SCPTnomRPM / nciNmlSpeed Definition: Network config input SNVT_rpm nciNmlSpeed Explanation: Is used to set the nominal motor speed. Valid range: 0 .. 65535 rpm (1 rpm) The value 0xFFFF represents invalid data. Default value: Read from the drive. Otherwise 0. SCPTnomFreq / nciNmlFreq Definition: Network config input SNVT_freq_hz nciNmlFreq Explanation: Is used to set the nominal frequency of the motor. Valid range: 0 .. 6553.5 Hz (0.1 Hz) Default value: Read from the drive. Otherwise 0.