Functions Settings ■ Functions Settings ●P codes: Motor Parameters Func. Code

Name

Data setting range

(No. of poles) 2 to 22 poles (Rated capacity) 0.01 to 30.00 kW (where, the data of function code P99 is 0, 3, or 4.) 0.01 to 30.00 HP (where, the data of function code P99 is 1.) (Rated current) 0.00 to 100.0 A (Auto-tuning) 0 : Disable 1 : Enable (Tune %R1 and %X while the motor is stopped.) 2 : Enable (Tune %R1 and %X while the motor is stopped, and no-load current while running.) (ON-Line tuning) 0 : Disable 1 : Enable (No-load current) 0.00 to 50.00 A (%R1) 0.00 to 50.00 % (%X) 0.00 to 50.00 % (Slip compensation gain(driving)) 0.0 to 200.0 % (Slip compensation response time) 0.00 to 10.00 s (Slip compensation gain(braking)) 0.0 to 200.0 % (Rated slip frequency) 0.00 to 15.00 Hz Motor Selection 0 : Characteristics of motor 0(Fuji standard motors, 8-series) 1 : Characteristics of motor 1 (HP-rated motors) 3 : Characteristics of motor 3(Fuji standard motors, 6-series) 4 : Other motors Motor

Min.

Unit

Data Default setting copy*2

2 0.01 0.01 0.01 -

Pole kW HP A -

Y1Y2 4 Y1Y2 Nominal rated capacity of standard motor Y1Y2 Rated carrent of Fuji’s standard motor N 0

-

-

Y

0

0.01 0.01 0.01 0.01 0.01 0.01 0.01 -

A % % % s % Hz -

Y1Y2 Y1Y2 Y1Y2 Y Y1Y2 Y Y1Y2 Y1Y2

Rated carrent of Fuji’s standard motor Rated carrent of Fuji’s standard motor Rated carrent of Fuji’s standard motor 100.0 0.50 100.0 Rated carrent of Fuji’s standard motor 0

Min.

Unit

-

-

N

0

1 0.1 -

Times s -

Y Y Y

0 5.0 0

-

-

Y

0

-

-

Y

0

-

-

Y

0

-

-

Y

0

-

-

Y

1

0.1 0.01

s Hz/s

0.1 -

s -

Y Y

999 0

0.01 0.1 -

V Hz -

Y Y Y

1.60 0.0 0

1 0.1 0.1 1

s Hz V

N N N N N N Y Y Y2

0 Set at factory shipping 0.0 0.0 0

0.1 1

Hz V

Y Y2

0.0 0

0.01 0.01

s s

Y Y

6.00 6.00

●H codes: High Performance Functions Func. Code

Name Data Initialization

Auto-reset

(Times) (Reset interval) Cooling Fan ON/OFF Control Acceleration/Deceleration Pattern

Limiting the direction of the motor rotation

Starting mode (Auto-search for idling motor speed)

Deceleration Mode Instantaneous Overcurrent Limiting (Mode selection) Restart Mode after Momentary Power Failure (Restart time) (Frequency fall rate) (Allowable momentary power failure time) PTC Thermistor (Mode selection) (Level) Droop control Communications Link Function (Mode selection)

Capacitance of DC Link Bus Capacitor Cumulative Run Time of Cooling Fan Starting times of the inverter Mock Alarm Initial Capacitance of DC Link Bus Capacitor Cumulative Run Time of Capacitors on the Printed Circuit Board Starting Mode (Delay time) Non-linear V/f Pattern 1(Frequency) (Voltage) Non-linear V/f Pattern 2(Frequency) (Voltage) ACC/DEC time (Jogging operation) Deceleration Time for Forced Stop

Data setting range 0 : Disable initialization 1 : Initialize all function code data to the factory defaults 2 : Initialize motor parameters (Motor 1) 3 : Initialize motor parameters (Motor 2) 0 : Disable, 1 to 10 times 0.5 to 20.0 s 0 : Disable (Always in operation) 1 : Enable (ON/OFF controllable) 0 : Linear 1 : S-curve (Weak) 2 : S-curve (Strong) 3 : Curvilinear 0 : Disable 1 : Enable (Reverse rotation inhibited) 2 : Enable (Forward rotation inhibited) 0 : Disable 1 : Enable ( At restart mode after momentary Power Failure) 2 : Enable ( At restart mode after momentary Power Failure and at normal start) 0 : Normal deceleration 1 : Coast -to-stop 0 : Disable 1 : Enable 0.1 to 10.0 s "0.00 : Selected deceleration time 0.01 to 100.00 Hz/s, 999 : Follow the current limit command 0.0 to 30.0 s, 999 : The longest time automatically determined by the inverter 0 : Disable displayed.) 1 : Enable (Upon detection of (PTC), the inverter immediately trips and stops with 0.00 to 5.00V -60.0 to 0.0 Hz Frequency command Run command 0 : F01/C30 F02 1 : RS485-1 F02 2 : F01/C30 RS485-1 3 : RS485-1 RS485-1 4 : RS485-2 F02 5 : RS485-2 RS485-1 6 : F01/C30 RS485-2 7 : RS485-1 RS485-2 8 : RS485-2 RS485-2 Indication for replacing DC link bus capacitor (0000 to FFFF: Hexadecimal) Indication of cumulative run time of cooling fan for replacement Indication for replacing DC link bus capacitor (0000 to FFFF: Hexadecimal) 0 : Disable, 1 : Enable Indication for replacing DC link bus capacitor (0000 to FFFF: Hexadecimal) Indication for replacing capacitors on printed circuit board (0000 to FFFF: Hexadecimal). Resettable. 0.0 to 10.0 s 0.0 : Cancel, 0.1 to 400.0 Hz 0 to 240V : Output a voltage AVR-controlled (for 200 V series) 0 to 500V : Output a voltage AVR-controlled (for 400 V series) 0.0 : Cancel, 0.1 to 400.0 Hz 0 to 240V : Output a voltage AVR-controlled (for 200 V series) 0 to 500V : Output a voltage AVR-controlled (for 400 V series) 0.00 to 3600 s 0.00 to 3600 s