6-Requisitos e Avanços em P&D relacionados à Segurança - Daniel Colbourne

Page 32

New proposals for EN 378 and 60335-2-40 Can use any means to minimise leaked amount of refrigerant, but sensors to detect leak and close valves can be used to prevent further release optional solenoid valve in suction line

not leaked

1000

leaked

R290 mass [g]

800 600unit indoor (e.g., evaporator) 400 200

solenoid valve in liquid line

0 sys on; check temp; shut valve

Retained mass

Released mass

sys off; shut valve

sys on; gas detector; shut valve

Whilst tests found approx. 10 – 20% charge retained in system under “off� mode, with shut-off valves, up to 80% charge can be retained