ΣΥΜΒΑΤΙΚA ΣΥΣΤHΜΑΤΑ CONVENTIONAL ΠΥΡΑΝIΧΝΕΥΣΗΣ FIRE DETECTION SYSTEMS
www.olympia-electronics.gr
FIRE DETECTION PANELS WITH 2, 4 & 6 ZONES TYPE
DESCRIPTION
PICTURE
CODE
B B B
921163200 921163400 921163600
BS-1632 BS-1634 BS-1636
PRICE
2 zone fire detection panel 4 zone fire detection panel 6 zone fire detection panel
145,00 € 192,00 € 260,00 €
TECHNICAL SPECIFICATIONS FOR 2, 4 & 6 ZONES FIRE DETECTION PANELS
BS-1632
BS-1634
BS-1636
CODE DESCRIPTION OPERATION VOLTAGE CONSUMPTION BATTERY CHARGING CIRCUIT DURATION
921163200 2 zone fire detection panel
921163400 4 zone fire detection panel
921163600 6 zone fire detection panel
ZONE CIRCUITS
2 circuits monitored for short and open circuit conditions (max. current 35mA)
TYPE
220-240VAC/50Hz 50 VA Two 12V Lead acid sealed 2.6Ah Stabilized power supply 27.6V / max. 400mA 72 hours (Maximum connected detectors 72 and no load at output 24VM and 24VP) 4 circuits monitored for short and open circuit conditions (max. current 35mA)
6 circuits monitored for short and open circuit conditions (max. current 35mA)
ALARM CIRCUITS
Two 24V circuits that are monitored for open and short circuit conditions (maximum current 300mA each). Each output is protected with a self-reseting electronic fuse.
OUTPUTS RELAYS
Three relays contacts are rated at 30VDC and 5A maximum each. Under no circumstances should voltages or currents outside limits be connected. All relays output must be protected with a fuse of the same rating.
WEIGHT(without battery) PROD. IN ACCORDANCE WITH
2040gr (4030gr with battery)
EN 54-2, EN 54-4
CONVENTIONAL FIRE DETECTION PANEL WITH 6 ZONES TYPE
BS-636
PICTURE
CODE
A
921636000
DESCRIPTION
PRICE
6 zone fire detection panel
265,00 €
TECHNICAL SPECIFICATIONS FOR FIRE DETECTION PANEL WITH 6 ZONES
BS-636 BS-636
TYPE
921636000 6 zones fire detection panel
CODE DESCRIPTION OPERATION VOLTAGE CONSUMPTION BATTERY CHARGING CIRCUIT DURATION ZONE CIRCUITS ALARM CIRCUITS OUTPUTS
220-240VAC/50Hz 48 VA 12V/7Ah 13.8V / 400mA 36 hours (without using the outputs 24V_M and 24V_P) 6 zones Two 24V circuits that are monitored for open and short circuit conditions 1 Alarm relay, 1 relay per zone , 24V permanent 24V reset interrupted Ο
0 up to 50 C Up to 95% relative humidity
OPERATION TEMPERATURE HUMIDITY WEIGHT(without battery) PROD. IN ACCORDANCE WITH
2040gr (4030gr with battery)
EN 54-2, EN 54-4
PERIPHERAL DEVICES TYPE
PICTURE
A-632*
CODE
980163200
DESCRIPTION
PRICE
Recess wall mounting base for BS-1632/1634/1636/636
90,00 €
* Trade products
71