Issuu on Google+

CAPACITALK MYRON ZUCKER

INC.

36825 Metro Court • Sterling Heights, MI 48312-1013 • www.myronzucker.com Phone: (586) 979-9955 / (800) 245-0583 • Fax: (586) 979-9484

No. 101

Capacitors-At-Load (CAL) Actually DO Reduce KW-Hrs

F

or years, capacitor users and specifiers have acknowledged that capacitors not only improved the billing power factor, but also reduced the KVA loads by reducing current. Many folks are not aware, however, that this current reduction takes place only from the point of connection in the electrical system back to the utility source. Thus, a bank or automatically controlled capacitor installed on the primary side of a transformer

M

M

Why waste money using

MCC

M

the system method?

M

M

When you can SAVE $ using the CAL

HARMONIC FILTERS

method?!

will indicate an improved power factor on the utility primary meter, but will not reduce the KVA load on the transformer. On the other hand, capacitors connected at the secondary of the transformer will not only indicate an improved power factor, but also will reduce the KVA load on the transformer. The capacitors will not, however, reduce any of the ampere loads downstream from the transformer. Thus, all Feeders, Bus Ducts and Branch Circuits will reflect no current reduction whatsoever. Recognition of this fact was the main reason Myron Zucker, Inc. (back in the 1950s) developed the Calmount ® brand capacitor design, to make it easy to locate capacitors at or near the motor—the chief source of poor power factor. By reducing the ampere draw of all the major motors, more electrical capacity was made available throughout the entire distribution system, and thus, more loads could be safely added. Many large plants adopted the concept and obviously realized its benefits. Myron Zucker, Inc. knew that the CAL location versus the large bank location had another benefit: it would also reduce losses for in-plant wiring, and thus, reduce the KW-Hrs readings! Yet this idea was always looked on as being quite insignificant and not worthy of any further consideration. However, a reduction in amperes has to reduce the I2R losses, reflected in both lower KVA and KW readings!

(continued on back)

POWER FACTOR CORRECTION CAPACITORS ®


“Before and After” Case History Now one of our customers has provided us with an exciting “Before and After” case history to share with you! A plant engineer at a factory in Garden Grove, California has made a careful analysis of all their power readings with no capacitors in use, and then repeated this analysis after installing capacitors on 14 of their largest HP motors. The savings are most significant! He has enthusiastically expressed the results as follows:

2500 KVA Transformer 480V Secondary

1601 924 1849 2223

Figure 1 shows the layout of the plant’s electrical system. By installing Calmount ® brand capacitors directly connected to the load side of the starter contactors, the ampere reduction is occurring from that location all the way back to the meters. This reduction results in a smaller I2R loss (or KW reduction), and thus, the $21,420.00 savings announced by the plant engineer.

100' 750 MCM Aluminum 5/Phase Individual Machine Readings Taken Here

Sub Distribution Panel B 2000 A

45' 2/0 Copper 65' 3/0 Copper 85' 4/0 Copper 105' 4/0 Copper 125' 4/0 Copper 145' 2/0 Copper 185' 4/0 Copper

#1

2–60

#2 #2

1–75 1–27.5 1–125 1–30

2–25

#3

2–75

2–27.5

#4

2–75

2–27.5

#5

2–75

2–27.5

#6

2–75

2–27.5

#8

2–75

2–27.5

numbers which confirm the CAL concept, besides improving power factor, provides such large KW-Hr savings year after year. Think about it, call us, and let’s talk about it!

INC.

We thought it important to bring this story to your attention in case you are trying to decide whether to install large KVAR banks, next to your substation or switchgear, or to follow the CAL concept in your power factor improvement plan. The significant news is the

Plant-Wide Readings Taken Here

Sub Distribution Panel 3000 A

gs

1643 1295 2092 2516

in

After

125' 750 MCM Aluminum 8/Phase

M ac h M ine ot (H or P) S iz es Ca pa (K ci VA to R) r R at

Before

“The plant-wide reading shows a savings of 42KW, which will result in an annual savings of $21,420.00. This is based on 6,000 hours of operation times a cost of $.085 per KWh. The initial investment cost was $5,801.00. The return on investment is 3.25 months.”

MYRON ZUCKER

12KV Primary

Main Switchboard 4000A Main

Plant-Wide Readings KW: KVAR: KVA: Amps:

Figure 1 — Plant Electrical System

36825 Metro Court • Sterling Heights, MI 48312-1013 • www.myronzucker.com Phone: (586) 979-9955 / (800) 245-0583 • Fax: (586) 979-9484 ®

0100


/capacitalk101