Sav flatstation design guide rev july 2013

Page 26

SAV FLATSTATIONS - DESIGN GUIDE 9.3. Capacity testing – individual FlatStations Having established adequate temperature, flow and pressure conditions in the main heating system, the hot water outputs from individual FlatStations can be adjusted and tested as required: 1.

Set the pressure reducing valves on the boosted mains water supply branches to the required value for each apartment (i.e. typically 3bar minimum such that there is sufficient pressure available to satisfy the FlatStation and downstream hot water outlets).

2. In each apartment (or selected representative apartments) open sufficient tap outlets to simulate the anticipated peak simultaneous hot water demand for the dwelling. 3. Measure the hot water temperature from the tap outlets to ensure that the temperature obtained is within expected limits, and that flow rate (and hence pressure) is adequate.

9.4. Capacity testing - district heating system In setting up the pump, it should be possible to establish maximum and minimum load operating conditions for the pump. This test should demonstrate a significant reduction in pump speed at minimum load conditions. With the system operating at its design temperature, the procedure for carrying out these tests is as follows: 1. Ensure that all radiator circuits are set to full flow i.e. all zone control valves, and radiator valves are fully open. 2. Open a sufficient number of tap outlets, starting with the most remote outlets and working back towards the pump, until the measured flow rate through the pump is equal to the calculated maximum load flow rate for the system (as calculated following the guidance in section 8.2). 3. Measure the differential pressure being generated by the pump by reference to inlet and outlet pressure gauges. Confirm and record the total flow rate leaving the pump using the flow measurement device installed on the secondary circuit main return pipe. 4. Record how long it takes to empty the buffer tank at this condition. This should be a minimum of 10 minutes. 5. Next, close all tap outlets. Override the controls to force all 2 port heating zone control valves into their fully closed positions. 6. Measure the differential pressure being generated by the pump as before, and re-measure the total flow rate leaving the pump. If the pump is being controlled properly, the pump pressure value should be close to the controlled value at the differential pressure sensor. Furthermore the flow rate should be close to the flow rate passing through the by-pass at the top of the riser.

10.0. Specification Please contact SAV Systems for further information and specification templates.

26


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.