SIGNAL CONDITIONING & ISOLATION THERMOCOUPLE- LINEARIZED O/P

Sensor signal conditioner (THERMOCOUPLE TO MA CONVERTER (LINEARIZED)) MODEL NO.4.0-LTCI-XX

Salient Features  Programmable Thermocouple (TC) Amplifier unit with Diagnostic & Alarm  Programmable TC type selection ( J, K, B, E, R, S, T, N)  Programmable temperature range selection for 4-20mA O/P.  Software linearization algorithm achieves accuracy better than +/- 0.2%.  In-built Cold-Junction compensation (CJC) with Enable/Disable option.  Sensor FAULT (SF) detection with Digital Alarm Signal O/P.  DIP-Switch setting of 4-20mA O/P signal value on SF condition.  (Under Range / Over Range / Hold Last Process Value)  Output Wire Break (WB) indications.  Dual 4-20mA O/P with individual setting of O/P value on SF

Address: #2 & 3, ‘Vishwas’, Karnik Road, Off. Murbad Road, Kalyan (W) 421 301, Maharashtra, INDIA. Tel: +91-251-2322576 / 2203389 Telfax: +91-251- 2325849. Email: marketing@canopusinstruments.com Website: www.canopusinstruments.com


ISO 9001:2008 Certified

SIGNAL CONDITIONING & ISOLATION THERMOCOUPLE- LINEARIZED O/P

Product Overview The Sensor Signal Conditioner type 4.0-LTCI-XX is a Programmable Thermocouple (TC) Interface Unit with Diagnostic and Alarm capability. The unit can be programmed to interface to standard Thermocouple types J, K, B, E, R, S, T, & N. Thermocouple Temperature ranges for Full Scale output signal are selectable to obtain maximum resolution of the analog output signals. This unit performs the function of converting a TC signal into Single or Dual Isolated and Linerarized 4-20mA output signals. Complex software algorithms ensure very good stability and linearity levels of 0.1% of FS are achieved over the entire input range. In-built Cold Junction Compensation (CJC) facility is provided. The user has the option to ENABLE/DISABLE the CJC function in the analog output of the module. The unit incorporates an additional Diagnostic feature of “SENSOR FAULT (SF)” detection and ALARM output. The in-built unique sensor checking circuit performs a periodic Health Check operation to detect sensor fault. When a fault condition is detected it activates the “SF” indication (Red LED) on the front panel on the module. A logic output signal (24VDC) is also provided by the module which is used as an Alarm signal to warn an external control system about Sensor Fault condition. Additionally a DIP switch is provided to allow the user to select the output signal value set by the module in case of a Sensor Fault condition. The following options are selectable, a. b. c. d.

UPSCALE on Sensor Fault i.e. O/P > 22mA. DOWNSCALE on Sensor Fault i.e. O/P< 3.6mA. HOLD LAST VALUE on Sensor Fault. Do nothing. i.e. Output will follow Input (0mA on Sensor Fault.)

In a Dual output type unit, both the outputs can be individually set by the user to be set to any of the above values in case of SENSOR FAULT condition. Output Wire Break (WB) indications are also provided on the unit. This will indicate 4-20mA Output Open Circuit condition or load resistance >1KOhm across output. Other LED indications provided on the unit are, Input UNDERRANGE (UR), OVERRANGE (OR), & SYSTEM HEALTH (SH).

Address: #2 & 3, ‘Vishwas’, Karnik Road, Off. Murbad Road, Kalyan (W) 421 301, Maharashtra, INDIA. Tel: +91-251-2322576 / 2203389 Telfax: +91-251- 2325849. Email: marketing@canopusinstruments.com Website: www.canopusinstruments.com


ISO 9001:2008 Certified

SIGNAL CONDITIONING & ISOLATION THERMOCOUPLE- LINEARIZED O/P

The unit is offered with factory programmed TC type selection, CJC ENABLE/DISABLE & Temp. Range setting. The user can configure the DIP switch settings to set output response in Sensor Fault condition. Technical Specifications Thermocouple Input Signal

Input Options: J Type(-210 to +1200°C)*

Factory Set

K Type(-270 to +1372°C)* E Type(-270 to +1000°C)* B Type(0 to +1820°C)* R Type(-50 to +1768°C)* S Type(-50 to +1768°C)* T Type(-270 to +400°C)* N Type(-270 to +1300°C)* (*: Max. Measurement Range) Cold Junction Compensation(CJC)

Provided In –built CJC ENABLE/DISABLE

Output Signal

Output Options: 4-20mA. No of Outputs

Two (Max)

Load Resistance

For Output Current

1KOhm Max.

Performance

Accuracy

±0.2% of Span

Linearity

TC Input (mV)v/sOutput:0.1%

Linearization Temperature Drift

TC non-linearity is compensated by the unit. <0.01% / °C

Response Time

< 500mSec

Alarm Output

Active on SENSOR FAULT condition.24VDC, 50mA (Max.)

Dip Switch Setting

Allow the user to select the output signal value set by the module. Span (Trimpot )

Calibration General Specifications Isolation Power Supply

Enclosure ABS Plastic, 35 mm DIN Rail Mounted. IP40 Protection class.

Leakage Current Voltage Operating Range Ripple Power Supply Current Single Output

Termination Operating temp. range

2KV - 3 Port. <5mA. 24VDC(nominal) 18 to 36 VDC < 100 mVpp 200mA.Max W - 45mm H - 75mm D - 115mm Screw type terminals suitable for 1.5mmsq. Wire 0 – 60°C

0 – 80°C Storage temp. range Address: #2 & 3, ‘Vishwas’, Karnik Road, Off. Murbad Road, Kalyan (W) 421 301, Maharashtra, INDIA. 0– 90% Relative Humidity Tel: +91-251-2322576 / 2203389 Telfax: +91-251RH 2325849. Non-Condensing Max. Altitude

Email: marketing@canopusinstruments.com Website: www.canopusinstruments.com 3000 mts above MSL


ISO 9001:2008 Certified

SIGNAL CONDITIONING & ISOLATION THERMOCOUPLE- LINEARIZED O/P

Mechanical Details: PIN

Details

1

+ I/P (TC Input)

2

- I/P (TC Input)

3

SHLD (TC Input)

4

+ 24V DC (Supply)

5

GND(Supply)

6

Alarm O/P

7

- (O/P)Output2

8

+(O/P)Output2

9

- (O/P)Output1

10

+(O/P)Output1

In case of a sensor fault condition.(Refer Table 1.1) LED Indications System Health : SH (Green/red) Under range UR (Red) Over range OR (Red) Sensor Fault Both UR & OR (Red). O/P 1 Open WB1 (Red) O/P 2 Open WB2 (Red) Switch No. Switch Position 1

2

OFF

1

2

1

2

1

2

Function Description

OFF

CH1: UPSCALE on Sensor Fault i.e. O/P > 22mA

OFF

ON

CH1: DOWNSCALE on Sensor Fault i.e. O/P< 3.6mA

ON

OFF

CH1: HOLD LAST VALUE on Sensor Fault

ON

ON

3

4

OFF

OFF

CH1: Do nothing i.e. Output will follow Input (0mA on Sensor Fault.) CH2: UPSCALE on Sensor Fault i.e. O/P > 22mA

3

4

OFF

ON

CH2: DOWNSCALE on Sensor Fault i.e. O/P< 3.6mA

3

4

ON

OFF

CH2: HOLD LAST VALUE on Sensor Fault

3

4

ON

ON

CH2: Do nothing i.e. Output will follow Input (0mA on Sensor Fault.)

Ordering Information: Model Numbers Single Channel Dual Channel (4-20mA) Output with Alarm (4.0 – LTCI – A1) (4-20mA) Output with Alarm (4.0 –LTCI - A2) O/P O/P Single#2 Channel DualKalyan Channel Address: & 3, ‘Vishwas’, Karnik Road, Off. Murbad Road, (W) 421 301, Maharashtra, INDIA. (4-20mA) Output without (4.0 – LTCI - 1) (4-20mA) Output without (4.0 – LTCI - 2) Tel: +91-251-2322576 / 2203389 Telfax: +91-251Alarm O/P Alarm O/P 2325849. Email: marketing@canopusinstruments.com Website: www.canopusinstruments.com


ISO 9001:2008 Certified

SIGNAL CONDITIONING & ISOLATION THERMOCOUPLE- LINEARIZED O/P

Address: #2 & 3, ‘Vishwas’, Karnik Road, Off. Murbad Road, Kalyan (W) 421 301, Maharashtra, INDIA. Tel: +91-251-2322576 / 2203389 Telfax: +91-251- 2325849. Email: marketing@canopusinstruments.com Website: www.canopusinstruments.com

Thermocouple suppliers in India, thermocouple transmitter 4-20ma - Canopus Instruments  

Canopus Instruments are the manufacturers and suppliers of thermocouple signal converter, thermocouple transmitter 4-20ma, thermocouple to 4...

Thermocouple suppliers in India, thermocouple transmitter 4-20ma - Canopus Instruments  

Canopus Instruments are the manufacturers and suppliers of thermocouple signal converter, thermocouple transmitter 4-20ma, thermocouple to 4...

Advertisement