KE-Wire (Cable) General rules

Double suspension

2’6

2 rows of SafeClips

x

ma

1

20”

Mount horizontal cables (typically 1 3/8” above top of KE fabric duct). Apply tension of max. 45 lbs and then tighten wire locknut. A turnbuckle turned from fully open to fully tensioned will shorten the cable by approx. 3 2/8”. For cables longer than 50 ft we recommend turn-buckle at each end.

2”

’6 16

20

4

Please find information on delivery and installation in the box labelled INFO.

Clamp is mounted on inlet socket.

Delivery Note

KE-label (always pointing upper-most)

3

The KE fabric duct is mounted on to the cable by SafeClips in pairs. Do not use the fan to ”shoot” the textile duct into position.

The length of the SafeClips is stated on the delivery note. Standard clip length is ½ x Ø + 1 3/8”.

KE-------#Office 1 ------------------1 std KE-Wire

Room reference Suspension type

Ø + 1 3/8”

cable

2

(inflated - fan on)

(not inflated - fan off)

Wire Strap-up is mounted to the ceiling; the length of which is adjustable by the wire locknut. Adjust strap-up to correct length prior to mounting the KE fabric duct.

0980009-US


Begin by comparing the contents of the box against the delivery note (packing list).

Single suspension 1 row of SafeClips

20”

4

Clamp is mounted on inlet socket.

2”

You will need: Cable cutter, adjustable spanner. Not included: Screws/ hooks for wall and ceiling fixing.

x

ma

’6”

6 .1

KE-label (always pointing upper-most)

Ceiling fixing (hook or similar)----------------Crimp (pre-fixed)----------------------------------

2’6

Wire Strap-up (Ø1/8”)---------------------------

2

Wire Strap-up is mounted to the ceiling; the length of which is adjustable by the wire locknut. Adjust strap-up to correct length prior to mounting the KE fabric duct.

Wire locknut-------------------------------------Plastic snap hook--------------------------------SafeClip-----------------------------------Horizontal cable (Ø1/8”)---------Wire locknut----------------

Turnbuckle------Mount horizontal cables (typically 1 3/8” above top of KE fabric duct). Apply tension of max. 45 lbs and then tighten wire locknut. A turnbuckle turned from fully open to fully tensioned will shorten the cable by approx. 3 2/8”. For cables longer than 50 ft we recommend a turnbuckle at each end.

cable

3

The KE fabric duct is mounted on to the cable by SafeClips, one by one. Do not use the fan to ”shoot” the textile duct into position.

(inflated - fan on)

10/2013

Max: Ø x 1.5 + 1 3/8”

---------------------------Wall fixing (e.g. hook)

1

Ø + 1 3/8”

-------KE fabric duct

(not inflated - fan off)