7.1.4 Outdoor Unit Connection

➲ Refrigerant pipe diameter before 1st branch (A,E,F) Upward Outdoor Unit total capacity [HP] 8 10 12, 16 18~22 24 26~34 36

Liquid pipe [mm(inch)] Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) Ø19.05(3/4) Ø19.05(3/4)

Gas pipe [mm(inch)] Ø19.05(3/4) Ø22.2(7/8) Ø28.58(11/8) Ø28.58(11/8) Ø34.9(13/8) Ø34.9(13/8) Ø41.3(15/8)

* High/Low Pressure Common Pipe: Ø19.05(18HP or more)

◆ Indoor Unit Connection ➲ Indoor Unit connecting pipe from branch (a,b,c,d,e,f)

21

Indoor Unit capacity [kW(Btu/h)]

Liquid pipe [mm(inch)]

Gas pipe [mm(inch)]

≤ 5.6(19,100)

Ø6.35(1/4)

Ø12.7(1/2)

< 16.0(54,600)

Ø9.52(3/8)

Ø15.88(5/8)

≤ 22.4(76,400)

Ø9.52(3/8)

Ø19.05(3/4)