Emergency Lighting | Luminaires for central emergency power supply Series: Centryxx Type of protection: IP 20 (Wall (surface)), IP 40 (Ceiling (recessed)) Protection class: I Voltage: 220 - 240 V / 0 Hz, 50 - 60 Hz For escape route illumination Housing: die-cast aluminium, powder-coated; transparent plastic diffuser for optimum illumination of escape route. Ballast: EB Available colour (X): 2 = white
Ceiling (surface)
Ceiling (recessed), square
Ceiling (recessed), round
B
B
HE
HE
L
H
DA L
H
DA D
H
51
180
Ø5
Ø200
90
Ø185
Ø200
Ø185
Ø5
90 180
TWINControl (.72)
SINGLEControl (.81)
DUOControl (.82)
1 x LED 3 W
-
-
-
•
L 180, B 180, H 27
square
1 x LED 3 W
-
-
-
•
L 220, B 220, H 3 DA 185, HE 73
round
1 x LED 3 W
-
-
-
•
D 200, H 3 DA 185, HE 73
Type of installation
671841.00X.Y
Ceiling (surface)
square
671839.00X.Y
Ceiling (recessed)
671837.00X.Y
Ceiling (recessed)
Planning guide: Escape route illumination in accordance with EN 1838
Type
Lamp/Wattage
Table applies to all Centryxx series luminaires
Spacing table 671841.002
Lamp luminous flux:
a b
c
d
h
E = 1 lx along the centre line
Dimensions
Control 1 (.71)
Article number
Mains: 180 lm, Emergency: 180 lm The following values are indicated in m h
a
b
2.5
3.4
0.9 12.6
c
5.6
d
3.0
3.0
0.8 14.2
6.4
3.5
2.6
0.7 16.1
7.1
4.0
2.4
0.0 10.5
0.0
For connecting diagrams, see pages 119 - 121 | Catalogue number explanations: see page 276 Tender texts available upon request | Specifications subject to alteration