Catalogue Emergency Lighting

Page 207

Emergency Lighting | Luminaires for central emergency power supply Series: Centryxx Type of protection: IP 20 (Wall (surface)), IP 40 (Ceiling (recessed)) Protection class: I Voltage: 220 - 240 V / 0 Hz, 50 - 60 Hz For escape route illumination Housing: die-cast aluminium, powder-coated; transparent plastic diffuser for optimum illumination of escape route. Ballast: EB Available colour (X): 2 = white

Ceiling (surface)

Ceiling (recessed), square

Ceiling (recessed), round

B

B

HE

HE

L

H

DA L

H

DA D

H

51

180

Ø5

Ø200

90

Ø185

Ø200

Ø185

Ø5

90 180

TWINControl (.72)

SINGLEControl (.81)

DUOControl (.82)

1 x LED 3 W

-

-

-

L 180, B 180, H 27

square

1 x LED 3 W

-

-

-

L 220, B 220, H 3 DA 185, HE 73

round

1 x LED 3 W

-

-

-

D 200, H 3 DA 185, HE 73

Type of installation

671841.00X.Y

Ceiling (surface)

square

671839.00X.Y

Ceiling (recessed)

671837.00X.Y

Ceiling (recessed)

Planning guide: Escape route illumination in accordance with EN 1838

Type

Lamp/Wattage

Table applies to all Centryxx series luminaires

Spacing table 671841.002

Lamp luminous flux:

a b

c

d

h

E = 1 lx along the centre line

Dimensions

Control 1 (.71)

Article number

Mains: 180 lm, Emergency: 180 lm The following values are indicated in m h

a

b

2.5

3.4

0.9 12.6

c

5.6

d

3.0

3.0

0.8 14.2

6.4

3.5

2.6

0.7 16.1

7.1

4.0

2.4

0.0 10.5

0.0

For connecting diagrams, see pages 119 - 121 | Catalogue number explanations: see page 276 Tender texts available upon request | Specifications subject to alteration

205