GAS PRESSURE REGULATOR SERIES 277 HI-FLO™ Introduction, Application, Features, Technical Data Introduction • The Series 277 & 277H ‘Hi-Flo’ Regulators are direct acting, single main diaphragm, spring loaded open, balanced, lever operated regulators for use on pressure reduction systems. Designed to control a wide inlet pressure and capacity applications by utilising a pressure balancing secondary diaphragm. • Use with confidence on natural and manufactured gases of non-aggressive nature, including Nitrogen, Carbon Dioxide, Propane and Butane. Application

2

• Designed for use on gas pressure reduction services to domestic, business premises and industrial feeds to burners, heater units and boilers • For equipment where an accurate, safe, dependable pressure controlled supply is required. Features • Completely independent operation of regulator and safety cut-off valve. • Diaphragm casing may be rotated through steps of 45 deg. relative to body to give the optimum installed position. • Cartridge construction, servicing and inspection can be carried out without taking body out of the line. • Wide inlet and outlet pressure range achieved by a middle balancing diaphragm and interchangeable main springs. • External Pressure Impulse (Rc 1/2 connection). • With or without Internal Relief Valve. TECHNICAL DATA Size range: DN 50

Service conditions: Maximum inlet pressure

Flanged BS 4504 PN16 and ASA Class 150

10.3 Barg (149 psig)

Outlet Pressure Range: Series 277 Series 277H

10 to 350 mbarg (4 to 140” wg) 320 to 500 mbarg (128 to 200” wg)

Maximum Incidental Outlet Pressure: Series 277 Series 277H

550 mbarg (220” wg) (i.e. Max. Allowable OPCO trip set pressure) 700 mbarg (280” wg)

Internal Relief Valve Setting: Series 277 Series 277H Temperature Range Options • P - Type • R - Type

20 mbarg (8” wg) } Nominally 80 mbarg (32” wg) } (above regulator outlet pressure set-point) -20°C to +60°C No Internal Relief With Internal Relief

• Regulator can be fitted with the Series 309 Over pressure (OPCO), or Under/Over pressure (UPCO/OPCO), Safety Cut-Off Valve. These devices protect the downstream system in the event that an excessive gas pressure condition develops. • Trip Indicator to show Open/Closed condition

Installation • The regulator may be mounted in any orientation to suit site conditions, moisture or debris must not ingress the vent hole. • For optimum performance the recommended position is with diaphragm casing horizontal and spring housing vertically upwards. • It is important when installing equipment that pipeline stresses are kept to a minimum and no undue external forces are placed on the connections.


GAS PRESSURE REGULATOR SERIES 277 HI-FLO™ Technical Data

TECHNICAL DATA Regulator Spring Ranges

Spring Number

* Series 277H model only, requires special spring adjuster, spring carrier, top cap and internal relief spring.

1253

LP-OPCO:Safety Cut-Off Valve * Requires special spacer.

Red Grey Purple Green Yellow Black White Orange Blue Silver Brown

mbarg

10 - 15 15 - 20 18 - 35 20 - 28 28 - 45 45 - 75 75 - 110 95 - 150 140 - 225 200 - 350 320 - 500

Spring

Pressure cut-off range

861 1103 1104 1105 1254* 1255*

Brown Gold Purple Black Red Green

35 - 90 80 - 130 120 - 250 200 - 350 340 - 500 450 - 600

14 - 36 32 - 52 48 - 100 80 - 140 136 - 200 180 - 240

40 - 55 50 - 110 110 - 200 150 - 240

16 - 22 20 - 44 44 - 80 60 - 96

mbarg

1109 1110 1111 1140

Grey Green Silver Silver/Red

UPCO

1138

Blue/Green

MP2 - OPCO and UPCO/OPCO: OPCO

1132

Safety Cut-Off Valve

1104

Safety Cut-Off Valve

4- 6 6- 8 7 - 14 8 - 11 11 - 18 18 - 30 30 - 44 38 - 60 56 - 90 80 - 140 128 - 200

Colour

OPCO OPCO OPCO OPCO

Materials of Construction Regulator

Number

LP-UPCO/OPCO: Safety Cut-Off Valve

UPCO

ins wg

Test Spring for elevated outlet pressures to facilitate OPCO setting.

Outlet pressure range

Colour

1244 1245 1299 1246 1247 1248 1249 1250 1251 1252 1263*

White/Blue

Purple

Body Top & Bottom Half Casing, Top Cap, Spring Adjuster (Series 277) Spring Carrier, Top Cap (Series 277H) Orifice, Bottom Casing Guide Bush Lever Valve Spindle Spring Retainer and Diaphragm Plates Relief Valve & Main Springs

10 - 30

ins wg

4 - 12

500 - 800

200 - 320

50 - 190

20 - 76

Valve Seat ‘O’ Rings Diaphragms Balancing Cartridge

Ductile Iron: BS EN 1563 Grade EN-GJS-18-LT Aluminium Alloy: BS 1490 Grade Gr. LM24M Mild Steel: BS 970 Grade 070M20 plated Brass: BS 2874 Grade CZ 121 Stainless Steel: BS 3416 Grade ANC 3B Stainless Steel: BS 970 Grade 416S29 Mild Steel: BS 1449 Grade CS4 plated Spring Carbon Steel: BS 5216 Grade HS3 and Chrome Vanadium: BS 2803 Polyurethane Nitrile Moulded Nylon Reinforced Nitrile Aluminium: BS 1474 Grade 6082

Body Spindle Valve Valve Seating Diaphragm & ‘O’ Rings Spring Adjuster Spring

Aluminium: BS 1490 LM6 Stainless Steel: BS 970 Grade 316 S31 Aluminium: BS 1474 Grade 6082TF Polyurethane Nitrile Brass: BS 2874 Grade CZ 121 Spring Carbon Steel: BS 5216 Grade HS3

Minimum OPCO & UPCO/OPCO Settings: • P - Type: 35 mbarg (14” wg) or 10% above regulator set-point, whichever is the higher. • R - Type: 55 mbarg (22” wg), when Internal Relief fitted. • Minimum differential pressure between UPCO and OPCO is 45mbarg (18” wg) for P - Type and 65mbarg (26” wg) for R - Type with internal relief. • Maximum recommended OPCO setting above Regulator Set-Point is 200 mbarg (80” wg).

3


GAS PRESSURE REGULATOR SERIES 277 HI-FLO™ Performance

TABLE OF COEFFICIENTS Orifice Size (mm) 32mm

Body Size

Cg

K1

C1

DN 50

809

83

41

Note Cv = Cg C1

4

Capacity Performance Sub-Critical Flow • For in-control capacities see capacity tables given on page 5.

Critical Flow

• (Pe - Pa)≤0.5(Pe + Pb)

• Maximum full open capacities can be calculated using the following equations:

Q=

• (Pe - Pa)≥0.5(Pe + Pb)

6.97 Cg(Pe + Pb)sin K1 d(te + 273)

Pe - Pa Pe + Pb deg

6.97 Cg(Pe + Pb) Q= d(te + 273)

Example Calculation : For 2” size with 32mm orifice Conditions Medium

: Inlet Pressure (Pe) 1 barg : Outlet Pressure (Pa) 200 mbarg : Natural Gas SG 0.6

Test for flow conditions: (1 - 0.2) ≤0.5(1 + 1.01325) 0.8≤1.006 *Hence Sub-Critical Flow conditions.

Full Open Capacity: 6.97 0.8 x 809(2.01325)sin 83 Q= 0.6(15 + 273) 2.01325 deg Q=682 Sm3/hr

Performance Classification • Lock Up (SG): The amount of ‘Lock-Up’ pressure is dependant upon the main spring fitted and the prevailing inlet pressure ranges. • Accuracy Class (AC): All capacity data given in the tables is based on AC10 and AC20 • Flow Turn Down Ratio: Varies according to prevailing pressure, flow and installation design. For a general guide expect 50:1 minimum.

Internal relief

DEFINITION Q

Full Open Capacity in m3/hr at Metric Standard Conditions (M.S.C.)

Cg

Flow Coefficient

K1

Body Shape Factor

d

Relative Density/SG of Gas (Air = 1)

Pe

Inlet Pressure (bar g)

Pa

Outlet Pressure (bar g)

Pb

Ambient atmospheric pressure in barA (Absolute)

te

Gas temperature at inlet of unit in °C

6.97

Constant

M.S.C.

Absolute pressure of 1.01325 barA and temperature of 15°C


GAS PRESSURE REGULATOR SERIES 277 HI-FLO™ Capacities: DN 50 in sm³/hr for Natural Gas (SG 0.6)

ACCURACY CLASS AC10 Lock Up Pressure Class (SG)

SG30

SG30

SG30

SG30

Inlet Pressure 1244 1245 1246 1247

SG20

SG20

SG20

SG15

SG15

SG15

1250

1251

1252

1263

475

Spring Number 1248

1249

Set Point pas (mbar)

14 70 mbar 140 mbar 350 mbar 700 mbar 1 bar 2 bar 3 bar 4 bar 5 bar 6 bar 7 bar 8 bar 9 bar 10 bar

100 140 225 340 400 600 800 1250 1600 1850 2225 2600 2900 3350

17

25

90 140 225 340 500 700 900 1250 1600 1850 2225 2600 2900 3350

85 140 225 400 510 700 1000 1250 1600 1850 2225 2600 2900 3350

32

55

85

135

200

290

75 125 210 330 400 650 1000 1250 1600 1850 2225 2600 2900 3350

- 105 200 300 400 650 1000 1250 1600 1850 2225 2600 2900 3350

- 80 185 280 400 650 1000 1250 1600 1850 2225 2600 2900 3350

- - 185 280 400 650 1000 1250 1600 1850 2225 2600 2900 3350

- - 165 280 400 650 1000 1250 1600 1725 2125 2450 2700 3150

- - 100 280 375 650 900 1200 1500 1600 2000 2300 2500 2900

SG20

SG15

SG15

1250

1251

1252

250 350 600 800 1100 1400 1500 1850 2150 2350 2700

ACCURACY CLASS AC20 Lock Up Pressure Class (SG)

SG30

SG30

SG30

SG30

Inlet Pressure 1244 1245 1246 1247

SG20

SG20

SG15

Spring Number 1248

1249

1263

Set Point pas (mbar)

70 mbar 140 mbar 350 mbar 700 mbar 1 bar 2 bar 3 bar 4 bar 5 bar 6 bar 7 bar 8 bar 9 bar 10 bar

14

17

25

32

55

85

135

200

290

125 175 275 375 500 750 1125 1700 2100 2250 2600 3100 3400 3800

115 175 275 400 550 800 1220 1700 2100 2250 2600 3100 3400 3800

115 175 275 450 550 850 1300 1700 2100 2250 2600 3100 3400 3800

85 175 275 450 550 850 1300 1700 2100 2325 2750 3250 3500 3900

- 175 275 450 550 850 1300 1700 2100 2400 2900 3250 3600 4000

- 175 300 475 580 950 1375 1800 2250 2575 3000 3375 3800 4250

- - 325 500 620 1050 1450 1900 2400 2750 3100 3500 4000 4500

- - 325 450 600 1000 1400 1800 2250 2525 2900 3250 3700 4150

- - 300 400 550 950 1350 1700 2100 2300 2700 3000 3400 3800

* CAPACITY TABLES (In accordance with Specification BS EN 334)

Types of Gases The capacities given in the tables are given in terms of natural gas (SG 0.6). For all other gases multiply by the following correction factor:

0.6 SG of gas handled

475 350 500 900 1300 1650 2050 2250 2650 2900 3300 3700

5


GAS PRESSURE REGULATOR SERIES 277 HI-FLO™ Dimensions & Weights

Ø350

Note: Can be rotated in steps of 45° at this point

90

235 Service 100

276

65

‘A’

48

‘B’

113

506 Service

6

354 (277H)

+13 when OPCO is not fitted

70 Tapped Rc 1/8 for ECL

301 Boss Tapped Rc 1/2 for ECL

DIMENSIONS & WEIGHTS

277

Size ‘A’ ‘B’ Wt. with OPCO kg DN 50 Flanged All dimensions in mm

95

95

17

277H

Wt. No OPCO Wt. with OPCO Wt. No OPCO kg kg kg 16.5

18

17.5


GAS PRESSURE REGULATOR SERIES 277 HI-FLO™ Sectional Arrangement

Series 277R - 309 - OPCO

Interchangeable springs

2 Way vent valve connection Rc1⁄2

Internal Relief (Optional) Boss Tapped Rc1⁄8 for ECL

Lightweight cartridge design casing assembly

External control line connection (ECL) tapped Rc1⁄2

Balanced valve assembly

Safety cut-off valve (optional)

KEY: Inlet Pressure

Outlet Pressure

All contents are subject to copyright, with the possible exception of information that is universal and/or public domain. Bryan Donkin RMG Gas Controls Limited policy is one of continuous improvement and development. The company reserves the right to change, withdraw and introduce improved designs without notice.

Atmospheric Pressure

7


For More Information To learn more about RMG's advanced gas solutions, contact your RMG account manager or visit www.rmg.com GERMANY

ENGLAND

Honeywell Process Solutions

Honeywell Process Solutions

RMG Regel + Messtechnik GmbH

Bryan Donkin RMG Gas Controls Ltd.

Osterholzstrasse 45

Enterprise Drive, Holmewood

34123 Kassel, Germany

Chesterfield S42 5UZ, England

Tel: +49 (0)561 5007-0

Tel: +44 (0)1246 501-501

Fax: +49 (0)561 5007-107

Fax: +44 (0)1246 501-500

Honeywell Process Solutions

CANADA

RMG Messtechnik GmbH

Honeywell Process Solutions

Otto-Hahn-Strasse 5

Bryan Donkin RMG Canada Ltd.

35510 Butzbach, Germany

50 Clarke Street South, Woodstock

Tel: +49 (0)6033 897-0

Ontario N4S 0A8, Canada

Fax: +49 (0)6033 897-130

Tel: +1 (0)519 5398531 Fax: +1 (0)519 5373339

Honeywell Process Solutions RMG Gaselan Regel + Messtechnik GmbH

USA

Julius-Pintsch-Ring 3

Honeywell Process Solutions

15517 Fürstenwalde, Germany

Mercury Instruments LLC

Tel: +49 (0)3361 356-60

3940 Virginia Avenue

Fax: +49 (0)3361 356-836

Cincinnati, Ohio 45227, USA Tel: +1 (0)513 272-1111

Honeywell Process Solutions

Fax: +1 (0)513 272-0211

WÄGA Wärme-Gastechnik GmbH Osterholzstrasse 45

TURKEY

34123 Kassel, Germany

Honeywell Process Solutions

Tel: +49 (0)561 5007-0

RMG GAZ KONT. SIS. ITH. IHR. LTD. STI.

Fax: +49 (0)561 5007-207

Birlik Sanayi Sitesi, 6. Cd. 62. Sokak No: 7-8-9-10

POLAND

TR - Sasmaz / Ankara, Turkey

Honeywell Process Solutions

Tel: +90 (0)312 27810-80

Gazomet Sp. z o.o.

Fax: +90 (0)312 27828-23

ul. Sarnowska 2 63-900 Rawicz, Poland Tel: +48 (0)65 5462401 Fax: +48 (0)65 5462408

R.277 2010-10 © 2010 Honeywell International Inc.


/RMG_by_Honeywell_BD__277_Hi-Flo_GB_2010-10