Page 1

1. All clearances and protective devices to be in conformance to the most stringent requirements of either the NESC, NEC or other codes of governmental or regulating authorities as applicable.

2

2. If length of conduit exceeds 10 feet, coupling is permited on end adjacent to meter. 3. Guy pole as required. 4. For every additional 5' length on meter loop add 20' of wire to the installation.

1

4&5 3

4&5

Strap for every 5' of conduit in meter loop

7 7 6 66" Min 72" Max To Center of Meter

6 Strap below as required. Grade Ground rod per RUS standard H1.1 ITEM 1

MATERIALS LISTING DESCRIPTION 200A Three-Phase Meter Loop

UNIT Ea.

PREC # 8312-*

6 7T 200A 3 Phase Meter Box w/Disconnect Ea. 9186 Form 16S/15S Class 200 120-480V 4-Wire 3 Ă˜ Meter 7 Ea. Design Parameters: 277/480V 200A - 15, 25, & 50kVA Transformers ( 150 kVA Bank ) 4-Wire Self Contained, 15' & 20' Down Loop Mounted on Meter Pole > See design notes 1 through 4 above. ( Self Contained ) > *Loop length per staking sheet.

6/3/2008 Rev. 0

Q3.4-02SC*

q3_4_02sc  

Grade 4. For every additional 5' length on meter loop add 20' of wire to the installation. 1. All clearances and protective devices to be in...