2-point controllers | Thermostats

TSHK 681, 682: Fan-coil room temperature controller, with digital display Features •

Y

LCD of the room temperature or setpoint, with two buttons (±) for adjusting the setpoint

Output for heating or cooling depending on connection type, or change in direction of operation with external switch • With main switch for mains power supply and slide switch for three fan speeds • Suitable for wall mounting or fitting on recessed junction boxes

Electronics unit and switching relay

Quasi-continuous temperature control

2-point pulsed activation

Individual unitary temperature control in residential and business rooms for activating e.g. electric heating systems, thermal actuators, or fans or cooling units in air-conditioning systems.

TSHK68*F001

Technical data Power supply

Power supply1)

230 V~, approx. ±10 V, 50...60 Hz

Setting range Proportional band Display of actual value Hysteresis2) Shortest switching interval Time constant in still air Dead time in still air Time constant in moving air (0.2 m/s) Dead time in moving air (0.2 m/s)

5...30 °C; resolution 0.5 °C 3K 0...40 °C; resolution 0.1 °C Approx. ±0.1...0.5 K Approx. 18 minutes (E = 0.5) 20 minutes 2 minutes 15 minutes 1 minutes

Ambient temperature

0...55 °C

Load Fan load

3(2) A, 230 V~ 6(3) A, 230 V~

Weight Housing Housing material

0.18 kg Pure white (RAL 9010) Fire-retardant thermoplastic (fire classification UL94 HB) Black thermoplastic with NTC sensor At rear For cables of up to 2.5 mm²

Parameters

Ambient conditions

Outputs

Construction

Baseplate Cable inlet Screw terminals Standards and directives

Type of protection Protection class Energy class

1)

2)

IP30 (EN 60529) II (IEC 60730) I = 1% as per EU 811/2013, 2010/30/EU, 2009/125/EC

10% more voltage results in: Proportional band approx. 4 K, switching period 15 min, actual-value reduction approx. 0.5 K The device is pulsed electronically. When the temperature increases, the control factor falls to zero at the “Heating” output and rises to E = 1 at the “Cooling” output. A small temperature variation of ±0.1...0.5 K occurs as a result of pulsing, depending on the time constant of the room

Right of amendment reserved © 2021 Fr. Sauter AG

17

Profile for SAUTER Controls

SAUTER Catalogue 2021/2022 Products and Systems  

Comprehensive information about products and solutions.

SAUTER Catalogue 2021/2022 Products and Systems  

Comprehensive information about products and solutions.

Profile for sauter

Recommendations could not be loaded

Recommendations could not be loaded

Recommendations could not be loaded

Recommendations could not be loaded