ACS800 Standard

Page 73

73

Motor temperature measurement through an analogue I/O extension This section describes the motor temperature measurement of one motor when an optional analogue I/O extension module RAIO is used as the connection interface. RAIO module

One sensor Motor

AI1+ AI1-

T AO1+ 10 nF (> 630 VAC)

AO1-

SHLD

Three sensors

RAIO module

AI1+ Motor T

T

The minimum voltage of the capacitor must be 630 VAC.

AI1T

10 nF (> 630 VAC)

AO1+ AO1-

SHLD

WARNING! According to IEC 664, the connection of the motor temperature sensor to the RAIO module, requires double or reinforced insulation between motor live parts and the sensor. Reinforced insulation entails a clearance and creepage distance of 8 mm (400 / 500 VAC equipment). If the assembly does not fulfil the requirement: • The RAIO module terminals must be protected against contact and they may not be connected to other equipment. Or • The temperature sensor must be isolated from the RAIO module terminals. See also section Motor Thermal Protection on page 62.