Fire Resistant Cables

Page 1

FIRE RESISTANT CABLES


CONTENT Introduction_________________________________________________2 Fire Resisitant Cable_________________________________________2 INTERNATIONAL STANDARD COMPLIANCE_ ________________________3 CERTIFICATIONS________________________________________________3 CONSTRUCTION OF CABLES_ ____________________________________4 Single Core Armour__________________________________________5 Multi-Core UNArmour_ _______________________________________6 Multi-Core Armour___________________________________________7

1


INTRODUCTION

Today, LCIB has one of the most advanced facilities for the manufacturing of XLPE / PVC insulated Fire Resistant cables in the Asia-Pacific region. XLPE / PVC insulated Fire Resistant cables manufactured by LCIB are internationally renowned for its world-class quality standard. Fire Resistant cables manufactured by LCIB provide flexibility, resistance to high temperatures and resistance to combustion with low toxicity, low smoke and low acid gas generation. This catalog serves as a guide to LCIB’s manufacturing processes and standards in the production of Fire Resistant cables.

FIRE RESISTANT CABLES

In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the use of fire resistant and non-halogenated cables. These cables provide the following characteristics :

High fire resistance

Long-term circuit integrity in a fire

Low smoke and toxic gas emissions

Flame retardant properties

Zero halogen gases

Ease and low cost of installation

Fire Resistant cables are used, where required by local fire codes, in the wiring of :

2

Fire resistant safety circuits

Public address and emergency voice communication systems in high-rise buildings

Control and instrumentation services in industrial, commercial and residential complexes

High-temperature installation conditions


INTERNATIONAL STANDARD COMPLIANCE The Fire Resistant cables manufactured by LCIB complied with either one or combination of the specification as below: - BS 6387 - IEC 60331 Fire Resistant Test - IEC 60332-3 Cat A, B, C Flame Propagation Test - IEC 61034 Smoke Emission Test - IEC 60754 Halogen Content Test The Fire Resistant cables are categorized by a letter symbol (e.g. A) or series of symbols (e.g. CWZ) according to the requirements for the resistance characteristics which they meet according to BS 6387. Classification

Symbol

a) Resistance to fire alone 650°C for 3 hours

A

750°C for 3 hours

B

950°C for 3 hours

C

950°C for 20 minutes (short duration)

S

b) Resistance to fire with water

W

c) Resistance to fire with mechanical shock 650°C

X

750°C

Y

950°C

Z

CERTIFICATIONS The following certifications/type tests and approvals have been obtained by LCIB: Sirim QAS Sdn Bhd • Quality System Registration Certificate MS ISO 9002: 1994 Quality Systems • Product Certification Licence Jabatan Bomba Dan Penyelamat Malaysia • Testing of Fire Resistant Cables to IEC 60332-3 & BS 6387 Singapore Productivity and Standards Board (PSB) • Testing of Fire Resistant cables to BS 6387 & IEC 60332-1 KEMA Registered Quality Nederland BV • Testing of Fire Resistant Cables to BS 6387, IEC 60332-3, IEC 60754-1, IEC 60754-2, IEC 61034

3


Construction Conductors Class 2 Plain annealed copper wire to BS 6360 Fire resistance barrier Mica tape Insulation Extruded cross-linked polyethylene (XLPE) at 90째C *Bedding Extruded low smoke non halogen compound/PVC compound *Armour Galvanised steel wire armour for multi-core cable/Aluminium wire armour for single core cable spirally applied over the bedding. Outer sheath Extruded low smoke non halogen compound/ PVC compound * Not applicable for unarmoured power cable. Note: Sheathing material may be provided based on customer testing requirements.

Single Core Armour

Multi-Core Armour

Multi-Core UNArmour 4


Single Core Armour IEC 60502-1

MICA/XLPE - ARMOURED POWER CABLE Conductor

No. of core

1

IEC 60502-1

1

Nominal diameter Outersheath of nominal aluminium thickness wire

Cross sectional area

Standing No. /Dia. of cond

Approx. OD

Insulation nominal thickness

mm2

No./mm

mm

mm

mm

mm

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85 61/3.20 61/3.64

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3 26.2 29.8

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4

6.5 7.0 7.5 8.1 9.0 9.6 11.2 12.3 13.7 15.5 17.2 18.9 20.8 22.9 25.5 27.9 31.5 34.8 38.8

1.04 1.04 1.04 1.04 1.04 1.04 1.04 1.04 1.25 1.25 1.25 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0

Approx. overall diameter

Approx. weight

Max. DC resistance at 20째C

mm

mm

kg/km

Ohm/km

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.9 2.1 2.2 2.3

12.4 12.8 13.4 14.0 14.9 15.5 17.1 18.2 20.0 21.8 23.5 25.9 27.8 29.9 32.7 35.1 39.9 43.4 47.6

205 224 253 284 348 415 545 663 839 1084 1373 1715 2031 2449 3099 3753 4846 5934 7415

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

MICA/XLPE - UNARMOURED POWER CABLE Conductor

No. of core

Approx. diameter under armour

0.6/1 (1.2)kV

Cross sectional area

Standing No. /Dia.of cond

Approx. OD

Insulation nominal thickness

mm2

No./mm

mm

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85 61/3.20 61/3.64

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3 26.2 29.8

0.6/1 (1.2)kV

Outersheath nominal thickness

Approx. overall diameter

Approx. weight

Max. DC resistance at 20째C

mm

mm

mm

kg/km

Ohm/km

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.8 1.9 2.0 2.2

7.3 7.8 8.3 8.9 9.8 10.4 12.0 13.1 14.5 16.3 18.2 19.9 22.0 24.1 26.9 29.5 32.9 36.4 40.8

69 82 102 127 175 234 340 443 573 789 1059 1311 1606 1985 2590 3213 4077 5096 6505

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

5


Multi-Core UNArmour IEC 60502-1

MICA/XLPE - UNARMOURED POWER CABLE Conductor Cross sectional area

Standing No. /Dia.of cond

Approx. OD

Insulation nominal thickness

mm2

No./mm

mm

mm

2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

3

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3

4

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3

No. of core

6

0.6/1 (1.2)kV

Outersheath nominal thickness

Approx. overall diameter

Approx. weight

Max. DC resistance at 20째C

mm

mm

kg/km

Ohm/km

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9

12.6 13.4 14.5 15.6 17.5 18.7 21.9 24.1 26.8 30.5 34.3 37.9 41.9 46.3 51.9 57.1 63.9

174 207 255 315 429 562 825 1064 1371 1875 2510 3116 3808 4719 6133 7593 9625

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.1

13.2 14.1 15.3 16.5 18.5 19.8 23.2 25.7 28.5 32.7 36.7 40.5 44.9 49.7 55.7 61.3 68.9

204 248 311 391 546 735 1080 1410 1851 2571 3440 4284 5263 6535 8519 10568 13464

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.8 3.0 3.3

14.4 15.4 16.7 18.0 20.3 21.7 25.6 28.3 31.7 36.4 40.8 45.2 50.0 55.5 62.1 68.4 76.7

246 302 384 487 689 937 1385 1818 2385 3344 4478 5602 6856 8544 11146 13846 17615

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470


Multi-Core Armour IEC 60502-1

MICA/XLPE - ARMOURED POWER CABLE Conductor

Approx. diameter under armour

0.6/1 (1.2)kV Nominal diameter Outersheath of nominal aluminium thickness wire

Cross sectional area

Standing No. /Dia. of cond

Approx. OD

Insulation nominal thickness

mm2

No./mm

mm

mm

mm

mm

2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2

11.0 11.8 12.9 14.0 15.9 17.1 20.3 22.5 25.2 28.9 32.8 36.1 39.9 44.5 49.7 54.9 61.3

0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 2 2 2 2.5 2.5 2.5 2.5

3

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2

11.6 12.6 13.7 14.9 16.9 18.2 21.7 24.1 27.0 31.3 35.1 38.7 43.2 47.7 53.7 58.9 65.8

4

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400

7/0.53 7/0.67 7/0.85 7/1.04 7/1.35 7/1.70 7/2.14 19/1.53 19/1.78 19/2.14 19/2.52 37/2.03 37/2.25 37/2.52 61/2.25 61/2.52 61/2.85

1.6 2.0 2.6 3.1 4.1 4.6 5.8 7.0 8.1 9.7 11.5 12.9 14.3 16.1 18.4 20.6 23.3

0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0

12.8 13.8 15.1 16.5 18.7 20.1 24.0 26.7 29.9 34.8 39.0 43.4 48.0 53.1 59.7 65.6 73.7

No. of core

Approx. overall diameter

Approx. weight

Max. DC resistance at 20째C

mm

mm

kg/km

Ohm/km

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.8 3.1

16.5 17.4 18.5 19.6 22.2 23.3 27.3 29.5 32.2 36.3 41.2 45.4 49.4 55.5 61.0 66.5 73.5

470 520 595 680 960 1135 1650 1975 2385 3070 4175 4910 5805 7485 9215 10970 13475

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047

0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 2 2 2 2.5 2.5 2.5 2.5 2.5

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.8 3.0 3.2

17.2 18.2 19.3 20.5 23.2 24.5 28.7 31.1 34.2 39.5 43.7 48.2 54.1 58.9 65.3 70.9 78.2

520 585 675 785 1125 1350 1985 2405 2960 4190 5255 6260 7970 9520 11930 14330 17630

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047

0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.15

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.8 3.0 3.2 3.5

18.4 19.4 20.7 22.8 25.0 27.1 31.0 33.9 37.3 43.4 48.5 54.4 59.1 64.7 71.8 78.0 88.0

570 655 760 1025 1325 1780 2385 2940 3650 5170 6475 8320 9900 11890 15000 18030 23385

12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.047

7


Leader Cable Industry Berhad (26936-P)

Lot 1385, Tikam Batu Industrial Estate 08600 Sungai Petani, Kedah, Malaysia Tel: 604-438 9988 Fax: 604-438 8497 www.leadercable.com.my Selangor Sales Office Unit 8.2, Level 8, Building A, Peremba Square Saujana Resort, Seksyen U2 40150 Shah Alam, Selangor, Malaysia. Tel: 603-7845 7788/6699 Fax: 603-7845 2258/8323


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.