RISER DIAGRAM 602RF POWER SUPPLY

TO 120VAC POWER SOURCE TO FIRE ALARM – CLOSED CONTACT CONNECTION

4 COND

4 COND

E4KP CARD READER (OUTSIDE)

PTH-4 POWER TRANSFER HINGE

Z7850 ELECTRIFIED MORTISE LOCK

NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE.

Components Qty 1 1 1 1

Description Fail-Safe Electrified Mortise Lock 1 Amp Power Supply Power Transfer Hinge – 4 Conductor Proximity/PIN Card Reader

Part Number Z7850LU 602RF PTH-4 E4KP

Manufacturer SDC SDC SDC SDC

Method of Operation Access/Egress: Presenting an authorized card to the reader releases the lever of the locking device momentarily for access. Entry momentary unlock time is determined by the card reader programming. Egress will be free at all times. Emergency Release: All locks will release automatically (see note 5) upon activation of the fire life safety system.

PAGE 1 OF 2

© 2007 Security Door Controls Printed in U.S.A

PROJECT NAME:

LOCATION:

DISTRIBUTOR:

DWG. NO.: 0034

SO. NO.:

CONTACT:

DATE: 03-2007

SECURITY DOOR CONTROLS 3580 Willow Lane Westlake Village CA 91361-4921

DWN BY: ML

Tel. 805-494-0622 FAX: 805-494-8861


EMLock®

Exit Check®

HiTower®

Spacesaver®

SELECTRIC®

Sure Exit®

EntryCheck™

POINT TO POINT WIRING DIAGRAM 602 SERIES POWER SUPPLY

E4KP – CARD READER W/ CONTROLLER RELAY MODULE G

300 ft MAX J2

J3 RED BLK BRN ORG YEL

RED BLK BRN ORG

RED BLK BRN ORG

+12V GND CLOCK

ACCESS CONTROLLER

DATA

INPUT DC12V EXIT BUTTON DOOR SENSOR STRIKE

NOT USED

CARD READER

TO 120VAC PRIMARY VOLTAGE CONNECTION

W

K3 FUNCTION SETTING FUNCTION 1 2 DURESS/SHUNT ON OFF GUARD OFF ON OFF OFF PATROL

3 OFF OFF ON

ON 1 2 3

MODEL : E5RM S/N : 12345678

ALARM K3

+

-

B

RED BLK BRN ORG YEL GRN BLU

RED BLK BRN ORG YEL GRN BLU

YEL GRN BLU YEL GRN BLU

YEL GRN BLU YEL GRN BLU

24V

12V

REFER TO POWER SUPPLY INSTRUCTIONS FOR 12VDC VOLTAGE SELECTION PROCEDURE

+

-

+

-

C

+

J1

STANDBY BATTERY CONNECTION

E5RM CONTROLLER RELAY MODULE

(REMOVE FACTORY JUMPER ONLY IF FIRE ALARM IS USED)

12VDC OUTPUT

CLOSED FIRE ALARM CONTACT

Z7850 FAIL SAFE ELECTRIFIED MORTISE LOCK PTH-4 POWER TRANSFER HINGE

-

WHT

NOTE: REFER TO LOCK INSTRUCTION MANUAL FOR VOLTAGE SELECTION WIRING.

BLU BLK RED

+ © 2007 Security Door Controls Printed in U.S.A

SECURITY DOOR CONTROLS 3580 Willow Lane Westlake Village CA 91361-4921 Tel. 805-494-0622 FAX: 805-494-8861

NOTE: ALL WIRING MUST BE REVIEWED AND APPROVED BY THE PROJECT ENGINEER ASSIGNED TO THE LOCATION FOR IT’S CORRECTNESS AND SUITABILITY FOR THE APPLICATION IN THE WHICH THE EQUIPMENT INSTALLED AND OPERATED. ALL WIRING MUST CONFORM TO NATIONAL, STATE, AND LOCAL CODES FOR CLASS 2 FIRE PROTECTION AND CONTROL DEVICES.

PROJECT NAME: LOCATION.:

TITLE:

-

DIST.: --

SO NO.:

-CONTACT: --

REV --

DATE: 08-2007

DRAWN BY: ML

DWG. NO.: DWG0034

-PAGE 2 OF 2


Visio-DWG0034  

Qty Description Part Number Manufacturer 1 Fail-Safe Electrified Mortise Lock Z7850LU SDC 1 1 Amp Power Supply 602RF SDC 1 Power Transfer Hi...