CONTROL PANELS FOR 1 THREEPHASE ELECTRIC PUMP WITH THERMAL PROTECTION
QTDE10/...kW-T Electromechanic Direct start Control panel for 1 Three-phase electric pump with Thermal protection
Three-phase panels for control of 1-4 electric pumps are proposed with thermal or ammetric protection. Ammetric protection allows with a single model to cover 50/60% of the range of the correspondent thermal protection panels with power from 0,37 kW to 22 kW .
CONNECTION DIAGRAM
A
P
B
GENERAL CHARACTERISTICS: DESIGNED FOR FITTING OF: – Electromechanic control panel; – Power supply 3~ 50/60Hz 400V ±10%; – 24V voltage inputs for external control from pressure switch or float switch; – Cam switch for automatic-off-manual working; – Main pilot light; – Motor operator light; – Protected motor light; – Motor protection fuses; – Contactor with thermal relay internally resetable; – Auxiliary protection fuses; – General disconnecting switch with door lock; – Thermoplastic box (up to 16kW) or metal box (from 18,5kW to 22kWHp); – Protected to IP 55.
– CLU/3S-24V code 632.311 (see last pages): undecal base level control for 3 probes, more undecal base wired ZUC/CLU-3S code 225.23 (see page 71) it always must be bound together to the level control.
OPERATING CONDITIONS: – Ambient temperature -5/+40°C – Relative moisture 50% with a max temperature of 40°C.
N.B: The addition of the level control module from 7kW to 10kW requires the change of the box. Please consider an increase of Euro 20,00 price list. For panels over 10 kW contact our technical / sales dep.
TECHNICAL DATA AND OPERATING POWERS APPROX POWER AT 230V Hp
CURRENT ABSORPTION (A) MIN
CURRENT ABSORPTION (A) MAX
WEIGHT kg
DIMENSIONS mm A
DIMENSIONS mm B
DIMENSIONS mm P
0,37
0,5
0,9
1,3
4
340
235
160
0,55
0,75
1,4
1,9
4
340
235
160
0,75 - 1,1
1 - 1,5
2
3
4
340
235
160
2
3
4,5
4
340
235
160
2,5 - 3
4,5
5,8
4
340
235
160
6
8
4
340
235
160
5,5 - 7,5
9
13,5
4,2
340
235
160
8 - 9,5
14
18
4,2
340
235
160
7,5 - 10
10 - 14
17
22
4,2
340
235
160
11 - 13,5
15 - 18
20
29
5,5
430
315
165
35
5,5
430
315
165
45
11,5
450
340
185
11,8
450
340
185
MODEL
CODE
APPROX POWER AT 230V kW
QTDE10/0,37kW-T
235.21
QTDE10/0,55kW-T
235.22
QTDE10/1,1kW-T
235.23
QTDE10/1,5kW-T
235.24
1,5
QTDE10/2,2kW-T
235.25
1,8 - 2,2
QTDE10/3,7kW-T
235.26
3 - 3,7
4-5
QTDE10/5,5kW-T
235.27
4 - 5,5
QTDE10/7kW-T
235.28
6-7
QTDE10/10kW-T
235.29
QTDE10/13,5kW-T
235.30
QTDE10/16kW-T
235.33
15 - 16
20 - 22
28
QTDE10/18,5kW-T
235.31
18,5
25
35
QTDE10/22kW-T
235.32
22
30
46
56
For QTDE10/ from 30kW to 132kW contact our technical/sales office
NOTES: the value of the power rating is indicative, for a correct choice of the model, pls-check that motor ampere absorption is within thermal protection value. For possible variations to normal system, please contact our technical/sales office. MANIERO ELETTRONICA reserves the right to improve its products without prior notice. The addition of modules can lead to variations in the size of the box and the overall cost of the control panel.
www.manieroelettronica.it
19