I/P Signal Range XX Type J :XJ ( 0 – +1200º C)* Type K :XK ( 0 – +1370º C)* Type E :XE (0 – +1000º C)* Type B :XB ( 800 – +1820º C)* Type R :XR ( 0 – +1750º C)* 2D Type S :XS ( 0 – +1750º C)* Type T :XT (0 - +400º C)* Type N :XN ( 0 -+1300º C)* *: Max. Measurement Range; X: Actual Range of TC

O/P Signal Range X

Isolation 3P

0-5V:05

0-10V:10

4-20mA:42 3P 0-20mA:20

Mechanical Details: Single Input & Single Output Converter

PIN

Details

PIN

Details

1

+Input

5

+Output

2

-Input

6

-Output

3

NC

7

+24VDC

4

NC

8

GND

Related Products     

Thermocouple Converters (Linearized Output) Programmable Input TC types J,K,B,E,R,S,T,N RTD to 0-10V/4-20mA Converters Programmable Indicators- Thermocouple Input, Re-transmission 4-20mA output, MODBUS interface

About Us CANOPUS INSTRUMENTS is engaged in the development & manufacturing of industrial automation and process control instrumentation products. The product areas cover mainly Analog Signal Conditioning Instruments for Process Automation, Embedded Systems & Ultrasonic Equipment for Non-Destructive Testing Applications. All the CANOPUS range of products are designed and manufactured with special care, to ensure trouble free performance in Industrial applications where Electromagnetic Interference (EMI) & Harsh environmental conditions exist. Today these products come to our customers with the quality assurance and tech-support in H/W & S/W, which has evolved with our experience of over 25 years, to ensure uninterrupted operation in field conditions. This has enabled us to successfully create an installed base of tens of thousands units performing satisfactorily in a wide spectrum of Critical Real time Industrial applications all over India and in other parts of the world.

INNOVATION – QUALITY- RELIABILITY Address: #2 & 3, ‘Vishwas’, Karnik Road, Off. Murbad Road, Kalyan (W) 421 301, Maharashtra, INDIA. Tel: +91-251-2322576 / 2203389 Telfax: +91-251- 2325849. Email: marketing@canopusinstruments.com Website: www.canopusinstruments.com

Thermocouple Signal Converter - Canopus Instruments  

Buy top quality thermocouple converter in India. Canopus Instruments offers the best thermocouple transmitter and converter in industry. Get...

Thermocouple Signal Converter - Canopus Instruments  

Buy top quality thermocouple converter in India. Canopus Instruments offers the best thermocouple transmitter and converter in industry. Get...

Advertisement