Actual signals and parameters 267
All parameters No. Name/Value 4018 ACT1 MINIMUM
Description Sets the minimum value for ACT1. Scales the source signal used as the actual value ACT1 (defined by parameter 4016 ACT1 INPUT). For parameter 4016 values 6 (COMM ACT 1) and 7 (COMM ACT 2) scaling is not done. Par 4016 1 2 3 4 5
Source Analog input 1 Analog input 2 Current Torque Power
Source min. 1301 MINIMUM AI1 1304 MINIMUM AI2 0 -2 · nominal torque -2 · nominal power
Def/FbEq 0%
Source max. 1302 MAXIMUM AI1 1305 MAXIMUM AI2 2 · nominal current 2 · nominal torque 2 · nominal power
A = Normal; B = Inversion (ACT1 minimum > ACT1 maximum) ACT1 (%)
ACT1 (%) 4019
A
4018 Source max. Source min. Source signal
4018
B
4019 Source min. Source max. Source signal
-1000…1000% Value in percent 1 = 1% 4019 ACT1 Defines the maximum value for variable ACT1 if an analog 100% MAXIMUM input is selected as a source for ACT1. See parameter 4016 ACT1 INPUT. The minimum (4018 ACT1 MINIMUM) and maximum settings of ACT1 define how the voltage/current signal received from the measuring device is converted to a percentage value used by the process PID controller. See parameter 4018 ACT1 MINIMUM. -1000…1000% Value in percent 1 = 1% 4020 ACT2 MINIMUM
See parameter 4018 ACT1 MINIMUM.
-1000…1000% See parameter 4018. 4021 ACT2 See parameter 4019 ACT1 MAXIMUM. MAXIMUM -1000…1000% See parameter 4019. 4022 SLEEP SELECTION NOT SEL
0% 1 = 1% 100% 1 = 1%
Activates the sleep function and selects the source for the NOT SEL activation input. See section Sleep function for the process PID (PID1) control on page 153. No sleep function selected
0