Page 1

Guardian Home Inspections Cover Page

Property Inspection Report

123 Main Street, Austin Texas, 78726 Inspection prepared for: John Doe Inspection Date: 8/3/2011 Time: 7:30am Age: 8 years Size: 2,197 sq. ft. Weather: HOT / DRY Single story, slab on grade Inspector: Kevin Prellop TREC License #20021 8225 FM 620 N #2035, Austin, TX 78726 Phone: (512) 680.0336 Email: info@guardianaustin.com www.GuardianAustin.com


Guardian Home Inspections

123 Main Street, Austin, Texas

PROPERTY INSPECTION REPORT Prepared For:

John Doe (Name of Client)

Concerning:

123 Main Street, Austin Texas, 78726 (Address or Other Identification of Inspected Property)

By:

Kevin Prellop, TREC License #20021

8/3/2011

(Name and License Number of Inspector)

Date

This property inspection report may include an inspection agreement (contract), addenda, and other information related to property conditions. If any item or comment is unclear, you should ask the inspector to clarify the findings. It is important that you carefully read ALL of this information. This inspection is subject to the rules (“Rules”) of the Texas Real Estate Commission (“TREC”), which can be found at www.trec.state.tx.us. The TREC Standards of Practice (Sections 535.227-535.233 of the Rules) are the minimum standards for inspections by TREC-licensed inspectors. An inspection addresses only those components and conditions that are present, visible, and accessible at the time of the inspection. While there may be other parts, components or systems present, only those items specifically noted as being inspected were inspected. The inspector is not required to move furnishings or stored items. The inspection report may address issues that are code-based or may refer to a particular code; however, this is NOT a code compliance inspection and does NOT verify compliance with manufacturer’s installation instructions. The inspection does NOT imply insurability or warrantability of the structure or its components. Although some safety issues may be addressed in this report, this inspection is NOT a safety/code inspection, and the inspector is NOT required to identify all potential hazards. In this report, the inspector will note which systems and components were Inspected (I), Not Inspected (NI), Not Present (NP), and/or Deficient (D). General deficiencies include inoperability, material distress, water penetration, damage, deterioration, missing parts, and unsuitable installation. Comments may be provided by the inspector whether or not an item is deemed deficient. The inspector is not required to prioritize or emphasize the importance of one deficiency over another. Some items reported as Deficient may be considered life-safety upgrades to the property. For more information, refer to Texas Real Estate Consumer Notice Concerning Recognized Hazards, form OP-I. This property inspection is not an exhaustive inspection of the structure, systems, or components. The inspection may not reveal all deficiencies. A real estate inspection helps to reduce some of the risk involved in purchasing a home, but it cannot eliminate these risks, nor can the inspection anticipate future events or changes in performance due to changes in use or occupancy. It is recommended that you obtain as much information as is available about this property, including any seller’s disclosures, previous inspection reports, engineering reports, building/remodeling permits, and reports performed for or by relocation companies, municipal inspection departments, lenders, insurers, and appraisers. You should also attempt to determine whether repairs, renovation, remodeling, additions, or other such activities have taken place at this property. It is not the inspector’s responsibility to confirm that information obtained from these sources is complete or accurate or that this inspection is consistent with the opinions expressed in previous or future reports. Promulgated by the Texas Real Estate Commission (TREC) P.O. Box 12188, Austin, TX 787112188, 1-800-250-8732 or (512) 459-6544 (http://www.trec.state.tx.us). REI 7-2 (8/09)

REI 7-2 (8/09)

Page 1 of 36


Guardian Home Inspections

123 Main Street, Austin, Texas

ITEMS IDENTIFIED IN THE REPORT DO NOT OBLIGATE ANY PARTY TO MAKE REPAIRS OR TAKE OTHER ACTIONS, NOR IS THE PURCHASER REQUIRED TO REQUEST THAT THE SELLER TAKE ANY ACTION. When a deficiency is reported, it is the client’s responsibility to obtain further evaluations and/or cost estimates from qualified service professionals. Any such follow-up should take place prior to the expiration of any time limitations such as option periods. Evaluations by qualified tradesmen may lead to the discovery of additional deficiencies which may involve additional repair costs. Failure to address deficiencies or comments noted in this report may lead to further damage of the structure or systems and add to the original repair costs. The inspector is not required to provide follow-up services to verify that proper repairs have been made. Property conditions change with time and use. For example, mechanical devices can fail at any time, plumbing gaskets and seals may crack if the appliance or plumbing fixture is not used often, roof leaks can occur at any time regardless of the apparent condition of the roof, and the performance of the structure and the systems may change due to changes in use or occupancy, effects of weather, etc. These changes or repairs made to the structure after the inspection may render information contained herein obsolete or invalid. This report is provided for the specific benefit of the client named above and is based on observations at the time of the inspection. If you did not hire the inspector yourself, reliance on this report may provide incomplete or outdated information. Repairs, professional opinions or additional inspection reports may affect the meaning of the information in this report. It is recommended that you hire a licensed inspector to perform an inspection to meet your specific needs and to provide you with current information concerning this property. ADDITIONAL INFORMATION PROVIDED BY INSPECTOR -A complimentary maintenance guide should have been given to you following your inspection. This book contains valuable information and maintenance advice critical to understanding the report and the property. If you did not receive the maintenance guide, please contact our office to arrange delivery. -If the property inspected is a condominium or townhouse; systems, components or aspects of the property may not be accessible and / or may be outside the scope of this inspection (i.e. common areas, attics, roofs, foundations, etc.). Typically, a homeowners association is responsible for exterior repairs and maintenance. If problems are experienced with the roof, foundation, exterior wall coverings, common plumbing, et al., the association should be informed immediately. -If the property is occupied at the time of inspection; personal belongings, stored items, furniture, etc. may prevent complete observation of some aspects, systems, components or appliances. It is beyond the scope of this inspection to move or disrupt any such items and further evaluation is recommended. A return visit is not included in the price of the initial inspection. -We recommend that you get repair bids form at least three qualified service professionals for any system, component or appliance with the “Deficiency” box checked. Other problems may be discovered that were not noted during this limited visual evaluation. THE CONTENTS OF THIS REPORT ARE BASED ON THIS INSPECTORS PERSONAL EXPERIENCE AND OPINIONS.

Conditions present at the time of inspection: Precipitation: None Temperature: 85 degrees Natural gas: On Electric: On Water: On House faces: East Present at inspection: Buyers Approximate Age: 8 years Additional pages may be attached to this report. Read them carefully. This report may not be REI 7-2 (8/09) Page 2 of 36


Guardian Home Inspections

123 Main Street, Austin, Texas

complete without the attachments. If an item is present in the property but is not inspected, the “NI� column will be checked and an explanation is necessary. Comments may be provided by the inspector whether or not an item is deemed in need of repair.

REI 7-2 (8/09)

Page 3 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

I. STRUCTURAL SYSTEMS X

A. Foundations NOTE: FOUNDATION ON CLAY SOIL REQUIRES ADEQUATE AND EVEN MOISTURE AROUND PERIMETER OF THE FOUNDATION THE ENTIRE YEAR TO PREVENT MOVEMENT. TREES AND SHRUBS CAN CAUSE FOUNDATION DAMAGE WHEN GROWING TOO CLOSE. WATER SHOULD NOT BE PERMITTED TO POND OR ERODE UNDER OR ALONGSIDE ANY PART OF THE FOUNDATION. DEPENDING ON THE DESIGN AND METHOD OF ORIGINAL CONSTRUCTION OF A PIER AND BEAM FOUNDATION, THE FLOOR SYSTEM MAY NEED LEVELING PERIODICALLY. HAIRLINE CRACKS OR CORNER POPS MAY HAVE BEEN OBSERVED THAT ARE NOT INDIVIDUALLY NOTED. THIS TYPE OF CRACKING IS TYPICALLY THE RESULT OF SHRINKAGE OF THE CONCRETE AS IT CURES AND IS NOT TYPICALLY CAUSE FOR ALARM. THESE AREAS SHOULD BE MONITORED.

Type of Foundation: Slab on Grade Comments: An informal elevation survey as well as a visual examination of the visible exterior slab, framing connections, window, door and wall conditions indicated that the foundation appears to be performing within acceptable standards at the time of inspection. Some differential settlement and surface cracking may be acceptable. The amount of movement does not appear to suggest a serious structural problem at this time - although no benchmark of the original foundation was given and/or most foundations are poured or built with some out-of-levelness. This area should, of course, be monitored and maintained with proper grading and moisture control. The purpose of the foundation is to provide a stable base for the building, which in my opinion, it appears to be doing. The need for foundation repair in some cases can be an aesthetic judgment that must be made by the homeowner or buyer. The rate of movement cannot be predicted during a one-time inspection and continual observation is recommended.

REI 7-2 (8/09)

Page 4 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

B. Grading & Drainage

X

NOTE: FOUNDATION AREA-SURFACE OR SUBSURFACE DRAINS ARE NOT TESTED. WATER SHOULD NOT POND WITHIN 10 FEET OF THE FOUNDATION. THE GROUND SHOULD SLOPE AWAY FROM THE FOUNDATION AT A RATE OF 1-INCH PER FOOT FOR 610 FEET. IF PROPER GRADING CANNOT BE REASONABLY ACCOMPLISHED, A DRAINAGE SWALE, SUBSURFACE DRAIN OR SIMILAR SYSTEM TYPICALLY ACHIEVE THE DESIRED RESULT. A 4-8 INCH CLEARANCE SHOULD BE MAINTAINED BETWEEN FINISH GRADE AND TOP OF FOUNDATION WALL.

Comments: Grading acceptable around structure Recommend removal or separation of stones from current location in backyard. Current location facilitates water ponding and/or insect infestation, although none visible at time of inspection

Maintenance Issue: Downspout missing extension and/or splash block. Rainwater is pooling at corner of foundation, which can lead to future issues. Extend downspout 4-6 feet away from foundation wall or install splash block to divert water away from foundation.

Grading acceptable around structure

REI 7-2 (8/09)

Page 5 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Maintenance Issue: Downspout missing extension and/or splash block. Rainwater is pooling at corner of foundation, which can lead to future issues. Extend downspout 4-6 feet away from foundation wall or install splash block to divert water away from foundation.

REI 7-2 (8/09)

Recommend removal or separation of stones from current location in backyard. Current location facilitates water ponding and/or insect infestation, although none visible at time of inspection

Page 6 of 36


Guardian Home Inspections I=Inspected I X

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D X C. Roof Covering Materials NOTE: WEATHER CONDITIONS, WIND, HAIL AND EXTREME TEMPERATURES AFFECT ALL ROOFING FROM DAY TO DAY. CONTINUAL OBSERVATION IS RECOMMENDED. MOST ROOF FASTENERS ARE NOT READILY ACCESSIBLE OR VISIBLE AND ARE BEYOND THE SCOPE OF THIS INSPECTION. GUTTERS MAY BE DESIRABLE AND SHOULD NOT DISCHARGE ONTO THE ROOF SURFACE AND SHOULD BE CLEANED TO PREVENT SPILL OFF, WHICH COULD CREATE A POTENTIAL LEAK. ALL DOWNSPOUTS SHOULD DISCHARGE AWAY FROM THE FOUNDATION. THE ROOF IS WALKED UNLESS OTHERWISE NOTED.

Type(s) of Roof Covering: Single layer composition shingles over solid decking Comments: A limited cursory visual roofing inspection was performed to determine if the roof membrane was in need of immediate repairs. To determine the serviceability of the roofing membrane, the desired performance characteristics should be defined. In the inspector's opinion, this type of roof membrane must possess many performance characteristics, and a few are: 1) To be installed properly 2) The ability to shed water 3) Resist rapid deterioration 4) Provide a pleasing attractive appearance The purpose of this report was to determine the roofing membrane's ability to shed water so as to prevent viewable (when walking through the structure) water stains on the interior wall/ceiling surfaces within the living area of the house. It is not within the scope of this level of inspection to determine the point of origin and/or path through the structure. A more sophisticated and/or diagnostic type of inspection procedure would address the issues noted in items 1-3. Item 4 is very subjective and can be defined only by the observer.

Maintenance Issues: - Evidence of north and south side ponding due to inadequate shedding of rainwater from change in roof slope. Recommend installing gutters to prevent water from compromising the foundation backfill. - Evidence of water penetration behind gutters. It's possible gutters were installed as a result of such damage, or problem is because of faulty gutters. Monitor gutter system performance at next rainfall. - Seal penetrations at satellite dish on south side of roof to prevent moisture penetration. - Granules observed in gutter system. Clogged gutters could impede gutter performance, leading to leaks. I recommend cleaning of the gutters. Shingle REI 7-2 (8/09)

Page 7 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D surface immediately above them may have been compromised, evident by granule loss. Continue to monitor. - Missing drip edge at eaves. A drip edge can aid in the prevention of water being wicked up by the vulnerable fascia.

- Evidence of north and south side ponding due to - Evidence of water penetration behind gutters. It's possible inadequate shedding of rainwater from change in roof slope. gutters were installed as a result of such damage, or Recommend installing gutters to prevent water from problem is because of faulty gutters. Monitor gutter system compromising the foundation backfill. performance at next rainfall.

- Seal penetrations at satellite dish on south side of roof to prevent moisture penetration.

REI 7-2 (8/09)

Page 8 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

- Granules observed in gutter system. Clogged gutters could impede gutter performance, leading to leaks. I recommend cleaning of the gutters. Shingle surface immediately above them may have been compromised, evident by granule loss. Continue to monitor.

- Missing drip edge at eaves. A drip edge can aid in the prevention of water being wicked up by the vulnerable fascia.

REI 7-2 (8/09)

Page 9 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

D. Roof Structure & Attic

X

NOTE: ATTICS ARE NOT TOTALLY OBSERVABLE. FRAMING CONNECTIONS ARE CHECKED FOR EVIDENCE OF SIGNIFICANT STRUCTURAL DISTRESS. MINOR FRAMING DEFICIENCIES OR INCONSISTANCIES MAY BE PRESENT THAT DO NOT AFFECT THE OVERALL STRUCTURAL INTEGRITY. FRAMING, VENTILATION AND INSULATION ARE CONSIDERED ADEQUATE UNLESS OTHERWISE NOTED OR HIGHLIGHTED BELOW.

Approximate average thickness of insulation: 13 inches Approximate average thickness of vertical insulation: Not determined - The attic was entered and viewed from various readily accessible areas. Comments: Radiant barrier installed

Maintenance Issue: Nails should be removed from attic access door frame to allow for a complete seal of attic door, preventing dangerous exhaust gases from entering the attic.

Approximate thickness of insulation is 13 inches.

REI 7-2 (8/09)

Radiant barrier installed

Page 10 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Maintenance Issue: Nails should be removed from attic access door frame to allow for a complete seal of attic door, preventing dangerous exhaust gases from entering the attic.

REI 7-2 (8/09)

Page 11 of 36


Guardian Home Inspections I=Inspected I X

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D X E. Walls (Interior and Exterior) NOTE: CRACKS CAN BE EXPECTED TO DEVELOP AT OR AROUND DRYWALL JOINTS AND SEAMS OR IN BRICK MORTAR OVER TIME. THIS IS TYPICALLY DUE TO THE SETTLING OF THE FOUNDATION AND IS GENERALLY CONSIDERED NORMAL AND MAY CHANGE SEASONALLY. CRACKS ABOVE DOORS OR WINDOWS OR AT MORTAR JOINTS IN MASONRY VENEERS GREATER THAN 1/8 - 1/4 - INCH IN WIDTH CAN INDICATE GREATER THAN NORMAL AMOUNTS OF MOVEMENT WITHIN THE STRUCTURE AND MAY NEED FURTHER EVALUATION. PROPER WATER MAINTENANCE AND GRADING OF THE SOIL AROUND THE HOUSE WILL BE CRUCIAL IN THE FUTURE PERFORMANCE OF THE FOUNDATION. PLEASE NOT THAT WE DO NOT VERIFY THE PRESENCE OF CHINESE DRYWALL.

Interior walls are made of Drywall Exterior walls are clad with brick veneer and hardboard Comments: - Interior: Observation of the interior gypsum board ("drywall" or "sheetrock") wall and ceiling surfaces revealed the standard workmanship for a structure of this age. This type of construction reflects any frame movement and/or foundation movement by cracking and/or joint distortions appearing in the surface. No evidence of significant distortions and/or cracks were observed at the time of inspection but cosmetic appearing drywall and/or tape seam cracks or imperfections may have been observed that are not individually noted. This condition would suggest that major foundation movement does not appear to have occurred since the surfaces were last painted. - Exterior Siding: Hardboard, wood, or cement board siding is very flexible and does not typically reflect movement as readily as does a more brittle material such as masonry; therefore, observation of this type of wall surface does not generally reveal any evidence of the residence's structural behavior.

Maintenance Issues: - Evidence of moisture entering structure at north window. Seal all exterior holes, gaps, penetrations, etc.with an exterior-grade sealant to help prevent excess moisture and/or vermin entry. - Repair drywall in bedroom damaged from water intrusion. Patch and paint all holes and cutouts in drywall to maintain the building envelope. - Deteriorating fascia boards, trim around dormer windows, and trim around chimney stack. Recommend replacement, paint, and sealant to prevent moisture from entering the structure - Re-seal all gaps visible at frieze boards with exterior grade silicone sealant to prevent moisture penetration REI 7-2 (8/09)

Page 12 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

- Evidence of moisture entering structure at north window. Seal all exterior holes, gaps, penetrations, etc.with an exterior-grade sealant to help prevent excess moisture and/or vermin entry.

- Repair drywall in bedroom damaged from water intrusion. Patch and paint all holes and cutouts in drywall to maintain the building envelope.

- Deteriorating fascia boards, trim around dormer windows, and trim around chimney stack. Recommend replacement, paint, and sealant to prevent moisture from entering the structure

REI 7-2 (8/09)

Page 13 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

REI 7-2 (8/09)

Page 14 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

- Re-seal all gaps visible at frieze boards with exterior grade silicone sealant to prevent moisture penetration

X

F. Ceilings & Floors Ceiling is made of drywall Comments: General Information: A structure should be constructed in such a fashion that natural rainfall and resulting surface water will not be permitted to gain entry into the structure. To accomplish this desired ability to prevent water penetration, the building must be constructed in a fashion to shed rainfall and provide positive drainage away from the structure. Complete waterproofing is not practical; therefore, some minor dampness will generally be experienced. This level of minor dampness, as a general statement, may not present a problem and may go undetected. A water penetration inspection procedure can take on many forms; however, this present procedure was limited to a cursory visual procedure. In this type of inspection procedure, the structure's habitable area is "walked" in an effort to observe and determine if obvious wetness, staining and/or damage was viewable on the wall, ceiling and/or floor surfaces which would be suggestive of water penetration. It is not the intent to identify water and/or damage existing inside surfaces and/or structural elements or the path of water through the structure. Potential and/or future water penetration problems will not be addressed.

X

G. Doors (Interior & Exterior) NOTE: DOORS SHOULD BE TRIMMED, WEATHER STRIPPED OR ADJUSTED AS NECESSARY TO SEAL PROPERLY AND OPERATE SMOOTHLY. KEYLESS LOCKS SHOULD BE USED ON ALL EXTERIOR DOORS FOR ENHANCED SAFETY. ATTACHED GARAGE MAN DOORS SHOULD BE EQUIPPED WITH AUTO CLOSING DEVICES.

Comments: All doors are functional REI 7-2 (8/09)

Page 15 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D X H. Windows

X

NOTE: ONLY A REPRESENTATIVE NUMBER OF ACCESSIBLE WINDOWS WERE CHECKED FOR OPERATION AT THIS INSPECTION. AS THERMALPANE WINDOWS LOSE THEIR VACUUM, MOISTURE MAY APPEAR, AND THEN DISAPPEAR, DEPENDING ON INSIDE AND OUTSIDE TEMPERATURE, AROMETRIC PRESSURE AND THE HUMIDITY LEVEL. THEREFORE WINDOWS ARE LISTED AS OBSERVED AT TIME OF INSPECTION ONLY, AND NO WARRANTY IS IMPLIED. HOLES DRILLED IN WINDOW FRAMES FOR ALARM SENSORS MAY VOID MANUFACTURER'S WARRANTIES. THE MANUFACTURER SHOULD BE CONSULTED TO THIS REGARD. AT A MINIMUM ALL ALARM SENSORS SHOULD BE SEALED.

Windows are made of vinyl Comments: All operated windows were functional.

Maintenance Issues: - Damaged frame observed in master bedroom. - Re-seal around windows at exterior as needed.

- Damaged frame observed in master bedroom.

X

I. Stairways (Interior & Exterior) Comments: None present.

REI 7-2 (8/09)

Page 16 of 36


Guardian Home Inspections I=Inspected I X

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D X J. Fireplace/Chimney NOTE: THE FLUE IS NOT TOTALLY VISIBLE. WE DO NOT USE VIDEO OR SPECIALTY EQUIPMENT TO INSPECT FOR LEAKS, CRACKS, SEPERATIONS OR DAMAGE IN THE FLUE. IT IS ALWAYS RECOMMENDED TO HAVE YOUR CHIMNEYS CLEANED EVERY SEASON TO PREVENT CREOSOTE BUILD-UP.

Location: Fireplace is located in the family room Prefabricated gas fueled fireplace Comments: Gas lighter was tested and performing normally.

Safety Concern: Damper missing required bracket that keeps damper from fully closing when fireplace is equipped with gas logs or a gas log lighter.

Gas lighter was tested and performing normally.

REI 7-2 (8/09)

Safety Concern: Damper missing required bracket that keeps damper from fully closing when fireplace is equipped with gas logs or a gas log lighter.

Page 17 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D X K. Porches, Balconies, Decks, and Carports

X

NOTE: PROPER FLASHING OF BALCONIES OR ROOF DECKS IS NOT VERIFIED.

Patio is functional

Maintenance Issue: Porch support beam trim is weathered. Recommend replacing trim and resealing to prevent moisture from compromising the integrity of beams.

Maintenance Issue: Porch support beam trim is weathered. Recommend replacing trim and resealing to prevent moisture from compromising the integrity of beams.

X

L. Other

Comments:

II. ELECTRICAL SYSTEMS

REI 7-2 (8/09)

Page 18 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

X

A. Service Entrance and Panels NOTE: PROPER BONDING OF GAS AND WATER LINES MAY NOT BE VERIFIED UNLESS OTHERWISE NOTED. A QUALIFIED, LICENSED ELECTRICIAN SHOULD BE ENGAGED TO VERIFY BONDING.

125 - amp 120/240 volt underground service Location(s): - Service Panel: South exterior - Sub-Panel: Garage Type of service wiring entering panel: #2 AWG Copper Comments: In this inspector's opinion, the service and sub-panels appear to be of acceptable standards at the time of inspection.

Deficiencies: FYI: Current standards require arc-fault circuit interrupting devices (AFCI's) to serve family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas. Although this home may have been built prior to this requirement and may be "grandfathered", a qualified electrician should be consulted to this regard. NOTE: Bedroom circuits are AFCI protected as was required at the time of construction.

REI 7-2 (8/09)

Page 19 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

X

B. Branch Circuits, Connected Devices, and Fixtures NOTE: LIGHTS AND EQUIPMENT ACTIVATED BY PHOTOCELL SWITCHES WERE NOT CHECKED. ALSO, LANDSCAPE AND EXTERIOR GROUNDS LIGHTING IS NOT INCLUDED IN THIS INSPECTION. ANTIQUATED WIRING SHOULD BE UPDATED; IT CREATES A POSSIBLE HAZARD. ONLY A REPRESENTATIVE NUMBER OF ACCESSIBLE OUTLETS ARE CHECKED. SECURITY SYSTEMS ARE NOT INCLUDED IN THIS INSPECTION. SMOKE DETECTION DEVICES SHOULD BE INSTALLED IN ALL ROOMS. EXTENSION CORDS SHOULD NEVER BE USED AS PERMANENT WIRING. HOMES CONSTRUCTED PRIOR TO 2008 WERE NOT EQUIPPED WITH CURRENTLY REQUIRED ARC FAULT PROTECTION AND TAMPER RESISTANT OUTLETS. A QUALIFIED ELECTRICIAN SHOULD BE CONSULTED WITH REGARD TO THE BENEFITS OF ADDING AFCI PROTECTION AND TAMPER RESISTANT RECEPTACLES.

• General Information: Recessed light fixtures that are installed in insulated ceilings can represent a fire hazard if they are not suitably rated for this application. Unfortunately, it is difficult to verify that the installation has been made safely during a home inspection. It is recommended that a licensed electrician be engaged to verify the safety of recessed lighting systems. Recessed lights should be fitted with bulbs suitable to this application. Otherwise, there is a risk of overheating and/or fire. • General Information: Exterior outlets, fixtures, junction boxes, etc. should be sealed against the wall to prevent excess moisture. Comments: Type of branch circuit wiring: Copper A representative number of receptacles and switches were tested and found to be performing as intended. All GFCI circuits were tested and reset AFCI breakers present on bedroom circuits, not tested Mis-labeled GFCI receptacle located in dining area. Missing label from receptacle at bar. Swap out faceplates to avoid confusion.

Deficiencies: Outdoor receptacle is damaged. Replace promptly.

REI 7-2 (8/09)

Page 20 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Outdoor receptacle is damaged. Replace promptly.

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS

REI 7-2 (8/09)

Page 21 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

X

A. Heating Equipment NOTE: AIR CONDITIONING UNITS ARE NOT CHECKED WHEN OUTSIDE TEMPERATURES ARE BELOW 60 DEGREES. WE RECOMMEND THE A.C. UNIT BE COMPLETELY SERVICED BEFORE EACH COOLING SEASON AND THE CONDENSATE DRAIN FLUSHED WITH A CHLORINE BLEACH EVERY 2 MONTHS DURING THE COOLING SEASON TO PREVENT CLOGGING. EVAPORATOR COILS ARE NOT OPENED WHEN SEALED.

Energy Source: Electricity Type of Cooling System(s): Central Unit condenser size: 3 ton. Filter size: 12x30x1 NOTE: HEAT PUMPS ARE NOT OPERATED WHEN OUTDOOR TEMPERATURE IS ABOVE 75 DEGREES. WE RECOMMEND THE HEATING SYSTEM BE COMPLETELY SERVICED BEFORE EACH HEATING SEASON. FILTERS SHOULD BE CHANGED AS NEEDED (AT LEAST EVERY 2 MONTHS). CHECKING HUMIDIFIERS, ELECTRIC AIR FILTERS AND PROPER AIRFLOW BALANCE IS NOT INCLUDED IN THIS INSPECTION.

Energy Source: Natural Gas Type of Heating System(s): Central FYI: Outdoor temperature was above 80 degrees. Unit was visually inspected only. - Unit inspected for evidence of carbon monoxide and gas leaks and are considered serviceable unless otherwise noted.

Deficiencies: No sediment trap observed at gas pipe entry to appliance. A sediment trap is designed to "catch" debris that might be in the gas line, preventing it from damaging the appliance. It is unclear if there is one located behind the finished wall.

REI 7-2 (8/09)

Page 22 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

No sediment trap observed at gas pipe entry to appliance. A sediment trap is designed to "catch" debris that might be in the gas line, preventing it from damaging the appliance. It is unclear if there is one located behind the finished wall.

X

X B. Cooling Equipment NOTE: AIR CONDITIONING UNITS ARE NOT CHECKED WHEN OUTSIDE TEMPERATURES ARE BELOW 60 DEGREES. WE RECOMMEND THE A.C. UNIT BE COMPLETELY SERVICED BEFORE EACH COOLING SEASON AND THE CONDENSATE DRAIN FLUSHED WITH A CHLORINE BLEACH EVERY 2 MONTHS DURING THE COOLING SEASON TO PREVENT CLOGGING. EVAPORATOR COILS ARE NOT OPENED WHEN SEALED.

Energy Source: Electricity Type of Cooling System(s): Central Unit condenser size: 3 ton. Filter size: 12x30x1 Comments: Central air conditioning unit was operational at time of inspection Thermostat is functional

Deficiency: Seal all possible water entry points into the house

REI 7-2 (8/09)

Page 23 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Seal all possible water entry points into the house

X

X C. Duct System, Chases, and Vents NOTE: THE PURPOSE OF THIS INSPECTION IS TO DETERMINE THE ABILITY OF THE DUCTWORK TO REASONBLY DISTRIBUTE CONDITIONED AIR THROUGHOUT THE HOME. DUCTWORK IS CHECKED FOR SIGNIFICANT VISIBLE DEFICIENCIES - MUCH OF WHICH MAY BE CONCEALED. THE FOLLOWING MAINTENANCE ADVICE IS OFFERED: DUCTWORK CONNECTIONS SHOULD BE SEALED TIGHTLY AT SUPPLY PLENUM AND REGISTER CONNECTIONS WITH APPROPRIATE MASTIC. DUCTWORK SHOULD NOT BE CRAMMED TOGETHER IN ATTICS SO AS TO REDUCE CONDENSATION AND ALL RUNS SHOULD HAVE AS FEW BENDS AS POSSIBLE AND BE SUPPORTED OFF THE ATTIC FLOOR. RETURN CHASES/DUCTS SHOULD BE ADEQUATELY SIZED, SEALED AND INSULATED FOR OPTIMAL SYSTEM PERFORMANCE. THE DUCTS AND VENTS ARE CONSIDERED TO BE SERVICEABLE UNLESS OTHERWISE NOTED BELOW.

Ductwork properly supported, insulated, and performing as intended Registers are functional Filters are located below heater

Deficiency: Filters are dirty. Replace often (every 2 months) as accumulated dirt can damage the evaporator coils, leading to system failure.

REI 7-2 (8/09)

Page 24 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Ductwork properly supported, insulated, and performing as intended

IV. PLUMBING SYSTEMS X

A. Water Supply System and Fixtures NOTE: PIPES AND PLUMBING IN WALLS, IN OR UNDER CONCRETE SLABS OR CONCEALED BY PERSONAL EFFECTS ARE NOT INSPECTED. THE QUALITY, CONDITION OR PURIFICATION OF WATER IS NOT INCLUDED IN THIS INSPECTION. THE ONLY TRUE WAY TO TEST FOR PLUMBING LEAKS IS BY HYDRO-STATIC PRESSURE TEST WHICH IS BEYOND THE SCOPE OF THIS INSPECTION AND IS STRONGLY RECOMMENDED, ESPECIALLY IN OLDER HOMES. NOTE: SUPPLY PLUMBING IN ATTICS OR CRAWL SPACES SHOULD BE INSULATED. LAUNDRY CONNECTIONS (INCLUDING DRAIN) ARE VISUALLY INSPECTED ONLY. SHOWER STALLS ARE VULNERABLE TO LEAKS AND ARE TESTED BY RUNNING THE SHOWER FOR A SHORT PERIOD, TYPICALLY 30-45 MINUTES AND LEAKS MAY BE PRESENT THAT ARE NOT DISCOVERED DURING THE BRIEF TIME PERIOD OF THE INSPECTION. ALL BATH AND SHOWER FIXTURES SHOULD BE CAULKED AGAINST THE WALL TO PREVENT LEAKS.

Location of Water Meter: Front of structure, northeast side of driveway. Location of Main Water Supply Valve: Front of structure, northeast side of driveway, under "blue" cap. Static Water Pressure Reading: approximately 60 psi. Comments: Water had been off for an unknown period. It was turned on at time of inspection, turned off at end of inspection.

REI 7-2 (8/09)

Page 25 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Static Water Pressure Reading: Approx. 60psi

X

B. Drains, Wastes, and Vents NOTE: IF BATH TRAPS ARE NOT PRESENT OR READILY ACCESSIBLE, THEY ARE NOT INSPECTED. BATH TRAPS WITH ACCESS DOORS ARE RECOMMENDED BEHIND ALL TUBS/SHOWERS TO ALLOW FOR INSPECTION OF LEAKS, PROPER PLUMBING CONFIGURATION, WOOD DESTROYING INSECT ACTIVITY, ETC. WE RECOMMEND OLDER DRAIN/WASTE PIPING BE VIDEO INSPECTED AND/OR PRESSURE TESTED.

General Information: A flush and drain test is performed; i.e. tubs and sinks are filled then drained simultaneously while flushing commodes multiple times. The system is considered serviceable unless otherwise noted below. Comments: System was performing as intended at the time of inspection.

REI 7-2 (8/09)

Page 26 of 36


Guardian Home Inspections I=Inspected I X

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D X C. Water Heating Equipment NOTE: TEMPERATURE PRESSURE RELIEF VALVES (TPR) VALVES ARE NOT TESTED DUE TO POTENTIAL LEAKAGE AND SHOULD BE REPLACED EVERY 2 YEARS. WATER HEATERS SHOULD BE DRAINED REGULARLY AS PART OF GENERAL MAINTENANCE. THE WATER HEATER IS CONSIDERED SERVICEABLE UNLESS OTHERWISE NOTED OR HIGHLIGHTED BELOW.

Location of Water Heater: Garage Energy Source: Gas Capacity: 40 gallon Appears to be approximately 8 years old. Comments:

Priority Items: - The water heater shows evidence of rust and corrosion at pipe connections. - The pilot ignition source is missing; unable to test burner. - No sediment trap visible at appliance connection. Unable to determine whether it is located behind finished wall or not. - The pilot light igniter is missing. Unable to light burners and test for proper combustion. - No sediment trap observed at gas pipe entry to appliance. A sediment trap is designed to "catch" debris that might be in the gas line, preventing it from damaging the appliance. It is unclear if there is one located behind the finished wall.

REI 7-2 (8/09)

Page 27 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

- The water heater shows evidence of rust and corrosion at pipe connections. - The pilot ignition source is missing; unable to test burner. - No sediment trap visible at appliance connection. Unable to determine whether it is located behind finished wall or not.

Pilot light igniter is missing.

X

- No sediment trap observed at gas pipe entry to appliance. A sediment trap is designed to "catch" debris that might be in the gas line, preventing it from damaging the appliance. It is unclear if there is one located behind the finished wall.

D. Hydro-Massage Therapy Equipment Comments: None present.

REI 7-2 (8/09)

Page 28 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

V. APPLIANCES A. Dishwasher

X

Comments: Unit was operated in normal mode and showed no evidence of visible leaks or other issues unless otherwise noted.

B. Food Waste Disposer

X

Comments: The food disposer was operated and is considered to be serviceable unless otherwise noted.

C. Range Exhause Vent

X

• Comments: • Exhaust vented through overhead microwave then out to exterior. • Fan operated normally at all speeds. • Appears to be performing intended function unless otherwise noted. X

D. Ranges, Cooktops, and Ovens Comments:

Safety Issue: - Unit was not lit due to reported gas leak from client, confirmed by gas company. - Install anti-tip device on back of oven to prevent injury from a "curious climber".

REI 7-2 (8/09)

Page 29 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

- Install anti-tip device on back of oven to prevent injury from a "curious climber".

E. Microwave Oven

X

NOTE: MICROWAVE OVENS ARE TESTED FOR FUNCTIONALITY ONLY. RADIATION LEAKAGE IS BEYOND THE SCOPE OF THIS HOME INSPECTION.

Comments: Microwave operated normally at time of inspection unless otherwise noted. X

F. Trash Compactor Comments: None present.

X

G. Mechanical Exhaust Vents and Bathroom Heaters NOTE: BATHROOM EXHAUST FANS SHOULD TERMINATE DIRECTLY TO THE EXTERIOR. GAS WALL HEATERS SHOULD BE REMOVED OR REPLACED AS THEY ARE NO LONGER CONSIDERED SAFE.

Comments: All bath exhaust fans operated normally unless otherwise noted.

REI 7-2 (8/09)

Page 30 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

X

H. Garage Door Operator(s) Door Type: Sectional door. Comments: General Information: Automatic garage door operators are operated by switch in garage and remote (if available), the automatic reverse sensors (photo-eye and pressure-applied) safety devices are tested. Garage doors are performing as intended unless otherwise noted. Automatic garage door operator (left garage door) was functioning as intended at the time of inspection. Right garage door was manually operated and appears to be functioning as intended. Recommend to secure door lock on unit operated by opener in the "unlocked" position for convenience and consistent entry.

X

I. Doorbell and Chimes Comments: Doorbell operated normally.

X

J. Dryer Vents NOTE: DRYER VENTS THAT VENT UP THROUGH THE ROOF REQUIRE PERIODIC CLEANING AND SHOULD TERMINATE THROUGH A BACKDRAFT DAMPER.

Comments: Dryer vent terminates at north-side roof exterior. Backdraft damper is installed and functional. Continue to monitor and clean as necessary.

REI 7-2 (8/09)

Page 31 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

Dryer vent terminates at north-side roof exterior. Backdraft damper is installed and functional. Continue to monitor and clean as necessary.

VI. OPTIONAL SYSTEMS X

A. Lawn and Garden Sprinkler Systems Comments: None present.

X

B. Swimming Pools, Spas, Hot Tubs, and Equipment

Comments: None present. X

C. Outbuildings Materials:

Comments: None present.

REI 7-2 (8/09)

Page 32 of 36


Guardian Home Inspections I=Inspected I

NI=Not Inspected

123 Main Street, Austin, Texas NP=Not Present

D=Deficient

NI NP D

D. Outdoor Cooking Equipment

X

Comments: None present. X E. Gas Supply Systems

X

NOTE: PRESSURE TESTING OF GAS LINES IS SPECIFICALLY EXCLUDED FROM THIS INSPECTION. A QUALIFIED PLUMBER OR LOCAL UTILITY REPRESENTATIVE SHOULD BE ENGAGED TO PERFORM SUCH TESTING.

Comments:

SAFETY ISSUE: Reported gas leak at oven/stovetop connections. Gas supply at this appliance was turned off by gas company at time of inspection. Full evaluation and correction of gas supply system highly recommended. X

F. Private Water Wells (A coliform analysis is recommended) Comments: None present.

X

G. Private Sewage Disposal (Septic) Systems Comments: None present.

X

H. Whole-House Vacuum Systems Comments: None present.

X

I. Other Built-in Appliances Comments: None present.

REI 7-2 (8/09)

Page 33 of 36


Guardian Home Inspections

123 Main Street, Austin, Texas

Report Summary Report Summary

STRUCTURAL SYSTEMS Page 6 Item: B

Grading & Drainage

Page 9 Item: C

Roof Covering Materials

Maintenance Issue: Downspout missing extension and/or splash block. Rainwater is pooling at corner of foundation, which can lead to future issues. Extend downspout 4-6 feet away from foundation wall or install splash block to divert water away from foundation. Maintenance Issues: - Evidence of north and south side ponding due to inadequate shedding of rainwater from change in roof slope. Recommend installing gutters to prevent water from compromising the foundation backfill. - Evidence of water penetration behind gutters. It's possible gutters were installed as a result of such damage, or problem is because of faulty gutters. Monitor gutter system performance at next rainfall. - Seal penetrations at satellite dish on south side of roof to prevent moisture penetration. - Granules observed in gutter system. Clogged gutters could impede gutter performance, leading to leaks. I recommend cleaning of the gutters. Shingle surface immediately above them may have been compromised, evident by granule loss. Continue to monitor.

- Missing drip edge at eaves. A drip edge can aid in the prevention of water being wicked up by the vulnerable fascia. Page 11 Item: D Roof Structure & Maintenance Issue: Nails should be removed from attic Attic access door frame to allow for a complete seal of attic door, preventing dangerous exhaust gases from entering the attic. Page 15 Item: E Walls (Interior and Maintenance Issues: Exterior) - Evidence of moisture entering structure at north window. Seal all exterior holes, gaps, penetrations, etc.with an exterior-grade sealant to help prevent excess moisture and/or vermin entry. - Repair drywall in bedroom damaged from water intrusion. Patch and paint all holes and cutouts in drywall to maintain the building envelope. - Deteriorating fascia boards, trim around dormer windows, and trim around chimney stack. Recommend replacement, paint, and sealant to prevent moisture from entering the structure

REI 7-2 (8/09)

- Re-seal all gaps visible at frieze boards with exterior grade silicone sealant to prevent moisture penetration Page 34 of 36


Guardian Home Inspections Page 16 Item: H Windows

123 Main Street, Austin, Texas Maintenance Issues: - Damaged frame observed in master bedroom.

- Re-seal around windows at exterior as needed. Page 17 Item: J Fireplace/Chimney Safety Concern: Damper missing required bracket that keeps damper from fully closing when fireplace is equipped with gas logs or a gas log lighter. Page 18 Item: K Porches, Maintenance Issue: Porch support beam trim is Balconies, Decks, weathered. Recommend replacing trim and resealing to and Carports prevent moisture from compromising the integrity of beams.

ELECTRICAL SYSTEMS Page 19 Item: A Service Entrance and Panels

Page 21 Item: B Branch Circuits, Connected Devices, and Fixtures

Deficiencies: FYI: Current standards require arc-fault circuit interrupting devices (AFCI's) to serve family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas. Although this home may have been built prior to this requirement and may be "grandfathered", a qualified electrician should be consulted to this regard. NOTE: Bedroom circuits are AFCI protected as was required at the time of construction. Deficiencies: Outdoor receptacle is damaged. Replace promptly.

HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS Page 23 Item: A Heating Equipment Deficiencies: No sediment trap observed at gas pipe entry to appliance. A sediment trap is designed to "catch" debris that might be in the gas line, preventing it from damaging the appliance. It is unclear if there is one located behind the finished wall. Page 24 Item: B Cooling Equipment Deficiency:

Page 25 Item: C Duct System, Chases, and Vents

Seal all possible water entry points into the house Deficiency: Filters are dirty. Replace often (every 2 months) as accumulated dirt can damage the evaporator coils, leading to system failure.

PLUMBING SYSTEMS

REI 7-2 (8/09)

Page 35 of 36


Guardian Home Inspections Page 28 Item: C Water Heating Equipment

123 Main Street, Austin, Texas Priority Items: - The water heater shows evidence of rust and corrosion at pipe connections. - The pilot ignition source is missing; unable to test burner. - No sediment trap visible at appliance connection. Unable to determine whether it is located behind finished wall or not. - The pilot light igniter is missing. Unable to light burners and test for proper combustion. - No sediment trap observed at gas pipe entry to appliance. A sediment trap is designed to "catch" debris that might be in the gas line, preventing it from damaging the appliance. It is unclear if there is one located behind the finished wall.

APPLIANCES Page 30 Item: D Ranges, Cooktops, Safety Issue: and Ovens - Unit was not lit due to reported gas leak from client, confirmed by gas company. - Install anti-tip device on back of oven to prevent injury from a "curious climber".

OPTIONAL SYSTEMS Page 33 Item: E Gas Supply Systems

REI 7-2 (8/09)

SAFETY ISSUE: Reported gas leak at oven/stovetop connections. Gas supply at this appliance was turned off by gas company at time of inspection. Full evaluation and correction of gas supply system highly recommended.

Page 36 of 36

Sample HI Report  

Guardian Home Inspections: Sample Home Inspection Report