Deadend Assembly per Staking Sheet

1. All clearances and protective devices to be in conformance to the most stringent requirements of either the NESC, NEC or other codes of governmental or regulating authorities as applicable.

Only 2 cutouts Disregard this unit

2. If length of conduit exceeds 10 feet, coupling is permited on end adjacent to meter. 3. Guy pole as required. 4. For every additional 5' length on meter loop add 20' of wire to the installation.

7 3

A B C

1 1 H2 H1

X1 X2

X3

H2

X1 X2

11

12"

H1

8

X3

a b c

16

Open Delta uses only 2 transformers

Strap for every 5' of conduit in meter loop

9

13

12

Open Wye - Open Delta

15

15 400A

15' MIN to Customer Disconnect

66" Min 72" Max To Center of Meter

Finished Grade

ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14

15 16

DESCRIPTION 350 MCM THHN Cu (350A Rating) 5/8" x 16" Machine Bolt Transformer Trainer Brackets 2 x 2 Square Washer 5/8" Locknut 1/2" x 4" Lag Bolt 350 Terminal Adapter (Pigtail) 12" Standoff Bracket 1/2" x 1" SS Bolt 1/2" Spring Nut 4" Weatherhead 4" Schedule 80 PVC 4" Pipe Strap 4" PVC Terminal Adapter

MATERIALS LISTING QTY 10' DL 100 2 2 2 2 4 5 2 4 4 1 10 2 1

13T 400A 3 Phase Instrument Rated Meter Cabinet Form 9S/8S Class 20 120-480V 4-Wire 3Ă˜ Meter

UNIT Ft. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ea. Ft. Ea. Ea.

PREC # 3145 1083 9052 9091 9096 9110 9266 9290 9856 9295 8220-4 8245-4 9155 9801-4

1 1

Ea. Ea.

8116-3

120/240V 400A - Open Delta 4-Wire Instrument Rated Down Loop Mounted on Transformer Pole

Design Parameters: >See design notes above. >*Loop length as required.

1 1

QTY 15' DL 120 2 2 2 2 6 5 3 4 4 1 15 3 1